Installing the PRO4200 Two Reader Module
Wiring Diagram for Connectors TB1,TB7-9
OP40HONE, OP90HONE, OT30HONA, OT31HONA, OT35HONA, and
OT36HONA.
Each reader port supports a reader with TTL interface. Power to the reader is
selectable as 5VDC or 12VDC (pass-through). This selection is done by setting the
jumpers J2 for reader 1 and J3 for reader 1. Set jumper at position "5" for 5VDC or
"12" for pass-through 12VDC. The factory defaults set J2 and J3 to "5".
For wiring to a reader port
The LED control terminal in each reader port can be configured via host software to
support one-wire single or bi-colored reader LED. An example of the most common
configuration is shown below. If Beeper Control is not used, its terminal can be
programmed to be the second wire for the two-wire bi-colored reader LED.
To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader
port configuration is set via host software
Input Wiring
Inputs 0 to 7 may be configured to use normally open or normally closed contacts and
non-supervised or supervised (with standard ±1% tolerance 1K ohm). Four of these
Table 4:
Settings for Wiring to a Reader Port
Terminal
Typical Wire
Color
Wiegand
Reader
Clock/Data
Readers
1
Red
Power (5 or
12 Vdc)
Power (5 or 12
Vdc)
2
Brown
LED control
LED control
3
Yellow
Beeper
Control
Beeper
Control
4
White
Data 1
Signal
Clock Signal
5
Green
Data 0
Signal
Data 0
Signal
6
Black
Common
Common
Table 5:
LED Output->
High
Tri- Stated
Low
Single Color LED
LED ON
LED OFF
LED OFF
Bi- Color LED
Green LED ON
Both LEDs OFF
Red LED ON