background image

R7500C WIDE RANGE PROPORTIONAL TEMPERATURE CONTROLLER 

COMPENSATION RATIO ADJUSTMENT 

Compensation ratio is the number of degrees temperature 
change required at the compensation sensor to change the 
primary sensor control point one degree F. 

When a compensation sensor (T2) is used, the compensation 
ratio adjustment provides a means for adjusting the effect of 
the compensation sensor on the primary sensor (T1). For 
example, with a compensation ratio setting of 10, a 10 
degree F drop in temperature at the compensation sensor is 
required to increase the controlled temperature 1 degree F. 

This adjustment has a range of 0.25 to 20. A blank table 
provided in the controller is for noting the compensation 
schedule. 

Use the formula below to calculate the compensation ratio for 
hot water reset applications: 

Change in outside air temp.

Comp. Ratio = 

Change in hot water temp. + P.B. 

Adding P.B. to the change in hot water temperature 
compensates for proportional offset. 

CALIBRATION 

The R7500 family of controllers are factory calibrated and 
checked prior to shipment and should operate satisfactorily 
on job startup. 

If the sensor and/or the setpoint potentiometer are a long 
distance from the controller, it may be necessary to 
recalibrate the controller. Calibration potentiometers are 
behind the three holes on the left side of the front panel, see 
Figure 6. To compensate for main sensor and/or setpoint 
potentiometer lead wires or calibration, adjust the middle 
potentiometer R7 (Cal. Pot. No. 2) clockwise. This 
compensates for leadwire length and a controlling 
temperature which is lower than the setpoint. (3.5 degrees 
of rotation per ohm of leadwire resistance or per degree 
off-calibration). 

To compensate for the compensation sensor leadwire 
resistance, adjust the top left potentiometer R1 (Cal. Pot. 
No. 1) clockwise. (3.2 degrees of rotation per ohm of 
leadwire resistance or per degree off-calibration.) Cal. Pot. 
No. 1 also can be used to vary the compensation start point 
(temperature at which compensation affect is zero). The 
factory compensation start point setting is 70F. Turning Cal. 
Pot. No. 1 CCW lowers the compensation start point 
temperature. 

CHECKOUT AND TESTING 

CHECKOUT 

The only checkout ordinarily required is to slowly rotate the 
Setpoint Adjustment through the total proportional band of the 
device to determine if the output devices operate properly. 

If the system does not function properly or the controller 
appears to be out of calibration, proceed with the following 
testing information. 

TESTING 

Before testing, be sure the Controller power supply (11 to 
12 Vdc) is present  at test point (+) and (–1) of R7500 models. 
If the correct supply voltage is not available at these points, 
check the power input device as indicated in the literature 
accompanying the applicable unit. 

NO. 1 (R1) 

CALIBRATION 

POTENTIOMETER 

NO. 2 (R7) 
CALIBRATION 
POTENTIOMETER 

POWER SUPPLY 

TEST POINT (+) 

POWER SUPPLY 

TEST POINT (-) 

OUTPUT VOLTAGE 

TEST POINT Y1 

C8041 

Fig. 6. Test Points and Calibration Adjustment Locations. 

All R7500 series of controllers include test points on the left 
side of the front panel (see Fig. 6). All Controllers have the 
following points— 

Y1  =  Output voltage (yellow leadwire) 
–1  =  Power supply (–), (violet leadwire) 

=  Power supply (+), (orange leadwire) 

Using the appropriate scale voltmeter, insert test probes into 
appropriate holes for voltage checks. 

95-7205 

Содержание R7500C

Страница 1: ...s controller is surface mounted through the two holes in the back of the case Observe ambient temperature 30 to 140F 0 to 60C and relative humidity 5 to 95 limitations No special tools are required to install this controller CAUTION This controller requires a 11 to 12V dc power supply for proper operation The power may be supplied by an R7503 Modutrol Motor Converter R7504 Two Position Converter R...

Страница 2: ...25 4 0 14 1 60 2 6 12 2 00 1 6 10 2 50 1 0 When determining proper wire size remember there are two wires to the sensor and the setpoint potentiometer Double the distance to the sensor or potentiometer to obtain the proper wire length Calibration of the controller will be offset approximately 1F 0 5C for every one ohm of lead wire resistance BALCO MAIN SENSOR MAIN SENSOR BLACK ORANGE ORANGE YELLOW...

Страница 3: ...job drawing or as required TEMPERATURE SETPOINT ADJUSTMENT Integral setpoint adjustment is provided on the R7500C When it is desired to use a remote setepoint adjustment set the integral setpoint adjustment knob to the same temperature as the top end of the remote setpoint scale When using the 14002385 008 remote setpoint assembly set the integral setpoint knob to REMOTE Calibration of the remote ...

Страница 4: ...e which is lower than the setpoint 3 5 degrees of rotation per ohm of leadwire resistance or per degree off calibration To compensate for the compensation sensor leadwire resistance adjust the top left potentiometer R1 Cal Pot No 1 clockwise 3 2 degrees of rotation per ohm of leadwire resistance or per degree off calibration Cal Pot No 1 also can be used to vary the compensation start point temper...

Страница 5: ...utput is not connected wire a 390 ohm load resistor from orange to yellow wires R7500 Adjust setpoint knob to correspond to the ambient temperature at the main sensor Set the proportional band at 5 The output voltage between points Y1 and should be approximately one half power supply voltage minus 0 6 Vdc If this reading is not found the device can be recalibrated by adjusting the calibration pote...

Страница 6: ...ng Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 740 Ellesmere Road P O Box 524 Scarborough Ontario QUALITY IS KEY Minneapolis MN 55408 0524 M1P 2V9 95 7205 Rev 10 95 Printed in U S A ...

Отзывы: