S9240F1004 MODULATING HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

69-2088—01

12

— The IFC verifies the limit and rollout switch circuits are 

closed.

— The IFC verifies the low and high pressure switch 

circuits are open.

— The IFC energizes the inducer and adjusts to the 

ignition firing rate speed.

— When the low pressure switch closes, Prepurge 

begins.

— After the completion of Prepurge, the HSI energizes 

for the Igniter Warm-up Period.

— When the Igniter Warm-up Period expires, the gas 

valve energizes, the Inducer remains at the ignition 

firing rate, gas flow begins, and the Trial for Ignition 

(TFI) begins. 

• During TFI, the HSI remains energized.
• After TFI, the HSI de-energizes, the gas valve 

remains energized, and the Inducer remains at the 

ignition firing rate for the flame recognition period.

— The heat fan on delay is started upon entering Trial for 

Ignition.

— When flame is sensed during Trial for Ignition, the IFC 

de-energizes the HSI.

— When the ignition stabilization delay expires, the IFC 

moves to the ignition firing rate.

— After successful lightoff, the IFC moves to the target 

firing rate (see note below) based on the current 

thermostat inputs and the selected operating 

sequence.

NOTES: Unless the special Lennox modulating sequence is 

selected (SW1 is OFF and SW2 is ON), there are 

three target firing rates:

1.

Low Fire Rate, which is about 40% of appliance 

full rate.

2.

Mid Fire Rate, which is about 70% of appliance 

full rate.

3.

High Fire Rate, which is about 100% of appliance 

full fire rate. 

Normal Heat Mode - Conventional 2-Stage 

Thermostat (standard 2-stage operation 

selected)

Refer to Fig. 9-14 beginning on page 19 for the operating 

sequence diagrams.

Call for Stage 1 Heat

A call for 1st stage heat is signaled by the thermostat closing 

the contacts between R and W1. 

Upon a call for 1st stage heat:

— After a successful Light Off and expiration of the 

ignition stabilization period, the Inducer adjusts to the 

mid firing rate speed.

— After expiration of the heat fan on delay, the IFC 

adjusts the circulator to the appropriate speed (CFM).

— If a discharge air sensor is present, the circulator 

adjusts to maintain the target discharge air 

temperature.

— The IFC remains in this state until the thermostat 

generates a 2nd stage call for heat or the 1st stage 

call for heat is removed.

Call for Stage 2 Heat

A call for 2nd stage heat is signaled by the thermostat 

simultaneously closing the contacts R, W1, and W2.

On the first call for 2nd stage heat, the request is ignored until 

the 2nd stage recognition delay expires.

When a 2nd stage recognition delay expires (and on 

subsequent calls for 2nd stage heat in the same heating 

cycle), the following occurs:

— The Inducer adjusts to the high firing rate speed.

— The IFC adjusts the circulator speed to the appropriate 

speed (CFM).

— If a discharge air sensor is present, the circulator 

adjusts to maintain the target discharge air 

temperature.

— The IFC remains in this state until the 2nd stage call 

for heat or the 1st stage call for heat is removed.

2nd Stage Heat Satisfied, Call for 1st Stage Heat 
Remains

When the 2nd stage heat request is removed and there is still 

a demand for heat on the 1st stage, the following occurs:

— The Inducer adjusts to the mid firing rate speed.

— The IFC adjusts the circulator speed to the appropriate 

speed (CFM).

— If a discharge air sensor is present, the circulator 

adjusts to maintain the target discharge air 

temperature.

— The IFC remains in this state until the thermostat 

generates a 2nd stage call for heat or the 1st stage 

call for heat is removed.

Call for 1st Stage Heat Satisfied

When the 1st stage is satisfied:

— The gas valve de-energizes.

— When the loss of flame is detected, the Postpurge and 

circulator fan off delay timings begin.

— When the Postpurge time completes, the inducer 

de-energizes.

— When the circulator fan off delay expires, the circulator 

de-energizes.

1st and 2nd Stages Satisfied Simultaneously

When both 1st and 2nd stages are satisfied simultaneously:

— The gas valve de-energizes.

— When the loss of flame is detected, the Postpurge and 

circulator fan off delay timings begin.

— When the Postpurge time completes, the inducer 

de-energizes.

— When the circulator fan off delay expires, the circulator 

de-energizes.

Lennox Modulating Mode - Conventional 

2-Stage Thermostat (special Lennox 

sequence selected)

The Lennox modulating firing rate is proprietary to Lennox. 

Contact your Lennox representative for specific details.

Содержание S9240F1004

Страница 1: ...Honeywell amplified gas air gas valve Controls a 3 phase 120 Vac inducer motor Fasco Model 92B1 or other with identical voltage frequency curve and blower assembly based on heat demand and other parameters Controls the Regal Beloit 3 0 ECM circulator motor and blower based on defined appliance CFM profiles and or a discharge air sensor signal Controls single stage or 2 stage cooling equipment The ...

Страница 2: ... Auto Restart Delay 60 minutes after Soft Lockout Ignition Trials Five total four retries if flame is not sensed on the first trial Ignition Recycles 4 total 3 recycles if flame lost on first trial Second Stage Recognition Delay 30 seconds only on First Call for High Fire on a Call for Heat Second Stage ON Delay 7 or 12 minutes when used with a single stage thermostat see Table 5 on page 8 default...

Страница 3: ...equipment damage or malfunction If the integrated furnace control must be mounted near water or moisture provide suitable waterproof enclosure Location The integrated furnace control is mounted on a panel within the circulator compartment of the furnace The location must provide Access to the field wiring terminals Operating ambient temperatures between 40 F and 175 F 40 C and 79 C Relative humidi...

Страница 4: ... screw Outdoor Sensor E4 Not used Discharge Air Sensor optional If used Discharge air sensor Straight Spade Quick Connect Flame Sense E42 Flame signal input 12 pin connector male terminals Main Harness J2 Main valve pressure switches rollout limit chassis ground and 24 Vac 6 pin connector male terminals Circulator Motor P79 Motor serial control interface and furnace size select input Table 2 Wirin...

Страница 5: ...ation disabled factory default CUT Harmony III and dehumidifying operation enabled M28148 EAC HUM HSI 3 1 1 7 4 10 6 9 3 12 15 17 16 14 18 19 L1 1 11 9 8 10 13 12 4 3 6 1 P80 1 2 3 4 5 6 7 2 NEUTRALS R C I I FLAME SENSE OUTDOOR SENSOR DISCHARGE AIR SENSOR I W914 DEHUM OR HARMONY W951 HEAT PUMP W915 2 STAGE COMPR CUT FOR OPTION SELECTION W1 W2 G Y2 Y1 DH H O DS C OUTDOOR EQUIPMENT INDOOR EQUIPMENT ...

Страница 6: ...NS 3 PHASE COMBUSTION AIR INDUCER 95V HSI FLAME ROD DISCHARGE AIR SENSOR OPTIONAL FLAME SENSE HUM EAC LINE VOLTAGE HUMIDIFIER OPTIONAL ELECTRONIC AIR CLEANER OPTIONAL REGAL BELOIT ECM 3 0 INDOOR AIR BLOWER 24 VAC MAIN VALVE LOW PRESSURE SWITCH HIGH LIMIT SWITCH ROLLOUT SWITCH HIGH PRESSURE SWITCH W951 W914 W915 24V HUMIDIFIER OPTIONAL L1 L2 1 2 P77 P79 J3 J2 E7 E4 M W1 G Y2 Y1 C R DH H L O DS W2 F...

Страница 7: ...espond to a thermostat as dictated by the SW1 selection The ON position configures the IFC for the Lennox modulating firing state sequence with 2 stage thermostat NOTE SW2 position is ignored if SW1 is ON SW3 2ND STAGE ON DELAY The On Delay timing applies to systems configured only with single stage thermostats It is the length of time operating in normal low fire mode before switching to high fir...

Страница 8: ...tat OFF Lennox modulating sequence with 2 stage thermostat ON 2nd Stage On Delay 7 minutes OFF 2nd Stage On Delay 12 minutes ON Heat Fan Off Delay 60 seconds OFF ON Heat Fan Off Delay 90 seconds OFF OFF Heat Fan Off Delay 120 seconds ON OFF Heat Fan Off Delay 180 seconds ON ON Low fan speed fan only operation OFF ON Medium low fan speed fan only operation OFF OFF Medium high fan speed fan only ope...

Страница 9: ...factory set cooling profile The fan speed ramps up and down during speed changes Fig 7 Fan cooling speed ramp up and ramp down profile factory default shown DIP SWITCH S2 M28152 COOLING PROFILE COOL SPEED 8 9 11 10 12 13 COOL SPEED ADJUSTMENT ON M28161 30 TIME SECONDS F A N S P E E D 50 82 100 30 1 1 FAN SPEED AS A PERCENT OF MAXIMUM 450 Table 6 DIP Switch S2 Settings Cooling Airflow Description I...

Страница 10: ...ith factory default settings all OFF DIP SWITCH S3 M28153 14 15 17 16 18 19 LOW HEAT CFM CHANGE 7 OR 15 LOW HEAT CFM NORMAL MODIFIED LOW HEAT CFM INCREASE DECREASE HIGH HEAT CFM CHANGE 7 OR 15 HIGH HEAT CFM NORMAL MODIFIED HIGH HEAT CFM INCREASE DECREASE ON Table 7 DIP Switch S3 Settings Heating Airflow Description Individual Switches SW14 SW15a a Switch 15 is ignored if switch 14 is in the OFF po...

Страница 11: ...ior to calibration NOTE The calibration process takes 60 to 120 seconds to complete successfully The LED flashes C A L during a the calibration cycle Successful Calibration Calibration data is stored in volatile memory and is used to determine furnace operation and control parameters in heating mode The IFC will not perform additional calibrations unless required by changes in the appliance s oper...

Страница 12: ...to maintain the target discharge air temperature The IFC remains in this state until the thermostat generates a 2nd stage call for heat or the 1st stage call for heat is removed Call for Stage 2 Heat A call for 2nd stage heat is signaled by the thermostat simultaneously closing the contacts R W1 and W2 On the first call for 2nd stage heat the request is ignored until the 2nd stage recognition dela...

Страница 13: ...ing profiles When the cool request is satisfied the circulator de energizes per one of the selectable ramping profiles Two Stage Cooling The two stage cooling jumpera on the IFC must be clipped to enable two stage cooling control A call for 1st stage cooling is signaled by The shorting of R to Y1 The shorting of R to Y1 and G simultaneously A call for 2nd stage cooling is signaled by the shorting ...

Страница 14: ...a thermostat reset at which time the IFC resumes normal operation See Table 12 on page 27 for LED error code and lockout information Limit Switch Circuit Operation during heat cycle NOTE If the limit switch circuit opens in any mode other than heat it is ignored If the limit switch circuit opens during a heating cycle The gas valve immediately de energizes The inducer de energizes after the postpu...

Страница 15: ...ggering circuit to energize the igniter are continuously monitored during the Igniter Warm up and Ignition Activation periods If a problem is detected the IFC flashes an LED error code See Table 12 on page 27 for LED error code and lockout information Humidity Control Humidity control is available via line voltage or low voltage operation Line Voltage Humidifier The line voltage humidifier output ...

Страница 16: ...od the ignition sequence proceeds as normal If however the sensed flame lasts longer than the Flame Debounce Period The igniter de energizes The inducer energizes at ignition fire rate speed and the circulator energizes at mid heat speed The IFC flashes an LED error code indicating the flame is sensed out of sequence Once the sensed flame goes away the IFC proceeds to Postpurge followed by Soft Lo...

Страница 17: ...de If the motor does not exit cutback mode the IFC reduces the input rate by another step and adjusts the CFM to match This sequence continues until the motor exits cut back mode c If the IFC has reduced the input rate down to minimum 40 and the RBC 3 0 motor is still in cutback mode the IFC shuts down the furnace activates the blower off delay enters soft lockout and flashes the appropri ate LED ...

Страница 18: ... 2 Set the thermostat to call for heat System should oper ate as indicated in Fig 9 on page 19 or Fig 12 on page 22 3 Following lockout open the manual gas valve and make sure no gas is flowing to the burner Operating Sequences Figures 9 through 14 beginning on page 19 describe the various operating cycles Light Off Heat Run Cool and Fan of the S9240F1004 Integrated Furnace Control IFC ...

Страница 19: ...G H T O F F Safety Check Circulator OFF After Heat Fan OFF Delay Low Heat Speed Verify There Is No Main Burner Flame YES YES Low Pressure Switch Opens High Pressure Switch Opens YES Inducer ON at Ignition Firing Rate Speed NO Pressure Switch Calibration Pre Purge 15 Seconds YES H S I ON 20 Seconds Gas Valve Energized Ignition Trial Begins H S I ON Heat Fan On Delay Timer Started Flame Sensed Withi...

Страница 20: ... Delay 30 Seconds YES Inducer ON High Fire Speed Increase Inducer Speed if Not at Maximum High Pressure Switch Closes Within 10 Seconds NO Error Code Flashes NO YES Wait 5 Minutes 3A 2 Adjust Circulator To Appropriate Speed SYSTEM WILL ALWAYS LIGHT ON LOW FIRE EVEN IF 2ND STAGE CALL FOR HEAT IS IN PLACE SPECIAL LENNOX MODULATING MODE HAS NOT BEEN SELECTED IF THE HIGH PRESSURE SWITCH DOES NOT CLOSE...

Страница 21: ...EAT COOL FLAME LEVEL 3 Call for Heat Satisfied 2nd Stage Call for Heat satisfied NO Inducer speed switched to Mid speed Adjust Circulator to appropriate speed 1st Stage Call for Heat satisfied Gas valve De Energized Inducer OFF after 20 second Post Purge Circulator OFF after OFF Delay YES M28156 NO Wait for Call 2 Stage Thermostat Wait for Call Single Stage Thermostat 1 4 3A 3B RUN MODE SINGLE STA...

Страница 22: ... After Heat Fan OFF Delay Low Heat Speed Verify There Is No Main Burner Flame YES YES Low Pressure Switch Opens High Pressure Switch Opens YES Inducer ON at Ignition Firing Rate Speed NO Pre Purge 15 Seconds YES H S I ON 20 Seconds Gas Valve Energized Ignition Trial Begins H S I ON Heat Fan On Delay Timer Started Flame Sensed Within 4 seconds H S I OFF Gas Valve De energized H S I OFF Interpurge 1...

Страница 23: ...ng Contactor Compressor Fan 1st Stage Cooling Request Still Active De Energize 2nd Stage Cooling Contactor Compressor Fan Energize and Maintain Circulator at Low Cooling mode Energize Circulator High Cooling mode Maintain Circulator High Cooling mode M28158 De energize Circulator Per Ramping Profile NO NO YES NO 5 2ND STAGE COOLING OPERATION REQUIRES A 2 STAGE THERMOSTAT A 2 STAGE COOLING SYSTEM A...

Страница 24: ...Received Request for Cooling Received NO YES Call for Fan Removed YES NO Maintain Circulator at set speed Maintain Circulator at set speed YES Maintain Circulator at set speed Go to Call for Cooling M28159 Go to Call for Heat 2 Stage Thermostat Go to Call for Heat Single Stage Thermostat 6 1 4 5 OR CIRCULATOR LOW COOLING MODE AND HIGH COOLING MODE HAVE SPECIFIC ON OFF AND SPEED RAMPING PROFILES TH...

Страница 25: ...er to Table 10 12 beginning on page 26 Pushbutton The pushbutton enables alternate modes of operation such as Field Test Mode and Diagnostic Recall mode A simple common use pattern is applied to maintain consistency By pressing and holding the pushbutton The LED cycles through three menu options Idle Diagnostic Recall Field Test Every 5 seconds a new menu item displays If the button is released wh...

Страница 26: ... display in idle mode Pressure switch proving states purge states HSI warm up TFI etc All transitional ignition states H Heating stage Shows what stage of furnace heating is currently operating Shown only while heating is active and unit is set up to work as staged equipment not modulating The display example in this table shows the LED display when the 1st stage heat is active H 1 Pause Display C...

Страница 27: ...e unit is providing dehumidification instead of straight cooling D Pause Display CFM Repeat Cooling Stage Shows what stage of cooling is currently operating The display example in this table shows the LED display when the 2nd stage cooling is active C 2 Pause Display CFM Repeat Defrost Mode Shown only while in an active defrost simultaneous Y W and O D F Pause Display CFM Repeat Table 12 LED Statu...

Страница 28: ...ut Retry maximum last one due to low pressure switch open 271 Retry If failed allowed times go to Soft Lockout Error counter cleared when exiting lockout Recycle maximum last one due to low pressure switch open 272 Retry If failed allowed times go to Soft Lockout Error counter cleared when exiting lockout Recycle maximum last one due to flame lost in run mode 273 Retry If failed allowed times go t...

Отзывы: