background image

PS1202A REPLACEMENT POWER SUPPLY KIT FOR ELECTRONIC AIR CLEANER

3

69-1136EF—01

Fig. 3. Internal schematic for F50F and F58F Electronic Air Cleaner with W8600E.

Fig. 4. Retrofitted schematic for F50F and F58F Electronic Air Cleaner with W8600E.

BLACK

1

2

3

4

1

2

3

4

TERMINAL STRIP

FRONT

BACK

TO

W8600E

WALL

PANEL

W4

W2

W1

W3

AIRFLOW SWITCH BOARD

ORANGE

GRAY

VIOLET

BLACK

1   INTERLOCK SWITCH.

2   OZONE REDUCTION JUMPER.

3   AIRFLOW SWITCH DISABLE JUMPER.

4   ONE-CELL UNIT SIMILAR, BUT WITH JUST ONE CELL.

5   P1, P2 TERMINALS ON 120V MODELS ONLY.  POWER CONNECTIONS ON 240V MODELS ARE TO 

     QUICK-CONNECTS ON POWER SUPPLY TRANSFORMER.  BROWN LEAD GOES TO TOP TERMINAL 

     AND BLACK LEAD TO BOTTOM TERMINAL.

M15096B 

2

4

BLACK

RED

CONTACT

BOARD

RED IONIZER

BLACK COLLECTOR

BLACK

5

BLACK

BLACK

BROWN

BLACK

GREEN

3

1

P4

P1

P2

J3

POWER SUPPLY

J4

J8

P3

2.1mA

1.65mA

1.29mA

1.05mA

0.9mA

0.25mA

P5

T1

U4

8150V

7500V

P8

E6

E4

E5

E3

E1

E2

J1

J2

J1

5

3

2

1

BLACK

WHITE

GROUND

CHOKE

P4

P1

P2

J3

POWER SUPPLY

J4

J1

P3

2.1mA

1.65mA

1.29mA

1.05mA

0.9mA

0.25mA

P5

T1

U4

8150V

7500V

P8

E6

E4

E5

E3

E1

E2

BLACK

B4

R3

Y2

G1

1

2

3

5

W4 W2 W1 W3

AIRFLOW SWITCH BOARD

ORANGE

GRAY

VIOLET

BLACK

1   INTERLOCK SWITCH.

2   OZONE REDUCTION JUMPER.

3   AIRFLOW SWITCH DISABLE JUMPER.

4   W8600E REMOTE PERFORMANCE INDICIATOR DRIVER.

5   NEON LIGHT.

M15097B

POWER

SUPPLY

5

BLACK

4

BLACK

BLACK

BROWN

L1    L2

BLACK

GREEN

3

1

J1

J2

GREEN

YELLOW

RED

BLUE

BLACK

RED

CONTACT

BOARD

RED IONIZER

BLACK COLLECTOR

J8

GROUND

CHOKE

2

Содержание PS1202A

Страница 1: ... damage the product or cause a hazard ous condition such as electrical shock 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING ELECTRICAL HAZARD Can Cause Electric...

Страница 2: ...onnect power for directly wired devices See Fig 3 or 4 for internal schematic The air cleaner operates correctly at any fan speed on a multispeed or modulated speed system wired with conduit or plugged in NOTE To reduce the risk of electric shock this product has a grounding type plug with a third grounding pin This plug fits only into a grounding type power outlet If the plug does not fit into th...

Страница 3: ...GOES TO TOP TERMINAL AND BLACK LEAD TO BOTTOM TERMINAL M15096B 2 4 BLACK RED CONTACT BOARD RED IONIZER BLACK COLLECTOR BLACK 5 BLACK BLACK BROWN BLACK GREEN 3 1 P4 P1 P2 J3 POWER SUPPLY J4 J8 P3 2 1mA 1 65mA 1 29mA 1 05mA 0 9mA 0 25mA P5 T1 U4 8150V 7500V P8 E6 E4 E5 E3 E1 E2 J1 J2 J1 5 3 2 1 BLACK WHITE GROUND CHOKE P4 P1 P2 J3 POWER SUPPLY J4 J1 P3 2 1mA 1 65mA 1 29mA 1 05mA 0 9mA 0 25mA P5 T1 U...

Страница 4: ...mal Test Button When pushed the test button shorts from collector voltage to ground The resulting arcing sound indicates that high voltage is being supplied to the collector The solid state power supply controls current flow to the collector On air cleaners with a W8600E the CHECK LED comes on when the test button is held down Fig 6 Use an ohmmeter to check the electronic cells for short circuits ...

Страница 5: ...WIRING BETWEEN W8600E AND AIR CLEANER USE MAX NO 18 4 WIRE THERMOSTAT CABLE CONNECTED 1 G TO 1 G 2 Y TO 2 Y 3 R TO 3 R AND 4 B TO 4 B WIRING OK CORRECT WIRING REPLACE W8600E 3 CHECK FOR CORRECT INPUT VOLTAGE ACROSS P1 AND P2 TERMINALS ON POWER SUPPLY INSPECT CELL S FOR BENT COLLECTOR PLATES BROKEN IONIZER WIRES DIRT ON INSULATORS DAMAGED IONIZER OR COLLECTOR CONTACT TABS YES NO YES NO FIX WIRING R...

