Specifications
Physical: Width: 2-1/8” (53mm)
Height: 3-1/4” (84mm) Depth: 1” (25mm)
Electrical:
Polling loop input voltage range: 8-12VDC
Polling loop current draw: 7mA (continuous)
Relay contact rating: 2A @ 28VAC/VDC, resistive loads
Aux Zone:
10k EOLR (internal when white jumper intact; external
when white jumper cut
300 ohm max zone resistance (excluding EOLR)
Responds to open or short circuit faults having 250mSec
or longer duration
Class B (style B when used with panels providing earth
ground fault detection)
For UL Commercial Fire Applications, must be used as
N.O. zone and white jumper must be cut
Agency Listings
UL864 Commercial Fire
UL985 Household Fire
UL1023 Household Burglary
UL609 Commercial Burglary
CSFM
FM
MEA
Warranty
For the latest warranty information, please go to:
http://www.honeywell.com/security/hsc/resources/wa/
TAMPER SWITCH
MOUNTING SCREW
HOLES (IN CASE BACK)
4101SN
TERM. ASSIGNMENT
1 (+) POLLING LOOP
POLLING LOOP
(+)
2
3 (+) AUX ZONE (+)
4
RELAY N.O.
5
RELAY N.C.
6
RELAY C
+
+
POLLING LOOP - CLASS B, STYLE 4
MAX WIRING IMPEDANCE 25 OHMS
+
POLLING LOOP
TERMINALS ON
CONTROL
1 2 3
4 5 6
RELAY C CONTACT
RELAY N.C. CONTACT
RELAY N.O. CONTACT
10K EOLR
(USE ONLY IF WHITE
JUMPER IS CUT)
N.O. N.C.C
MOUNTING
CASE BACK
TERMINAL
BLOCK TB1
(SUITABLE FOR
14-22 AWG WIRE)
COVER SCREW HOLE
WHITE JUMPER
WIRING ACCESS
HOLES (SLOTS)
MOUNTING SCREW HOLE
(IN CASE BACK)
N.C.
N.O.
AUX.
ZONE
OTHER
V-PLEX MODULES
TM
4101SN-001-V5
( )
( )
Always Observe Polarity.
V-Plex and Aux Circuits are supervised
and power-limited.
See Panel's I.I. Text For Wire Gauge
And Wire Length Requirements.
Always Connect In Parallel.
If switching power through a
relay, the power must be from
a power-limited source.
Relays are programmable but
outputs are not supervised.
Figure 1. 4101SN V-Plex
Single Output Relay Module
SEE THE CONTROL PANEL’S INSTALLATION INSTRUCTIONS FOR COMPLETE INFORMATION
REGARDING LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.
2
Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2020 Resideo Technologies, Inc.
www.resideo.com
ÊK3166V3B>Š
K3166V3B 10/12 Rev. B