6
www.honeywell.com
Introduction
Overview
1.1 Overview
The PW7K1R1E reader interface provides a network connected, single door with
paired reader, PoE based solution to the OEM integrator for interfacing TTL/
Wiegand/RS-485 type readers to door hardware. The on-board twisted pair Ethernet
jack with PoE support enables easy installation.
Note:
For UL installations, do not use POE-powered devices. Power for these devices
must be provided by an UL 294 listed, power limited source (12VDC).
A maximum of 16 PW7K1R1E downstream boards can be connected to PW6K1ICE
controller board.
You can control one physical barrier with PW7K1R1E, using single or paired readers.
The first reader port can accommodate a read head that utilizes Wiegand, magnetic
stripe, or 2-wire RS-485 electrical signaling standards, one or two wire LED controls,
and buzzer control (one wire LED mode only).
The second reader port can accommodate a read head that utilizes Wiegand or
magnetic stripe signaling, one or two wire LED controls, and buzzer control (one wire
LED mode only).
You can use two form-C relay outputs for door strike control or alarm signaling.The
relay contacts are rated at 5A @ 30VAC/DC, dry contact configuration. Four inputs
are provided for monitoring the door contacts, exit push buttons, and alarm contacts.
The PW7K1R1E requires power from PoE or local 12VDC. The reader power should
be based on peak reader power consumption.
The PW7K1R1E may be mounted in a 3-gang switch box; a mounting plate is
supplied with the unit. The PW7K1R1E may be mounted in an enclosure; the supplied
mounting plate has mounting holes that match the MR50 mounting footprint.
The PW7K1R1E has to be installed on the same subnet as PW6101 (i.e., PW6K1ICE)
or PW6000. The encryption between both PW6000 and PW6K1ICE, and, PW6101
and PW6K1ICE, is built-in and automatic.
1.2 Warranty
Honeywell Security Access warrants that the product is free from defects in material
and workmanship under normal use and service with proper maintenance for one year
from the date of factory shipment.
Honeywell Security Access assumes no responsibility for products damaged by
improper handling or installation. This warranty is limited to the repair or replacement
of the defective unit.
There are no expressed warranties other than set forth herein. Honeywell Security
Access does not make, nor intends, nor does it authorize any agent or representative to
make any other warranties, or implied warranties, and expressly excludes and
disclaims all implied warranties of merchantability or fitness for a particular purpose.