Страница 6: ...d carbon filter downstream from the air cleaner Make sure particles from the air filter cannot fall into the air cleaner WARNING ELECTRIC SHOCK HAZARD Can Cause Personal Injury Only a trained service technician should perform the following procedure 2 To reduce ozone production about 20 to 25 percent and reduce efficiency about seven to ten percent depending on actual airflow delivered by the fur ...

Страница 7: ... or reinstallation costs This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was caused by damage that occurred while the product was in the possession of a consumer Honeywell sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CO...

Страница 8: ...C AIR CLEANER Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2012 Honeywell International Inc 69 1136EF 01 M S 03 12 Printed in United States ...

Страница 9: ...ement de P5 INSTALLATION Lors de l installation de ce produit 1 Lire attentivement ces instructions Le non respect des instructions peut endommager le produit ou provoquer une situation dangereuse telle que des chocs électriques 2 Vérifier les caractéristiques nominales indiquées dans les instructions et sur le produit pour s assurer que le produit correspond bien à l appli cation prévue 3 L insta...

Страница 10: ...on Brancher les fils aux bornes du nouveau bloc IMPORTANT Ne pas épisser les fils de l ionisateur et du collecteur Ces fils doivent être intacts pour éviter les chocs électriques par le connecteur ou le ruban couvrant l épissure Brancher l épurateur d air électronique directement dans la prise de tension et de fréquence correctes ou rétablir l alimentation pour les dispositifs directement câblés V...

Страница 11: ... et F58F avec W8600E NOIR 1 2 3 4 1 2 3 4 BORNIER AVANT ARRIÈRE VERS PANNEAU MURAL W8600E W4 W2 W1 W3 TABLEAU DE COMMUTATEUR DE DÉBIT D AIR ORANGE GRIS VIOLET NOIR 1 INTERRUPTEUR DE VERROUILLAGE 2 CAVALIER DE RÉDUCTION D OZONE 3 CAVALIER DE DÉSACTIVATION DE COMMUTATEUR DE DÉBIT D AIR 4 UNITÉ À UNE CELLULE SIMILAIRE MAIS AVEC UNE CELLULE SEULEMENT 5 BORNES P1 P2 SUR MODÈLES 120 V SEULEMENT LES CONN...

Страница 12: ...NOIR NOIR MARRON L1 L2 NOIR VERT 3 1 J1 J2 VERT JAUNE ROUGE BLEU NOIR ROUGE PLAQUE À CONTACTS IONISATEUR ROUGE COLLECTEUR NOIR J8 INDUCTEUR DE TERRE 2 NOIR B4 R3 Y2 G1 1 2 3 5 W4 W2 W1 W3 TABLEAU DE COMMUTATEUR DE DÉBIT D AIR ORANGE GRIS VIOLET NOIR 1 INTERRUPTEUR DE VERROUILLAGE 2 CAVALIER DE RÉDUCTION D OZONE 3 CAVALIER DE DÉSACTIVATION DE COMMUTATEUR DE DÉBIT D AIR 4 ENTRAÎNEMENT DE L INDICATEU...

Страница 13: ...lecteur Sur les épurateurs avec W8600E la DEL Vérification s allume lorsque le bouton de test est maintenu pressé Fig 6 Utiliser un ohmmètre pour vérifier l absence de court circuit au niveau des cellules électroniques DEL Vérification épurateurs d air avec W8600E La DEL Vérification sur le W8600E s allume pour indiquer les problèmes suivants accumulation excessive de saleté supérieure à celle req...

Страница 14: ... 1 G À 1 G 2 Y À 2 Y 3 R À 3 R ET 4 B À 4 B CÂBLAGE OK CÂBLAGE OK REMPLACER LE W8600E 3 VÉRIFIER QUE LA TENSION D ENTRÉE EST CORRECTE ENTRE LES BORNES P1 ET P2 DU TABLEAU D ALIMENTATION INSPECTER LA OU LES CELLULES POUR DÉTECTER LES PROBLÈMES SUIVANTS PLAQUES DE COLLECTEUR COURBÉES FILS D IONISATEUR CASSÉS SALETÉ SUR LES ISOLATEURS LANGUETTES DE CONTACT DE COLLECTEUR OU IONISATEUR ENDOMMAGÉES OUI ...

Страница 15: ... l épurateur d air b Ouvrir la porte d accès c Retirer le couvercle du boîtier d alimentation Voir la Fig 1 d Repérer la tige de court circuit J8 sur le bloc d alimentation Voir la Fig 8 Retirer la tige de court circuit et la réinstaller sur une seule broche REMARQUE L ozone sera réduit et la tige de court circuit peut être réinstallée ultérieurement si nécessaire e Replacer le couvercle et la por...

Страница 16: ...0 1885 Douglas Drive Golden Valley MN 55422 La présente garantie ne couvre pas les frais de retrait ou de réinstallation La présente garantie ne s appliquera pas s il est démontré par Honeywell que la panne ou le mauvais fonctionnement sont dus à un endommagement du produit alors que le consommateur l avait en sa possession La responsabilité exclusive de Honeywell se limite à réparer ou à remplace...

Отзывы: