Honeywell Resideo ADEMCO 4101SN V-Plex Скачать руководство пользователя страница 1

 

 

 

K3166V3B  10/12 Rev B

ADEMCO 4101SN 

V-Plex® Single Output Relay Module

Installation and Setup Guide 

Features 

The  ADEMCO  4101SN  V-Plex

®

Single  Output  Relay 

Module  can  be  used  with  control  panels  that  support  V-Plex 

 

Polling  Loop  devices,  e.g.  VISTA-128FBP  (refer  to  the 
instructions for the control).   
The 4101SN features the following: 

  Form C relay contacts rated at 2A, Resistive 28VAC/VDC 

with contact supervision. 

 

The position of the relay is supervised, but 
not the actual external contact wiring. Note: 
some panels may not support this feature. 

Note:

  This  product  uses  latching  relays,  which  retain  their 

open/closed  position  even  when  power  is  disconnected.  Due 
to  shocks  or  vibration  during  shipment  and  installation  the 
out-of-box state of these relays may be either open or closed. 
When power is first applied, the relay will be set to its correct 
initial  state.  Please  bear  this  in  mind  during  installation;  it  is 
strongly recommended that you wire this module to the panel 
and  apply  power  to  the  panel  before  energizing  any  external 
circuit controlled by the latching relay. 

  One Class B/Style B EOLR-supervised aux input zone. 

  Operating  power  and  communication  with  control  panels 

via the V-Plex polling loop. 

  Electronics  mounted  in  a  small  plastic  case  with  tamper-

protected cover. 

  Suitable  for  household  and  commercial  burglary,  and 

household and commercial fire applications. 

Mounting Instructions 

 

1.

 

Remove the case cover by first removing the screw. (See 

Figure 1

.)  

2.

 

Fasten the case back to the wall with three #6 screws (not 
supplied) through the case back. 

 

  The wall surface must be flat and 

substantially vibration-free. 

  All power-limited wiring must be separated 

from non-power limited wiring by 1/4 –inch. 

 

UL 

 

For dry, indoor use only.  Do not install 
in air-handling spaces. 

 

For Commercial Burglary installations, 
the 4101SN must be tamper protected 
or mounted in a tamper-protected 
cabinet. 

 

In Commercial Fire applications, the 
module cannot be mounted inside the 
control unit’s cabinet, but can be 
mounted externally either in its plastic 
housing or in a separate metal cabinet. 

Wiring Instructions 

UL 

  For UL fire installations, no more than one 

wire per terminal may be connected. 

  Use only 14-22AWG wire. 

1.  Run  the  wiring  through  the  access  slots  in  the  case  back 

and connect at the appropriate terminal block screw(s). 

2.  Make  wiring  connections  as  shown  in 

Figure  1

.    When 

you  leave  the  white  jumper  intact,  the  10k  EOLR  for  the 
aux zone is internal. Only N.O. devices may be used, and 
these devices must be mounted no farther than 3 feet from 
the  module.    In  commercial  installations,  wiring  must  be 
mechanically protected with conduit or equivalent.   

3.  When you cut the white jumper, you must connect the 10k 

EOLR for the aux zone to the end of the zone wire run.  

4.  Either  N.O.  or  N.C.  devices  may  be  used,  and  these 

devices may be located where desired.  

UL 

For Commercial Fire Applications, use only 
N.O. contact closure devices. 

5.  When  the  aux  zone  is  programmed  for  burglary  response 

type,  you  may  use  the  discrete  10k  resistor  (supplied). 
When this zone is programmed for fire response type, you 
must  use  the  model  number  WA  610-13  resistor 
(supplied).  

6.  Place the cover over the PCB and insert the screw to hold 

it in place. 

Panel Programming Instructions 

The 4101SN Module’s serial number  must be enrolled in the 
control panel so that the panel can communicate with it.  Each 
4101SN  (if  there  is  more  than  one  connected  to  the  polling 
loop) is enrolled one at a time.   
The  following  steps  outline  the  general  procedure  for  how 
this  is  done.    Refer  to  the  control  panel’s  Installation 
Instructions for additional information. 

1.

 

Enter the panel’s Programming mode. 

2.

 

Enter Zone Programming mode.

  

  Assign  a  unique  zone  number  and  a  non-zero  zone 

response  type  to  the  4101SN.    This  zone  will  be  used 
to  annunciate  aux  zone  faults,  communication 
problems, and cover tamper faults for this 4101SN.  

  Select  Input  Type  =  “06”  (for  serial  number  polling 

loop device), V-Plex Relay = “Yes” and Loop # = “1” 
for this zone.  

  Select  the  Learn  S/N  =  “Yes”  option.  Remove  the 

enclosure  cover  (or  short  the  aux  zone)  to  cause  the 
4101SN  to  send  its  serial  number  to  the  panel.  The 
panel  will  acknowledge  receipt  of  the  serial  number 
and  will  require  the  cover  to  be  replaced  (or  the  aux 
zone  to  be  restored)  to  confirm  that  the  serial  number 
was enrolled correctly. 

 

UL

 

The cover tamper feature must be used in 
commercial burg installations when the 4101SN is 
not mounted inside the panel’s enclosure, and 
must be enabled at the control panel (program 
field *24=0 on most controls). 

 

Enter Relay Programming mode

.  

1.

 

Assign a unique 2-digit relay number “XX” and then 
assign relay start/stop activation options to the 4101SN.   

2.

 

Select Relay Type = “0” (for V-Plex relay) and then enter 
the zone number selected in Zone Programming as the V-
Plex Zone Number.  The panel will annunciate relay 
activation problems as well as communication problems 
and cover tamper faults for this 4101SN on system zone 
6XX where “XX” is the selected relay number.  
Generally, the panel’s default response for all such system 
zones is 24-hour trouble (type 19). If desired, this may be 
changed using the panel’s Zone Programming mode. 

3.

 

Repeat the above procedure for each 4101SN in the 
system. 