![Honeywell RMA 3000 Скачать руководство пользователя страница 48](http://html.mh-extra.com/html/honeywell/rma-3000/rma-3000_user-manual_151881048.webp)
40
34-ST-25-19 RMA 3000 Remote Meter Assemblies User Manual
Release: 1
6/04
IEC Methods of
Protection
The following table summarizes available methods of protection for use in given
locations.
Protection Concept Designation Permitted
Use
Principle
Flameproof
d
Zone 1 & 2
Contains explosion and
quenches flame.
Intrinsic Safety
ia
Zone 0, 1 & 2
Limits energy of sparks under 2
faults.
ib
Zone 1 & 2
Limits energy of sparks under
1 fault
Pressurized
p
Zone 1
Keeps flammable gases out.
Encapsulation
m
Zone 1 & 2
Keeps flammable gases out.
Increased Safety
e
Zone 1 & 2
No arcs, sparks or hot
surface.
Powder Filled
q
Zone 1 & 2
Contains explosion and
quenches flame.
Oil Immersion
o
Zone 1 & 2
Keeps flammable gases out.
Non-sparking
nA
Zone 2
No arcs, sparks or hot
surfaces under normal
conditions.
Enclosed Break
nC
Zone 2
Contains explosion and
quenches flame.
Limited Energy
nA
Zone 2
Limits energy of sparks and
surface temperature under
normal conditions.
Restricted Breathing
nR
Zone 2
Keeps flammable gases out.
Содержание RMA 3000
Страница 4: ...34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual Release 1 6 04 iv ...
Страница 8: ...viii 34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual Release 1 6 04 ...
Страница 34: ...26 34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual Release 1 6 04 ...
Страница 36: ...28 34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual Release 1 6 04 ...
Страница 38: ...30 34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual Release 1 6 04 ...
Страница 53: ...Release 1 34 ST 25 19 RMA 3000 Remote Meter Assemblies User Manual 45 6 04 ...
Страница 54: ...Industrial Measurement and Control Honeywell International Inc 2500 West Union Hills Drive Phoenix AZ 85027 ...