9. Maintenance

9.1. Inspection

9.1.1. Pressure reducing valve

1. Close shutoff valve on outlet
2. Check outlet pressure using a pressure meter when there 

is zero through-flow
• If the pressure is increasing slowly, the valve may be 

dirty or defective. In this instance, carry out servicing 
and cleaning

3. Slowly open shutoff valve on outlet
9.1.2. Check valve

1. Close shutoff valve on inlet
2. Remove test cockcovers of check valve
3. If not watertight, close shutoff valve on outlet
4. Unscrew sealing plug
5. Remove and exchange check valve
6. Mount sealing plug

• Check thread

7. Reassemble in reverse order
8. Slowly open shut off valves on inlet and outlet
9.1.3. Safety valve

1. Actuate lifting device
2. Release lifting device
• Shut-off valve closes
• available water flows completely off
Malfunction:
1. Actuate lifting device multiple times, if necessary initiate 

repairs

9.2. Maintenance

9.2.1. Pressure reducing valve

1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Loosen slotted screw

• Do not remove slotted screw

5. Slacken tension in compression spring

• Turn adjustment handle counter clockwise (-) until it 

does not move any more

6. Unscrew spring bonnet

• Use double ring wrench ZR06K

7. Remove slip ring
8. Remove valve insert with a pair of pliers
9. Unscrew filter bowl

• Use double ring wrench ZR06K

10. Remove slotted ring
11. Check that sealing ring, edge of nozzle and slotted ring 

are in good condition, and if necessary replace the entire 
valve insert

12. Remove filter, clean and reinsert
13. Place O-ring onto filter bowl
14. Reassemble in reverse order

15. Set outlet pressure and adjust setting scale
9.2.2. Check valve

1. Close shutoff valve on inlet
2. Close shutoff valve on outlet
3. Release pressure on outlet side (e.g. through water tap)
4. Unscrew sealing plug
5. Remove and exchange check valve
6. Mount sealing plug

• Check thread

7. Slowly open shut off valves on inlet and outlet

9.3. Adjusting the setting scale

If the adjustment knob is removed, this setting is lost. A new 
setting can be achieved using a pressure gauge.
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Fit pressure gauge
5. Loosen slotted screw

• Do not remove slotted screw

6. Slowly open shutoff valve on inlet
7. Set desired outlet pressure (e.g. 4 bar)
8. Align scale (e.g. 4) in middle of viewing window
9. Retighten slotted screw
10. Slowly open shutoff valve on outlet

DIN 1988, Part 8 specifies that the following operations 
be carried out regularly. 
A scheduled maintenance scheme is recommended.

Interval: once a year

Interval: once a year

Frequency: every 6 month

Frequency: every 1-3 years (depending on local 
operating conditions)
To be carried out by an installation company

Caution !

There is a spring in the spring bonnet. It may cause 
injuries if the spring is derailing. 
• Make sure tension in compression spring is slak-

kened!

Press in diaphragm with finger before inserting slip ring
Screw in filter cup hand-tight (up to max. 18Nm)

To be carried out by an installation company

Содержание SG160S

Страница 1: ...Istruzioni di montaggio Anleitung zum späteren Gebrauch aufbewahren Keep instructions for later use Conserver la notice pour usage ultérieur Conservare le istruzioni per uso successivo Sicherheits Gruppe Safety Group Vanne de sécurité combinée Gruppo di sicurezza 32303590 001 ...

Страница 2: ...0 23 Disposal 11 24 Troubleshooting 11 25 Spare Parts 12 26 Accessories 12 F 27 Consignes de sécurité 13 28 Description fonctionelle 13 29 Mise en oeuvre 13 30 Caractéristiques 13 31 Contenu de la livraison 14 32 Variantes 14 33 Montage 14 34 Mise en service 14 35 Maintenance 15 36 Matériel en fin de vie 16 37 Défaut recherche de panne 16 38 Apercu pièces 17 39 Accessoires 17 I 40 Avvertenze di si...

Страница 3: ...einer Membrankraft wirkt die Kraft einer Sollwertfeder entgegen Der Eingangsdruck wirkt weder im öffnenden noch im schließenden Sinn Druckschwankungen auf der Vorder seite beeinflussen deshalb den Hinterdruck nicht Der Rück flussverhinderer hat einen beweglichen Ventilkegel der bei Durchfluss gegen eine Federkraft in Offenstellung gedrückt wird Das nachgeschaltete Sicherheitsventil ist ein direkt ...

Страница 4: ...allieren Die Abblaseleitung muss in Größe des Sicherheitsventil Austrittsquerschnitt ausgeführt sein und darf nicht mehr als 2 Bögen aufweisen und höchstens 2 m lang sein Werden aus zwingenden Gründen mehr Bögen oder eine größere Länge erforderlich so muß die gesamte Abblase leitung eine Nennweite größer ausgeführt werden Mehr als 3 Bögen sowie eine Länge über 4 m sind unzulässig Die Abblaseleitun...

Страница 5: ...Zustand überprüfen falls erforderlich Ventileinsatz komplett auswechseln 12 Sieb herausnehmen reinigen und wieder einstecken 13 O Ring auf Siebtasse stecken 14 Montage in umgekehrter Reihenfolge 15 Federhaube mit Doppelringschlüssel einschrauben 16 Hinterdruck einstellen und Einstellskala justieren 9 2 2 Rückflussverhinderer 1 Absperrarmatur eingangsseitig schließen 2 Absperrarmatur ausgangsseitig...

Страница 6: ...nd SG160SD Tropft Während der Aufheizung des Wasserer wärmers kein Fehler normale Funktion Tropft ständig durch Verschmutzung Anlüftgriff mehrmals betätigen dadurch werden Schmutzpartikel ausgespült oder ggf austau schen Rückflussverhinderer schließt im Vorderdruckbereich nicht dicht ab Druckanstieg im Vorderdruckbereich Rückflussverhinderer austauschen Dichtflächen verschmutzt oder verschlissen R...

Страница 7: ...üfnummer TÜV SV 617 1 W p Bauteilprüfnummer TÜV SV 700 1 2 3 4 W p Bauteilprüfnummer TÜV SV 700 1 W p 6 bar 1 2 A152 1 2AA 3 4 1 A152 3 4AA 8 bar 1 2 A152 1 2AB 3 4 1 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 1 A152 3 4AC gültige Prüfnummer 2 VerschlussstopfenmitO Ring R1 4 5 Stück S06K 1 4 3 Ablauftrichter TA160S 4 Einsteckrückflussverhinderer 3 4 2110200 5 Dichtringsatz 1 2 0901443 10 Stück 3 4 09014...

Страница 8: ...against the force of an adjustment spring The inlet pressure has no influence on either opening or closing of the valve and therefore inlet pressure fluctua tions have no influence on the outlet pressure The check valve has a movable valve disc which pushes against a spring when flow occurs The downstream safety valve is a direct operating safety valve That is the opening force operates against th...

Страница 9: ...afety group and the drain guide The discharge line must be performed to the size of the safety valve outlet diameter and may not have more than 2 elbows and or be longer than 2m If for compelling reasons more elbows or a greater length becomes necessary then the entire discharge line must be designed to a larger nominal width More than 3 elbows as well as lengths over 4m are not permitted The disc...

Страница 10: ...f nozzle and slotted ring are in good condition and if necessary replace the entire valve insert 12 Remove filter clean and reinsert 13 Place O ring onto filter bowl 14 Reassemble in reverse order 15 Set outlet pressure and adjust setting scale 9 2 2 Check valve 1 Close shutoff valve on inlet 2 Close shutoff valve on outlet 3 Release pressure on outlet side e g through water tap 4 Unscrew sealing ...

Страница 11: ...eating up of the water heater no error normal function Continually drips from soiling Actuate lifting grip multiple times so that dirt particles are flushed out or replace as neces sary Check valve does not close off tightly in the front pressure area Pressure increase in the front pres sure area Replace check valve Seal surfaces dirty or worn Replace check valve Too little or no water pressure Cu...

Страница 12: ...00 1 2 3 4 W p Approval No TÜV SV 700 1 W p 6 bar 1 2 A152 1 2AA 3 4 1 A152 3 4AA 8 bar 1 2 A152 1 2AB 3 4 1 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 1 A152 3 4AC valid approval No 2 Blanking plug with O ring R1 4 5 pcs S06K 1 4 3 Discharge tundish TA160S 4 Check valve disc complete 3 4 2110200 5 Sealing ring 10 pcs 1 2 0901443 3 4 0901444 1 0901445 6 Spring bonnet complete with setting scale 1 2 1 09...

Страница 13: ... à dire qu un ressort avec une force de valeur de consigne s oppose à la force d une membrane La pression d alimentation n agit sur la soupape ni dans un sens de fermeture ni dans un sens d ouverture Des variations de pression à l entrée n ont pas d effet sur la pression à la sortie à cause de cela Le clapet de non retour a un cône mobile qui lors de l écoulement de l eau est poussé contre la forc...

Страница 14: ...nnecté directe ment avec la vanne de sécurité combinée il faut installer un tuyau de purge entre la vanne de sécurité combinée et l entonnoir de vidange Le tuyau de purge doit posséder au moins le diamètre de la sortie de la soupape de sécurité il ne doit pas dépasser les 2 m et ne pas avoir plus de 2 coudes Si des raisons impératives imposent plus de coudes l ensemble du tuyau de purge doit être ...

