Honeywell RA890F Protectorelay Primary Control Скачать руководство пользователя страница 4

60-2034—7

4

RA890F

INSTALLATION

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to fol-

low them could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced, flame safe-

guard control technician.

4. After installation is complete, check out product op-

eration as provided in these instructions.

CAUTION

1. Disconnect power supply before beginning in-

stallation to prevent electrical shock and equip-
ment damage.

2. All external timers must be Listed or Component

Recognized by authorities that have jurisdiction
for the specific purpose for which they are used.

Refer to Fig. 3 and 4 for typical field wiring connections.

See Fig. 5 for schematic diagram. Follow the burner manu-
facturer’s instructions if supplied. Otherwise proceed as
follows.

LOCATION
Temperature

Install the RA890F where the surrounding temperatures

remain within the Ambient Operating Temperature Ratings
listed in the SPECIFICATIONS section.

Humidity

Install the RA890F where the relative humidity never

reaches the saturation point. Condensation of moisture on
the RA890F may cause enough leakage to short the flame
signal to ground and prevent the burner from starting.

Vibration

Do not install the RA890F where it could be subject to

excessive vibration. Vibration shortens the life of the elec-
tronic and mechanical components.

Weather

The RA890F is not designed to be weathertight. If it is

installed outdoors, use a suitable weathertight enclosure.

Mount Subbase

Locate the subbase where ambient temperature is within

the specified rating.

Mount the subbase so the top and bottom are horizontal

and the back is vertical. The subbase can lean backward as
much as 45 degrees when necessary. See Fig. 1.

Fig. 1—Mounting subbase in in. (mm).

M8681

HORIZONTAL

VERTICAL

2-7/8

(73.0)

4-1/8  (104.8)

KNOCKOUTS (9) FOR
1/2 IN. (13) CONDUIT

45 DEGREES
MAXIMUM LEAN

WIRE SUBBASE

1. Disconnect power supply (see Fig. 2) before making

wiring connections to avoid electrical shock and equipment
damage. Assure all wiring complies with applicable electri-
cal codes, ordinances, and regulations. Use NEC Class 1
(line voltage) wiring.

When wiring the Q270A Universal Mounting Base for

use with the RA890F, use the terminal designations 6, T and
T (printed in white).

2A. For normal installations, use moisture-resistant

No. 14 wire suitable for at least 167

°

F (75

°

C). For

high temperature installations, use moisture-resis-
tant No. 14 wire selected for a temperature rating
above the maximum operating temperature for all
but the ignition and flame detector F leadwires.
a. For the ignition, use Honeywell Specification

no. R1061012 Ignition Cable or equivalent. (This
wire is rated at 350

°

F (175

°

C) for continuous

duty, and up to 500

°

F (260

°

C) for intermittent

use. It was tested to 25,000V.)

b. For the flame detector F leadwire, use Honeywell

Specification no. R1298020 or equivalent. (This
wire is rated up to 400

°

F (205

°

C) for continuous

duty. It was tested for operation up to 600V and
breakdown up to 7500V.)

2B. For ignition installations in a contaminating environ-

ment, use Honeywell Specification no. R1239001
High Tension Ignition Cable or equivalent. This
wire is very resistant to severe conditions of oil, heat,
and corona, and is tested to withstand high voltages
up to 25,000V rms in a salt bath for one minute
without breakdown. It is rated at 200

°

F (93

°

C) for

continuous duty, and up to 350

°

F (175

°

C) for inter-

mittent use.

Содержание RA890F Protectorelay Primary Control

Страница 1: ... required during Off cycle no tube to warm up before starting Push to reset safety switch in dust resistant enclosure Built inprotectionagainstignitioncrossoverinflame rod systems Does not start if flame simulating failure occurs in flame detector circuit Automatic safety shutdown if flame fails on start or if flame not re established after flame failure Flame signal current is directly measurable...

Страница 2: ...r 1 0A at 120 Vac in suitable wiring enclosure Low Voltage Control Circuit T T 0 3A Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number standard or TRADELINE 2 Voltage and frequency 3 Flame response time 4 Safety switch tim...

Страница 3: ...TE All devices meeting UL components recognition have the following symbol Replacement exchange controls that meet current UL requirements are identified with the term REMFR D following the listing or component recognition mark Canadian Standards Association Certified 120V models only File No LR1620 Factory Mutual Approved Report No 17678 19417 and 19784 American Gas Association Design Certified f...

Страница 4: ...nt temperature is within the specified rating Mount the subbase so the top and bottom are horizontal and the back is vertical The subbase can lean backward as much as 45 degrees when necessary See Fig 1 Fig 1 Mounting subbase in in mm M8681 HORIZONTAL VERTICAL 2 7 8 73 0 4 1 8 104 8 KNOCKOUTS 9 FOR 1 2 IN 13 CONDUIT 45 DEGREES MAXIMUM LEAN WIRE SUBBASE 1 Disconnect power supply see Fig 2 before ma...

Страница 5: ... ALARM TERMINALS ARE ENERGIZED THROUGH RA890 SAFETY SWITCH ALARM WILL NOT SOUND UNTIL SAFETY SWITCH TRIPS OUT POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR RA890E REPLACEMENT LEAVE POWER CONNECTED TO TERMINAL 1 SUBBASE WIRING CHANGES ARE NOT REQUIRED SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR OPERATING CONTACTS IN SERIES WITH THE MAIN F...

Страница 6: ...ON AS REQUIRED RA890F IS POWERED AT TERMINAL 6 ONLY WHEN REPLACING ANOTHER MODEL LEAVE HOT LINE L1 CONNECTED TO TERMINAL 1 EVEN THROUGH IT IS NOT NECESSARY FOR OPERATION MAY USE LINE OR LOW VOLTAGE CONTROLLER IF LINE VOLTAGE CONTROLLER IS USED CONNECT IT BETWEEN THE LIMIT CONTROLLER AND TERMINAL 6 JUMPER T T FOR INTERMITTENT IGNITION CONNECT TO TERMINAL 3 OPENING OF A LIMIT CONTROL OR LINE VOLTAGE...

Страница 7: ...SET PUSHBUTTON LOAD RELAY 1K Q270A SUBBASE M8766 FLAME RELAY 2K CAPTIVE MOUNTING SCREWS 10 ARC GAP PROTECTOR OPTIONAL ALARM CONTACT 3 PILOT LINK JUMPER WIRE 0N BASE ALONGSIDE TEST JACK TEST JACK PILOT LINK ARC GAP PROTECTOR M8767 Operation NORMAL OPERATION SUMMARY Normal control operation is summarized below Refer to Fig 5 for the internal schematic of the control 1 Call for heat Load relay pulls ...

Страница 8: ...m all checkout tests indicated below Flame Current Check all installations PilotTurndownTest allinstallationsthatrequireproofof pilot before main fuel valve is opened Safe Shutdown Checks Flame failure power failure limit action all installations Hot Refractory Hold In photocell applications only FLAME CURRENT CHECK The flame current check is the best indicator of proper flame detector application...

Страница 9: ... on the axis of a pilot flame or b Adjusting a flame rod detector so that a larger mini mum pilot is required CAUTION If the pilot needs to be adjusted and rechecked allow five minutes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the comple...

Страница 10: ...ners tested were found to leave deposits on the contact surfaces or to attack RA890 chassis parts Troubleshooting Whentroubleoccursintheheatingsystemanditscauseis not immediately apparent the service technician can apply the following step by step checkout to locate the cause of most problems Refer to Fig 3 and 4 for terminal locations and to Fig 6 for location of component parts CAUTION Use extre...

Страница 11: ... PROBLEMS Relay Chatter Load relay chatter can result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause Difficulty Resetting Safety Switch 30 Second Safety Switch Models _ Ambienttemperaturemaybebelow 10 F 12 C Prob lem is corrected by warm...

Страница 12: ...rol Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: