R7426A,B,C TEMPERATURE CONTROLLER
63-2564—1
14
APPENDIX A
Control and Configuration Parameters
The controller includes two groups of settings (I and II) for
control and configuration parameters. These settings are
automatically selected during programming. See Tables 13
NOTES: Parameter
Ctrltyp
determines the setting:
—
Ctrltyp
Lo selects setting I.
—
Ctrltyp
Hi1 and Hi2 select setting II.
Table 13. Control Parameters.
a
Unless otherwise noted.
b
If
tr
is greater than 120 sec, resolution is 30 sec; if
tr
is less than 120 sec, resolution is 10 sec.
c
Reset times are for P+I control.
R742
6
Parameter
Description
Setting I / Setting II
Resolution Unit
a
A B C
#
Name
Low
High
Default
x x x P.01 W1
I01 main setpoint
32
130 / 260
70 / 160
1
°F
x x x P.02 W
lim
I02 limit setpoint (low or high. See C.13)
40
130 / 260
60 / 200
x x x P.03 W
comp
I03 compensation changeover point
20
110
70
1
°F
x x x P.04 Wi
Winter reset
-350
+350
0
2
%
x x x P.05 Su
Summer reset
-100
+100
0
1
x x x P.06 W
cas
Submaster or cascade setpoint
Off, 50
130/260
70/Off
1
°F
x x x P.07 R
cas
Cascade reset span adjustment
0
70
20
x x x P.08 Xp1
I01 Throttling range (main control loop)
1
70
4/20
x x x P.09 Xp2
I02 Throttling range (cascade or limit control
loop)
1
70
20
x x P.10 Xpc
Cooling throttling range (sequence control)
Off, 1
70
6
x x P.11 Xph
Heating throttling range (sequence control)
1
70
12
x x x P.12 tr1
b
Reset time (main control loop)
c
Off,
20 sec
20 minutes
Off
10 sec /
0.5 min
sec /
min
x x x P.13 tr2
b
Reset time (cascade or limit control loop)
c
x x P.14 MINPOS
Minimum position (damper actuators)
0
50
20
1
%
x x x P.15 O
start
Mid-range shift start point (O1)
-40
+40
0
1
°F
x x x P.16 SOFFS
Main setpoint offset (unoccupied mode)
0
20
4 / 10
0.1
x x x P.17 I01Cal
Calibration of sensor I01
-40
+40
0
x x x P.18 I02Cal
Calibration of sensor I02
x x x P.19 I03Cal
Calibration of temperature sensor I03
x x P.20 RetOffs
Return air offset to simulate return air
conditioning
Off, 0
10
Off
x x
P.21 RuntimeO1 Actuator run time (O1)
6
180
60
1
sec
x
P.22 RuntimeO3 Actuator run time (O3)
x
P.23 RuntimeO2 Actuator run time (O2)
x x x P.24 NightLow
Night temperature low limit
Off, 50
70
Off
1
°F
x x x P.25 NightHigh
Night temperature high limit
Off, 70
100
x x x P.26 NOFFS
Main setpoint offset (night mode)
0
60
10 / 40
0.1