Страница 15: ...ensemble garniture de soupape 12 Retirer le filtre de remplacement le nettoyer et le replace 13 Enfoncer l anneau torique sur le pot de tamisage 14 Montage dans l ordre inverse 15 Réglé la pression aval et calibré l échelle de réglage 9 2 2 Clapet anti retour 1 Fermer le robinet d isolement en amont 2 Fermer le robinet d isolement en aval 3 Dépressuriser le côté sortie par ex en ouvrant la vanne d...

Страница 16: ... la mise en service du chauffe eau pas de panne fctmt normal goutte en permanence à cause d un encrassage actionner plusieurs fois le dispositif de purge ce qui rince les particules de saleté Le clapet de non retour dans la partie de l avant pression ne ferme pas de manière étanche augmentation de l avant pression Changer le clapet de non retour les joints sont encrassés ou usés Changer le clapet ...

Страница 17: ...17 1 2 3 4 W p Numéro de contrôle de composant TÜV SV 617 1 W p Numéro de contrôle de composant TÜV SV 700 1 2 3 4 W p Numéro de contrôle de composant TÜV SV 700 1 W p 6 bar 1 2 A152 1 2AA 3 4 1 A152 3 4AA 8 bar 1 2 A152 1 2AB 3 4 1 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 1 A152 3 4AC Numéro de contrôle valable 2 Bouchon de fermeture avec joint torique R1 4 5 pièces S06K 1 4 3 Cône d écoulement TA160...

Страница 18: ...e delle forze Ciò significa che la forza di una molla di regolazione agisce contro la forza di un diaf ramma La pressione d ingresso non influisce sulla valvola né per l apertura né per la chiusura Le fluttuazioni della pres sione d ingresso non influenzano pertanto la pressione d uscita La valvola antiriflusso ha un cono mobile che viene premuto durante il flusso in posizione aperta contro una fo...

Страница 19: ...ndotta di scarico va realizzata con la dimensione del diametro di uscita della valvola di sicurezza non deve presentare più di due curve e deve essere lunga al massimo 2 m Se sono indispensabili più curve o una lunghezza maggiore allora l intera condotta di scarico va realizzata con un ampiezza nominale maggiore Non sono comunque consentite più di 3 curve ed una lunghezza maggiore di 4 m La condot...

Страница 20: ... inserirlo di nuovo 13 Mettere l anello circolare sulla tazza a vaglio 14 Il montaggio ha luogo nella sequenza inversa 15 Impostare la pressione posteriore e registrare la scala graduata di regolazione 9 2 2 Valvola di ritegno 1 Chiudere il raccordo di blocco sul lato entrata 2 Chiudere il raccordo di blocco sul lato di uscita 3 Depressurizzare il lato di uscita per es tramite il rubi netto dell a...

Страница 21: ...hiude ermeticamente nel settore di pressione di entratab Aumento di pressione nel settore di pres sione in entrata Sostituire il dispositivo anti riflusso Le superfici di tenuta sono sporche o con sumate Sostituire il dispositivo anti riflusso La pressione dell acqua è poca oppure inesistente Armature di blocco davanti o dietro il gruppo di sicurezza non interamente aperte Aprire completamente i r...

Страница 22: ...mero di omologazione componente TÜV SV 617 1 W p Numero di omologazione componente TÜV SV 700 1 2 3 4 W p Numero di omologazione componente TÜV SV 700 1 W p 6 bar 1 2 A152 1 2AA 3 4 1 A152 3 4AA 8 bar 1 2 A152 1 2AB 3 4 1 A152 3 4AB 10 bar 1 2 A152 1 2AC 3 4 1 A152 3 4AC Numero di omologazione valido 2 Tappo di chiusura con guarni zione O ring R1 4 5 pezzi S06K 1 4 3 Imbuto di scarico TA160S 4 Ins...

Страница 23: ...MU1H 1346GE23 R1014 23 Honeywell GmbH I ...

Страница 24: ... 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Represen tative Honeywell GmbH MU1H 1346GE23 R1014 Subject to change 2014 Honeywell GmbH ...

Страница 25: ...neywell GmbH bar 6 8 10 4 2 0 5 6 4 8 1 3 8 1 7 2 2 4 5 3 1 9 1 2 bar 6 8 10 4 2 0 bar 6 8 10 4 2 0 6 4 5 3 1 9 2 1 7 8 bar 6 8 10 4 2 0 9 10 11 11 12 13 2 4 5 3 1 9 2 2 bar 6 8 10 4 2 0 5 4 6 1 3 9 3 7 9 10 8 1 3 4 9 4 6 5 ...

Страница 26: ...MU1H 1346GE23 R1014 Honeywell GmbH 1 3 5 2 2 4 12 1 13 bar 6 8 10 4 2 0 M07M ZR06K VSTM VST06 A VST06 B 2 6 7 5 8 9 10 1 3 5 2 2 4 12 2 ...

Отзывы: