8. Maintenance
8.1. Inspection
8.1.1. Check valve
1. Close shutoff valve on inlet
2. Open test valve
• Until the pressure is released, some water will flow out
of the test valve. After a short period of time the water
flow should stop. If the water continues to drip or run,
then the check valve must be replaced - see servicing
of check valve
3. Close test valve again
4. Slowly open shutoff valve on inlet
8.2. Maintenance
8.2.1. Check valve
1. Close shutoff valve on inlet
2. Release pressure on outlet side (e.g. through water tap)
3. Close shutoff valve on outlet
4. Replace check valve
5. Slowly open shut off valves on inlet and outlet
9. Disposal
• Grey cast iron housing end and housing
- Powdercoated with:
High-performance polyamide (DN50 - DN100)
High-performance epoxy resin (DN125 - DN300)
• Stainless steel screws and nuts
• Stainless steel disc (red bronze for DN 40 and DN 50)
• Stainless steel spring
• EPDM for lip seal ring
10. Spare Parts
In accordance with DIN 1988, Part 8, the following
operations should be carried out regularly. A planned
maintenance scheme is recommended.
Interval: once a year
To be carried out by an installation company
Observe the local requirements regarding correct waste
recycling/disposal!
No.Description
Dimension
Part No.
1
Valve disc guide
DN40
5605800
DN50
5605900
DN65
0900376
DN80
0900377
DN100
0900378
DN125
0900379
DN150
0900380
DN200
0900381
DN250
0900382
DN300
0900383
2
Lip seal ring
DN40
2238700
DN50
2238800
DN65
5350000
DN80
5350300
DN100
5350400
DN125
2070300
DN150
2067300
DN200
2238900
DN250
2239000
DN300
2239100
3
Hexagonal blanking DN40 - DN50
5726800
plug
DN65 - DN100
2248700
DN125 - DN300
2591000
4
Seal ring
DN40 - DN50
up to 06/2013
2166600
DN40 - DN50
from 07/2013 onwards
0904122
DN65 - DN100
5350500
DN125 - DN300
2698000