S05, S10, S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS

63-2607—08

4

Sizing

Required Torque

In lieu of data from a Specification Engineer or Manufacturer, 

required torque for a given damper load can be determined 

using the following method:

Where:

— T

R

 = Required torque for the damper load.

— T

D

 = Damper torque rating from the manufacturer, 

expressed in either (lb-in.)/(sq ft) or (N•m)/(sq m). the 

damper load.

— A

D

 = Damper area expressed in either sq ft or sq m.

Actuators Required

In lieu of data from a Specification Engineer or Manufacturer, 

the number of required actuators for a given damper load can 

be determined using the following method:

Where:

— N = Number of actuators.

— T

R

 = Required torque for the damper load. (See above.)

— T

A

 = Actuator torque rating.

— SF = Safety factor.

NOTE: The safety factor accounts for variables such as mis-

alignments, aging of the damper, etc. 0.8 is a typical 

safety factor.

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazardous 

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Low voltage can shock individuals or short 

equipment circuitry.

Disconnect power supply before installation.

IMPORTANT

All wiring must agree with applicable codes, 

ordinances and regulations.

Location

These actuators are designed to mount directly to a damper 

external drive shaft. The shaft coupling fastens to the drive 

shaft. The actuator housing includes slots which, along with an 

anti-rotation bracket, secure the actuator to the damper frame 

or duct work (see Fig. 8).

NOTES:

When mounted correctly, these slots allow the 

actuator to 

float

 without rotating relative to the 

damper shaft.

Using other brackets or linkages, the actuator can 

be foot-mounted or tandem-mounted.

CAUTION

Motor Damage Hazard.

Deteriorating vapors and acid fumes can damage 

metal parts.

Install motor in areas free of acid fumes and other 

deteriorating vapors.

CAUTION

Equipment Damage Hazard.

Tightly securing actuator to damper housing can 

damage actuator.

Mount actuator to allow it to float along its vertical axis.

Preparation

Before mounting the actuator onto the damper shaft, determine 

the:

— Damper/valve opening direction for correct spring return 

rotation. The actuator can be mounted to provide clockwise 

or counterclockwise spring return.

— Damper shaft size (see the Specifications section).

Determine Appropriate Mounting Orientation

The actuators are designed to open a damper by driving the 

damper shaft in either a clockwise 

 or counterclockwise 

 direction (see Fig. 2).

NOTES:

Actuators are shipped in the fully closed (spring 

return) position.

An arrow molded into the hub points to tick marks 

on the label to indicate the hub rotary position.

Fig. 2. Spring Return DCA mounting orientation.

Measure Damper/Valve Shaft Length

If the shaft is less than three inches in length, the shaft 

coupling must be located between the damper/valve and 

actuator housing. If the shaft length is more than three inches, 

the shaft coupling may be located on either side of the actuator 

housing.

T

R

T

D

A

D

×

=

N

T

R

T

A

SF

×

-------------------

=

M20953

CCW TO CLOSE
(FAIL-SAFE 
POSITION)

CW TO OPEN

CW TO CLOSE
(FAIL-SAFE 
POSITION)

CCW TO OPEN

Содержание S05 Series

Страница 1: ...position models Self centering shaft adapter shaft coupling for wide range of shaft sizes Models available with three torque ratings 44 lb in 5 N m 88 lb in 10 N m and 175 lb in 20 N m Models available for use with two position single pole single throw spst line Series 40 or low Series 80 voltage controls Models available for use with floating or switched single pole double throw spdt Series 60 co...

Страница 2: ...er the removable access cover Electrical Ratings See Table 1 End Switches Two SPDT Settings fixed 7 nominal stroke 85 nominal stroke Ratings maximum load Low Voltage Models 250 Vac 5A resistive 3A inductive Line Voltage Models 250 Vac 5A resistive Mounting Self centering shaft adapter shaft coupling Round Damper Shafts 0 375 to 1 06 in 10 to 27 mm Square Damper Shafts 1 2 to 3 4 in 13 to 19 mm Act...

Страница 3: ...ied with actuator 50001194 001 Foot Mount Kit 50005859 001 NEMA4 4X Enclosure 50006427 001 Anti Rotation Bracket supplied with actuator SW2 US Auxiliary Switch Package See also Form 62 2620 Floating Modulating 60 sec models 20 000 full stroke cycles 100 000 repositions Table 2 O S Number Selection see Table 3 also a Model manufactured for sale in the United States b Model manufactured for sale in ...

Страница 4: ...y to a damper external drive shaft The shaft coupling fastens to the drive shaft The actuator housing includes slots which along with an anti rotation bracket secure the actuator to the damper frame or duct work see Fig 8 NOTES When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft Using other brackets or linkages the actuator can be foot mount...

Страница 5: ... changed the actuator drives less than the full 95 degrees stroke The stroke is adjustable in 5 degree increments Once adjusted the actuator drives until the shaft coupling reaches the mechanical stop part of the housing The stop causes the motor to discontinue driving and the shaft coupling drives no farther When the actuator returns it stops at the fail safe position To set the fail safe positio...

Страница 6: ...lightly from fully open 9 Carefully adjust span knob toward minimum until the actuator hub returns to fully open Auto Adapt When using these actuators for standard stroke applications this function can be ignored When it is desirable to use a mechanically limited stroke see Mechanical Stroke Limit Adjustment section it is possible to use the Auto Adapt feature to rescale the input signal over the ...

Страница 7: ...ee Fig 8 2 Mark screw holes on damper housing 3 Remove actuator and mounting bracket 4 Drill or center punch holes for mounting screws or use no 10 self tapping sheet metal screws 5 Turn damper blades to desired normal closed position 6 Place actuator and mounting bracket back into position and secure bracket to damper box with sheet metal screws 7 Using 10 mm wrench tighten shaft coupling securel...

Страница 8: ...amage the device NOTE This cover can be removed before or after actuator mounting In order to wire the device the access cover must be removed as follows 1 Remove the screw from the center of the cover set the screw aside 2 Pull the cover along the long axis of the actuator 3 If the actuator is not yet mounted set it aside 4 Remove conduit dust covers as necessary 5 Thread wire through conduit hol...

Страница 9: ...TED IN A SAME POLARITY MANNER V OR OR N A FEEDBACK ACTUATOR 1 2 3 5 4 3 1 7 85 S1 S2 S3 S4 S5 S6 2 M19571B ACTUATOR SPST 24 VAC 1 1 2 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE ENSURE PROPER GROUNDING OF ACTUATOR CASE V 1 2 M19718C 3 3 ACTUATOR SPST 1 1 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION ...

Страница 10: ...2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK FEEDBACK 5 4 3 1 2 M19574B 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE 4 ACTUATOR 4 TO 20 mA PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 2 490 TO 510 OHMS 1 2 W MINIMUM LINE VOLTAGE POWER S...

Страница 11: ...3 1 2 M19575B 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 4 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE ACTUATOR 0 2 TO 10 VDC PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 4 4 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWIT...

Страница 12: ...TROLLER 1 2 3 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK 5 4 3 1 2 M22288A 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 24 VAC 1 24 VAC 1 2 24 VAC 1 HOT COM 4 ENSURE PROPER GRO...

Страница 13: ...ion or similar applications 1 Override to full open a Disconnect the input signal from terminal 3 b Apply 24 Vac to terminal 3 c See Fig 27 2 Override to full closed a Disconnect the input signal from terminal 3 b See Fig 28 Fig 27 Override to full open Fig 28 Override to full close End Switches Some models include end switches see Table 2 For wiring details see Fig 11 SPDT Switches Fig 29 For SPD...

Страница 14: ... 10 12 mA signal to terminal 3 c Floating apply 24 Vac to appropriate CW 3 or CCW 4 terminal 5 Allow the actuator to drive to 50 position 6 Disconnect wire from terminal 1 7 Actuator spring returns to 0 position 8 Re connect wire to terminal 1 actuator drives towards 100 position Feedback Operation 1 Connect a multi meter set for Vdc to terminals 2 and 5 2 Apply the same signal as in step 4 of Mod...

Страница 15: ...15 63 2607 08 ...

Страница 16: ...ited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com S05 S10 S20 SERIES SPRING RETURN DIRECT COUPLED ACTUATORS U S Registered Trademark 2008 Honeywell International Inc 63 2607 08 M S Rev 07 08 ...

Отзывы: