Q7055B1047 OPEN VIEW NET SERVER (OVN)

7

95-7711

OPERATION

For complete operating instructions, refer to form no. 74-4036, 
Open View Net User’s Guide.

Location of Parts and Controls

Refer to Figures. 10 and 11 and the following descriptions for 
the location and function of parts and controls.

1—RESET

Hardware reset button. Located directly behind the small hole 
in the front panel. To reach this button, a pointed object like a 
sharp pen or an unfolded paper clip is necessary. Pressing 
this button resets the Excel 5000

 

Open View Net Server 

immediately.

2—POWER

Power indicator. This LED lights up when power is connected 
to the Excel 5000 Open View Net Server.

3—HEARTBEAT LEDS

The BOOT and NML LEDs indicate the status of the Excel 
5000 Open View Net Server. The BOOT LED blinks (Red) 
during boot up. The NML LED lights (Green) during the 
normal operation.

4—C-BUS

C-Bus activity display. This display contains two green LEDs; 
one showing the Excel 5000 Open View Net Server receive 
activity (Rx), and the other showing the Excel 5000 Open 
View Net Server transmit activity (Tx).

Fig. 10. Excel 5000 Open View Net Server front panel.

5—LAN

Local Area Network (LAN) activity display. Shows the actual 
LAN traffic status using three LEDs:

10LNK

. Ethernet speed of 10 mbps indicator (Green). If 

this LED is lit, then the Ethernet link is operating at 
10 mbps.

100LNK.

 Ethernet speed of 100 mbps indicator (Green). If 

this LED is lit, then the Ethernet link is operating at 
100 mbps.

ACTIVITY.

 Link activity indicator (Green) will blink if there 

is any activity (transmission/reception) on the LAN.

6—AC/DC IN 24 V

Power connector for 24 Vac (50 Hz to 60Hz) or 24 Vdc power 
supplies and chassis ground. Power consumption is 8 VA 
(connected via 10/100BaseT, cable). An external power 
supply is required. 

7—10/100BASET

10/100BaseT RJ-45 Ethernet LAN-connector, meets the 
requirements of ANSI/TIA/EIA 586 Category 5, for unshielded 
twisted pair connections.

8—RS-232

9-pin SUB-D male RS-232 connector, electrically isolated, PC 
pin compatible, protected against spikes. This interface is 
used for initial server setup and requires a standard 
Null-Modem cable when interfacing to a PC.

9—C-BUS

2-pin connector for field bus channel 1 connection, electrically 
isolated, meets EMC and FCC requirements. 

10—C-BUS TERMINATION SWITCH

This switch is used to select field bus termination and biasing. 

Fig. 11. Excel 5000 Open View Net Server rear panel.

The system must be maintained in accordance with the 
system documentation and procedures and practices 
contained in applicable standards. The Q7055B1047 OVN 
Server has no user replaceable fuses. 
For service, contact your local Honeywell Automation & 
Control Solutions office as listed in the phone book, or contact 
a regional office as shown at the end of this document.

Jameco

®

 is a registered trademark of Arndt Electronics Corporation

Enterprise Buildings Integrator EBI™ and Excel 5000™ are trademarks of Honeywell International, Inc.

Reset

Power

Test

M25118

1

5

4

2

C-BUS

Rx

Tx

LAN

10

100

ACT

EXCEL

TM

5000

OPEN VIEW NET

3

Boot

NML

M25119

9

10

C-BUS

normal

A(+) B(-)

AC/DC IN

24V

10/100

6

7

8

Содержание Q7055B1047

Страница 1: ...ice providers With its combination of scalable performance density and low per port pricing the OVN allows network layer capabilities to be extended to a much wider range of network configurations and environments OVN supports a full range of Building Management System BMS features such as commanding of points as well as performing complex functions like alarm and schedule management Advanced feat...

Страница 2: ...0013930 001 Mounting Bracket BEFORE INSTALLATION Perform the following steps prior to installing the OVN server 1 Verify that the product has been received without damage 2 Verify that the correct OVN server has been delivered 3 Check the package contents The following items are included in each product package Building Network Adapter device Building Network Adapter driver software CD Building Ne...

Страница 3: ...own on the desk Remove the four feet from the bottom of the OVN by pushing horizontally away from the housing with a flat screwdriver Push the four inserts included fully and horizontally into the housing Adjust the four retaining clips included on top of the inserts Fasten the retaining clips with the included four screws Use the housing with the clips to mark the positions of the four mounting h...

Страница 4: ...EPARATED FROM ALL NON POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1 4 IN 6 MM NOTE TYPICAL MOUNTING LOCATIONS FOR 14005680 089582 592 FIBER OPTIC INTERFACE 1 ALL WIRING MUST BE IN ACCORDANCE WITH NFPA 70 NATIONAL ELECTRICAL CODE AND ALL APPLICABLE LOCAL CODES 2 G GROUNDING CONDUCTOR 3 GROUND CONNECTION 8 32 STUD WITH 8 32 KEPS NUT 4 GROUND CONNECTION FOR 14507678 SERIES PNET PROTECTOR AND OTHER ...

Страница 5: ... at the end of the cable 2 Strip the two power cable ends and insert each cable end into the openings of the 3 pole Phoenix connectors that are marked for power 3 Fasten them with a screwdriver 4 Connect a chassis ground to the third position on this connector as marked NOTE The polarity of the 3 pole Phoenix power connector for DC power supplies is don t care Field Bus Connection The 2 pole Phoen...

Страница 6: ...AN via an Ethernet Hub the required cable should be configured as shown in Fig 8 Fig 8 Straight through pinning for OVN to Ethernet Hub connections Connect OVN to Workstation When an OVN needs a direct connection to a workstation without using an Ethernet Hub a crossover cable is required Fig 9 shows how the different signals should be connected Fig 9 Crossover pinning for OVN to workstation direc...

Страница 7: ...g at 100 mbps ACTIVITY Link activity indicator Green will blink if there is any activity transmission reception on the LAN 6 AC DC IN 24 V Power connector for 24 Vac 50 Hz to 60Hz or 24 Vdc power supplies and chassis ground Power consumption is 8 VA connected via 10 100BaseT cable An external power supply is required 7 10 100BASET 10 100BaseT RJ 45 Ethernet LAN connector meets the requirements of ...

Страница 8: ... Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 www honeywell com buildingsolutions U S Registered Trademark 2006 Honeywell International Inc 95 7711 J I 04 06 ...

Отзывы: