Heavy Duty Pressure Transducers
PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi
Issue B
32313758
Table 6. Output Transfer Function Codes
Fault Condition
Analog Diagnostic Rail
EEPROM Corrupt
below lower rail
Sensor Bridge Open
(any element)
above upper rail
Sensor Bridge Short
(any element)
above upper rail
Low supply voltage
below lower rail
Loss of ground con-
nection
above upper rail
Diagnostics Mode
The PX3 Series diagnostics mode allows the device to indicate
when internal or external faults occur. If an internal fault occurs,
the output will rail to the preset lower or upper limit values shown
in Figure 3 and Table 6.
External faults will result in the sensor’s output exceeding those
preset limits (lower or upper). (For example, if the external sensor
ground (signal) were lost, the sensor output would exceed the up-
per rail of 97.5%.)