Honeywell RA890F Protectorelay Primary Control Скачать руководство пользователя страница 11

11

60-2034—7

RA890F

TROUBLESHOOTING

terminal 6 with the controller calling for heat. If there is
power at terminal 6 and a line voltage controller is used,
clean all relay contacts. Replace the RA890 if the relay still
does not pull in. If a low voltage controller is used, proceed
to step 9.

9. Check low voltage controller, if used, by jumping T-T.
a. Load relay pulls in with T-T jumpered; check control-

ler and external circuit.

b. Load relay does not pull in with T-T jumpered; clean

all relay contacts. Replace the RA890 if the load relay
still does not pull in.

10. If the load relay pulls in but the pilot will not light or the

burner will not start, check voltage at terminals 3-2 or 4-2.

a. If no voltage at terminals 3-2 or 4-2 clean relay con-

tacts. Replace the RA890 when trouble cannot be
corrected.

b. If normal line voltage at terminals 3-2 or 4-2, check

external burner, ignition, and valve circuits. Check
wiring, burner adjustment, ignition system including
electrode spacing and location, oil quality, character
and efficiency of oil atomization, fuel supply pressure,
flame pattern, flame character and quality, pilot loca-
tion with respect to main burner, flame detector, or
other conditions that may delay lightoff.

TESTING FLAME DETECTING FUNCTION

11. Observe the flame relay (right relay) for pull-in when

flame is established.

a. Flame relay pulls in; proceed to step 13.
b. Flame relay does not pull in; proceed to step 12.

12. Check the flame relay with a 121708 Flame Simulator

if available (follow the instructions with the simulator), or
check the following:

a. Perform a flame current check according to the flame

current check section.

b. If the current is satisfactory, replace the RA890.
c. If the current is not satisfactory, check all items listed

in the Flame Current Check section.

OBSERVE SEQUENCING OPERATION

13. Observe the second stage oil valve or main gas valve

for opening when flame relay pulls in.

a. If valve does not open, check for line voltage at termi-

nals 2-5.

(1) Normal voltage—check valve and valve circuit.
(2) Zero voltage—clean relay contacts. Replace the

RA890 if this does not correct the problem.

14. Observe ignition for cutoff when flame relay pulls in

when connected to terminal 4.

a. If ignition stays on and wiring checks out, replace the

RA890.

MISCELLANEOUS PROBLEMS
Relay Chatter

Load relay chatter can result from extreme low voltage

(notify power company) or from a loose connection (tighten).

Flame relay chatter may result from improper combus-

tion (adjust burner) or soot or carbon on flame detector
(clean, and correct the cause).

Difficulty Resetting Safety Switch
(30 Second Safety Switch Models)_

Ambient temperature may be below +10

°

F (-12

°

C). Prob-

lem is corrected by warming the safety switch.

Repeated Lockouts Or Control Failures

The most common causes of repeated failures of the con-

trol or flame detector or repeated lockouts are:

a. High ambient temperatures—over 125

°

F (52

°

C). Sub-

tract 10

°

F (6

°

C) for alarm contacts and 10

°

F (6

°

C) for

50 Hz operation.

b. Supply voltage variation greater than +10 to -15 percent.
c. Electrical overloading of the contacts.
d. Marginal microampere signal.
e. Frequent cycling with high ambient temperatures.

IGNITION INTERFERENCE
(Flame Rod Detectors Only)

Ignition interference is a false signal from a spark ignition

system superimposed on the flame signal. The interference
may be additive or subtractive (increases or decreases the
flame current), and in some instances may be sufficient to
destroy the electronic network of the RA890E. The RA890F
network is protected against interference by the arc gap
shown in Fig. 7.

The arc gap conducts at high voltage levels. It also glows

when it conducts, providing a visual indication that interfer-
ence is occurring. This prevents the control from operating
and causes a shutdown.

Ignition interference (below the arcing level) can be

determined by measuring the flame current with ignition and
pilot on, and then with only pilot on. Any significant differ-
ence may indicate interference.

IMPORTANT: When an RA890F replaces an RA890E,

there may be installations where ignition interference
is not sufficient to destroy the RA890E, but is sufficient
to prevent operation of the RA890F due to its arc gap
protection. Be very suspicious of ignition interference
on any installation where the RA890E operates and
the RA890F does not.

HOW TO ELIMINATE INTERFERENCE
(Tabulated in Order of Importance)

1. Provide adequate flame grounding area.
2. Be sure the ignition electrode and the flame rod are on

opposite sides of the grounding area.

3. Check for correct spacing on the ignition electrode.

Spacing should be 1/16 in. to 3/32 in. (1.6 to 2.4 mm) for
6,000V systems and 1/8 in. (3.2 mm) for 10,000V systems.

4. Eliminate any marginal spacing at other areas along

the lead routes. Replace any deteriorated leads.

Содержание RA890F Protectorelay Primary Control

Страница 1: ... required during Off cycle no tube to warm up before starting Push to reset safety switch in dust resistant enclosure Built inprotectionagainstignitioncrossoverinflame rod systems Does not start if flame simulating failure occurs in flame detector circuit Automatic safety shutdown if flame fails on start or if flame not re established after flame failure Flame signal current is directly measurable...

Страница 2: ...r 1 0A at 120 Vac in suitable wiring enclosure Low Voltage Control Circuit T T 0 3A Ordering Information When purchasing replacement and modernization products from your TRADELINE wholesaler or your distributor refer to the TRADELINE catalog or price sheets for complete ordering number or specify 1 Order number standard or TRADELINE 2 Voltage and frequency 3 Flame response time 4 Safety switch tim...

Страница 3: ...TE All devices meeting UL components recognition have the following symbol Replacement exchange controls that meet current UL requirements are identified with the term REMFR D following the listing or component recognition mark Canadian Standards Association Certified 120V models only File No LR1620 Factory Mutual Approved Report No 17678 19417 and 19784 American Gas Association Design Certified f...

Страница 4: ...nt temperature is within the specified rating Mount the subbase so the top and bottom are horizontal and the back is vertical The subbase can lean backward as much as 45 degrees when necessary See Fig 1 Fig 1 Mounting subbase in in mm M8681 HORIZONTAL VERTICAL 2 7 8 73 0 4 1 8 104 8 KNOCKOUTS 9 FOR 1 2 IN 13 CONDUIT 45 DEGREES MAXIMUM LEAN WIRE SUBBASE 1 Disconnect power supply see Fig 2 before ma...

Страница 5: ... ALARM TERMINALS ARE ENERGIZED THROUGH RA890 SAFETY SWITCH ALARM WILL NOT SOUND UNTIL SAFETY SWITCH TRIPS OUT POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR RA890E REPLACEMENT LEAVE POWER CONNECTED TO TERMINAL 1 SUBBASE WIRING CHANGES ARE NOT REQUIRED SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR OPERATING CONTACTS IN SERIES WITH THE MAIN F...

Страница 6: ...ON AS REQUIRED RA890F IS POWERED AT TERMINAL 6 ONLY WHEN REPLACING ANOTHER MODEL LEAVE HOT LINE L1 CONNECTED TO TERMINAL 1 EVEN THROUGH IT IS NOT NECESSARY FOR OPERATION MAY USE LINE OR LOW VOLTAGE CONTROLLER IF LINE VOLTAGE CONTROLLER IS USED CONNECT IT BETWEEN THE LIMIT CONTROLLER AND TERMINAL 6 JUMPER T T FOR INTERMITTENT IGNITION CONNECT TO TERMINAL 3 OPENING OF A LIMIT CONTROL OR LINE VOLTAGE...

Страница 7: ...SET PUSHBUTTON LOAD RELAY 1K Q270A SUBBASE M8766 FLAME RELAY 2K CAPTIVE MOUNTING SCREWS 10 ARC GAP PROTECTOR OPTIONAL ALARM CONTACT 3 PILOT LINK JUMPER WIRE 0N BASE ALONGSIDE TEST JACK TEST JACK PILOT LINK ARC GAP PROTECTOR M8767 Operation NORMAL OPERATION SUMMARY Normal control operation is summarized below Refer to Fig 5 for the internal schematic of the control 1 Call for heat Load relay pulls ...

Страница 8: ...m all checkout tests indicated below Flame Current Check all installations PilotTurndownTest allinstallationsthatrequireproofof pilot before main fuel valve is opened Safe Shutdown Checks Flame failure power failure limit action all installations Hot Refractory Hold In photocell applications only FLAME CURRENT CHECK The flame current check is the best indicator of proper flame detector application...

Страница 9: ... on the axis of a pilot flame or b Adjusting a flame rod detector so that a larger mini mum pilot is required CAUTION If the pilot needs to be adjusted and rechecked allow five minutes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the comple...

Страница 10: ...ners tested were found to leave deposits on the contact surfaces or to attack RA890 chassis parts Troubleshooting Whentroubleoccursintheheatingsystemanditscauseis not immediately apparent the service technician can apply the following step by step checkout to locate the cause of most problems Refer to Fig 3 and 4 for terminal locations and to Fig 6 for location of component parts CAUTION Use extre...

Страница 11: ... PROBLEMS Relay Chatter Load relay chatter can result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause Difficulty Resetting Safety Switch 30 Second Safety Switch Models _ Ambienttemperaturemaybebelow 10 F 12 C Prob lem is corrected by warm...

Страница 12: ...rol Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Отзывы: