background image

PRODUCT DATA

63-2607-08

S05, S10, S20 Series 

Spring Return Direct Coupled Actuators

MS4105, MS4110, MS4120, MS71XX, MS7505, MS7510, MS7520, 

MS8105, MS8110, MS8120

APPLICATION

MS41XX, MS71XX, MS75XX, MS81XX Spring Return Direct 

Coupled Actuators (DCA) are used within heating, ventilating, 

and air-conditioning (HVAC) systems. They can drive a variety 

of quarter-turn, final control elements requiring spring return 

fail-safe operation.

Applications include:

• Volume control dampers, mounted directly to the drive 

shaft or remotely (with the use of accessory hardware).

• Quarter-turn rotary valves, such as ball or butterfly valves 

mounted directly to the drive shaft.

• Linear stroke globe or cage valves mounted with linkages 

to provide linear actuation.

FEATURES

• Brushless DC submotor with electronic stall protection 

for floating/modulating models.

• Brush DC submotor with electronic stall protection for 

2-position models.

• Self-centering shaft adapter (shaft coupling) for wide 

range of shaft sizes.

• Models available with three torque ratings: 

44 lb-in. (5 N•m), 88 lb-in. (10 N•m), 

and 175 lb-in. (20 N•m).

• Models available for use with two-position, single pole 

single throw (spst), line- (Series 40) or low- (Series 80) 

voltage controls.

• Models available for use with floating or switched 

single-pole, double-throw (spdt) (Series 60) controls.

• Models available for use with proportional current or 

voltage (Series 70) controls.

• Models available with combined floating/modulating 

control in a single device.

• Models available with adjustable zero and span.
• Models available with line-voltage internal end 

switches.

• Access cover to facilitate connectivity.
• Metal housing with built-in mechanical end limits.
• Spring return direction field-selectable.
• Shaft position indicator and scale.
• Manual winding capability with locking function.
• UL (cUL) listed and CE compliant.
• All Models are plenum-rated per UL873.

Contents

Application .......................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

4

Wiring ...............................................................................

8

Operation ......................................................................... 13

Checkout .......................................................................... 14

Содержание S05 Series

Страница 1: ...position models Self centering shaft adapter shaft coupling for wide range of shaft sizes Models available with three torque ratings 44 lb in 5 N m 88 lb in 10 N m and 175 lb in 20 N m Models available for use with two position single pole single throw spst line Series 40 or low Series 80 voltage controls Models available for use with floating or switched single pole double throw spdt Series 60 co...

Страница 2: ...er the removable access cover Electrical Ratings See Table 1 End Switches Two SPDT Settings fixed 7 nominal stroke 85 nominal stroke Ratings maximum load Low Voltage Models 250 Vac 5A resistive 3A inductive Line Voltage Models 250 Vac 5A resistive Mounting Self centering shaft adapter shaft coupling Round Damper Shafts 0 375 to 1 06 in 10 to 27 mm Square Damper Shafts 1 2 to 3 4 in 13 to 19 mm Act...

Страница 3: ...ied with actuator 50001194 001 Foot Mount Kit 50005859 001 NEMA4 4X Enclosure 50006427 001 Anti Rotation Bracket supplied with actuator SW2 US Auxiliary Switch Package See also Form 62 2620 Floating Modulating 60 sec models 20 000 full stroke cycles 100 000 repositions Table 2 O S Number Selection see Table 3 also a Model manufactured for sale in the United States b Model manufactured for sale in ...

Страница 4: ...y to a damper external drive shaft The shaft coupling fastens to the drive shaft The actuator housing includes slots which along with an anti rotation bracket secure the actuator to the damper frame or duct work see Fig 8 NOTES When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft Using other brackets or linkages the actuator can be foot mount...

Страница 5: ... changed the actuator drives less than the full 95 degrees stroke The stroke is adjustable in 5 degree increments Once adjusted the actuator drives until the shaft coupling reaches the mechanical stop part of the housing The stop causes the motor to discontinue driving and the shaft coupling drives no farther When the actuator returns it stops at the fail safe position To set the fail safe positio...

Страница 6: ...lightly from fully open 9 Carefully adjust span knob toward minimum until the actuator hub returns to fully open Auto Adapt When using these actuators for standard stroke applications this function can be ignored When it is desirable to use a mechanically limited stroke see Mechanical Stroke Limit Adjustment section it is possible to use the Auto Adapt feature to rescale the input signal over the ...

Страница 7: ...ee Fig 8 2 Mark screw holes on damper housing 3 Remove actuator and mounting bracket 4 Drill or center punch holes for mounting screws or use no 10 self tapping sheet metal screws 5 Turn damper blades to desired normal closed position 6 Place actuator and mounting bracket back into position and secure bracket to damper box with sheet metal screws 7 Using 10 mm wrench tighten shaft coupling securel...

Страница 8: ...amage the device NOTE This cover can be removed before or after actuator mounting In order to wire the device the access cover must be removed as follows 1 Remove the screw from the center of the cover set the screw aside 2 Pull the cover along the long axis of the actuator 3 If the actuator is not yet mounted set it aside 4 Remove conduit dust covers as necessary 5 Thread wire through conduit hol...

Страница 9: ...TED IN A SAME POLARITY MANNER V OR OR N A FEEDBACK ACTUATOR 1 2 3 5 4 3 1 7 85 S1 S2 S3 S4 S5 S6 2 M19571B ACTUATOR SPST 24 VAC 1 1 2 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE ENSURE PROPER GROUNDING OF ACTUATOR CASE V 1 2 M19718C 3 3 ACTUATOR SPST 1 1 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION ...

Страница 10: ...2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK FEEDBACK 5 4 3 1 2 M19574B 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE 4 ACTUATOR 4 TO 20 mA PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 2 490 TO 510 OHMS 1 2 W MINIMUM LINE VOLTAGE POWER S...

Страница 11: ...3 1 2 M19575B 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 4 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE ACTUATOR 0 2 TO 10 VDC PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 4 4 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWIT...

Страница 12: ...TROLLER 1 2 3 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK 5 4 3 1 2 M22288A 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 24 VAC 1 24 VAC 1 2 24 VAC 1 HOT COM 4 ENSURE PROPER GRO...

Страница 13: ...ion or similar applications 1 Override to full open a Disconnect the input signal from terminal 3 b Apply 24 Vac to terminal 3 c See Fig 27 2 Override to full closed a Disconnect the input signal from terminal 3 b See Fig 28 Fig 27 Override to full open Fig 28 Override to full close End Switches Some models include end switches see Table 2 For wiring details see Fig 11 SPDT Switches Fig 29 For SPD...

Страница 14: ... 10 12 mA signal to terminal 3 c Floating apply 24 Vac to appropriate CW 3 or CCW 4 terminal 5 Allow the actuator to drive to 50 position 6 Disconnect wire from terminal 1 7 Actuator spring returns to 0 position 8 Re connect wire to terminal 1 actuator drives towards 100 position Feedback Operation 1 Connect a multi meter set for Vdc to terminals 2 and 5 2 Apply the same signal as in step 4 of Mod...

Страница 15: ...15 63 2607 08 ...

Страница 16: ...ited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com S05 S10 S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS U S Registered Trademark 2008 Honeywell International Inc 63 2607 08 M S Rev 07 08 ...

Отзывы: