background image

R7500C WIDE RANGE PROPORTIONAL TEMPERATURE CONTROLLER 

WIRING 

All wiring must agree with local electrical codes and 
ordinances. 

Since the Controller circuits are rated NEC Class 2, some 
local codes allow open (no conduit) wiring. 

Number 18 gage 1.0 mm insulated wire or two- or three­
conductor thermostat cable is acceptable for use with these 
Controllers, except on long sensor or remote setpoint 
potentiometer runs where a larger wire size should be used. 
See Table 1. 

All control wiring connections to the Controller are made to 
the 6-inch (152 mm), color-coded leadwires found bundled 
under the cover. There are two orange wires to facilitate 
connections to the converter and/or sensors. 

Crimp type connectors are recommend for field connections 
of the control wiring. Refer to job drawings for specific wiring 
information. See Figures 2 through 4 for some typical 
wiring diagrams. 

IMPORTANT 
Observe color-coding of wires when making connections. 

R7503

BALCO 

CONVERTER 

Table 1. Wire Resistance, Ohms per 1,000 Feet (304m). 

Wire Gage 

Wire Dia. 

Size (mm) 

Ohms/1000 ft 

(304 m) of Wire 

18 

1.00 

6.5 

16 

1.25 

4.0 

14 

1.60 

2.6 

12 

2.00 

1.6 

10 

2.50 

1.0 

When determining proper wire size, remember there are two 
wires to the sensor and the setpoint potentiometer. Double 
the distance to the sensor or potentiometer to obtain the 
proper wire length. Calibration of the controller will be 
offset approximately 1F (0.5C) for every one ohm of lead 
wire resistance. 

BALCO MAIN SENSOR 

MAIN SENSOR 

BLACK 

ORANGE 

ORANGE 

YELLOW 
VIOLET 

POWER 

BROWN 



R7500 

BALCO COMPENSATION 
SENSOR 

BOTH ORANGE WIRES ARE ELECTICALY IDENTICAL.

OPTIONAL DISCHARGE COMPENSATION SENSOR. 
SUBSTITUTE WITH 500 OHM RESISTOR WHEN 
COMPENSATION IS NOT USED. 

C7828 

Fig. 2. Typical Hookup Diagram of R7500C Model with 

Integral Setpoint Adjustment. 

NOTE:   When the compensation sensor is not used, 

substitute a 500-ohm resistor and set the 
compensation ratio at the maximum setting (20). 

M734K 

M745J 

14002385-008 
REMOTE 
SETPOINT 
ADJUST 

BLK 

ORN 

ORN 

YEL 
VIO 

POWER 

BRN 





R7500

270

Ω 

CONNECT Z-D FOR DIRECT ACTION; Z-R FOR 
REVERSE. 

OPTIONAL DISCHARGE COMPENSATION SENSOR. 
SUBSTITUTE WITH 500 OHM RESISTOR WHEN 
COMPENSATION IS NOT USED. 

MOVE WIPER UP TO RAISE SETPOINT. 

BOTH ORANGE WIRES ARE ELECTRICALY IDENTICAL. 

C7829 

BALCO COMPENSATION 
SENSOR 

Fig. 3. Typical Hookup Diagram of R7500C with Remote 

Temperature Selector. 

95-7205  

Содержание R7500C

Страница 1: ...s controller is surface mounted through the two holes in the back of the case Observe ambient temperature 30 to 140F 0 to 60C and relative humidity 5 to 95 limitations No special tools are required to install this controller CAUTION This controller requires a 11 to 12V dc power supply for proper operation The power may be supplied by an R7503 Modutrol Motor Converter R7504 Two Position Converter R...

Страница 2: ...25 4 0 14 1 60 2 6 12 2 00 1 6 10 2 50 1 0 When determining proper wire size remember there are two wires to the sensor and the setpoint potentiometer Double the distance to the sensor or potentiometer to obtain the proper wire length Calibration of the controller will be offset approximately 1F 0 5C for every one ohm of lead wire resistance BALCO MAIN SENSOR MAIN SENSOR BLACK ORANGE ORANGE YELLOW...

Страница 3: ...job drawing or as required TEMPERATURE SETPOINT ADJUSTMENT Integral setpoint adjustment is provided on the R7500C When it is desired to use a remote setepoint adjustment set the integral setpoint adjustment knob to the same temperature as the top end of the remote setpoint scale When using the 14002385 008 remote setpoint assembly set the integral setpoint knob to REMOTE Calibration of the remote ...

Страница 4: ...e which is lower than the setpoint 3 5 degrees of rotation per ohm of leadwire resistance or per degree off calibration To compensate for the compensation sensor leadwire resistance adjust the top left potentiometer R1 Cal Pot No 1 clockwise 3 2 degrees of rotation per ohm of leadwire resistance or per degree off calibration Cal Pot No 1 also can be used to vary the compensation start point temper...

Страница 5: ...utput is not connected wire a 390 ohm load resistor from orange to yellow wires R7500 Adjust setpoint knob to correspond to the ambient temperature at the main sensor Set the proportional band at 5 The output voltage between points Y1 and should be approximately one half power supply voltage minus 0 6 Vdc If this reading is not found the device can be recalibrated by adjusting the calibration pote...

Страница 6: ...ng Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 740 Ellesmere Road P O Box 524 Scarborough Ontario QUALITY IS KEY Minneapolis MN 55408 0524 M1P 2V9 95 7205 Rev 10 95 Printed in U S A ...

Отзывы: