Installing the PRO4200 Two Reader Module

Wiring Diagram for Connectors TB1,TB7-9

PRO4200 Two-reader module User Guide, Document 800-25698V1

19

Note:  

The SIO board port for a PRO42IC in WIN-PAK is port 6 and is set as the 

default.
Each reader port supports a reader with TTL (D1/D0, Clock/Data), F/2F, or 2-wire 

RS-485 signaling. Power to the reader is selectable:

Input on supervised F/2F readers may be unsupervised or supervised (supervised 

shown).

Reader Wiring

The following Honeywell reader module numbers have been approved by UL for use 

with the PRO4200: OM40BHONA, OM55BHONA, OP10HONE, OP30HONE, 

Reader\ Input\ Output

0

1

Reader\ Input\ Output

1

2

Содержание PRO4200

Страница 1: ...September 2020 2020Honeywell International Inc All rights reserved 800 25698V1 I PRO4200 Two Reader Module PRO42R2 Installation Guide ...

Страница 2: ...or notice WIN PAK is a trademark of Honeywell International Inc Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellaccess com to post your comments Discover Customer Portal Self Service Produc...

Страница 3: ...EE Marking vii Unpacking Procedure vii Shipping Instructions ix Limited Warranty ix Confidentiality x Installing the PRO4200 Two Reader Module Description 11 Specification 12 Set Up 13 LED Operation 15 Power 16 Communications 16 Wiring 17 Wiring Diagram for Connectors TB1 TB7 9 18 2 Reader Input Module Programming Guide 25 CONTENTS ...

Страница 4: ...iv www honeywell com This page is left blank intentionally for double sided printing ...

Страница 5: ... what to do is a life safety requirement Always make certain that any required approvals are obtained in writing DO NOT ACCEPT VERBAL APPROVALS BECAUSE THEY ARE NOT VALID Honeywell never recommends using the PRO4200 or related products for use as a primary warning or monitoring system Primary warning or monitoring systems should always meet local fire and safety code requirements The installer mus...

Страница 6: ...rference in which case the user will be required to correct the interference at his own expense Note This document and the data in it shall not be duplicated used or disclosed to others for procurement or manufacture except as authorized by and with the written permission of Honeywell Inc The information contained in this document or in the product itself is considered the exclusive property and t...

Страница 7: ... 5SB Scotland United Kingdom Tel 44 0 1698 738200 Email UK64Sales Honeywell com CE and WEEE Marking Description of the used symbol Unpacking Procedure Caution If any damage to the shipment is noticed before unpacking a claim must be filed with the commercial carrier All containers should be opened and unpacked carefully in order to prevent damage to the contents The following steps are used to unp...

Страница 8: ...Notices Unpacking Procedure viii www honeywell com If shipping caused damage to the unit a claim must be filed with the commercial carrier If any other defect is apparent call for a return authorization ...

Страница 9: ...A number prior to returning any Product for service repair credit or exchange Honeywell warrants that its Products shall be free from defects in materials and workmanship for a period of two years from date of shipment of the Product to Customer The warranty on Terminals Printers Communications Products and Upgrade kits is 90 days from date of shipment Satisfaction of this warranty shall be limite...

Страница 10: ... as confidential Customer shall acquire no rights in the design of the Products or the related materials except to use such information solely for the purpose of and only during the time it sells the Products Customer shall not copy the design of any of the Products or use or cause to be used any Product design or related materials for its own benefit or for the benefit of any other party The cove...

Страница 11: ...s edge the next two connectors provide the reader and associated I O terminals for reader 1 The last connector on the rack mount edge provides terminals for two additional general purpose inputs When the board is mounted flat two additional relay outputs and two additional general purpose inputs are available along with two dedicated inputs for cabinet tamper and power fault detection on the oppos...

Страница 12: ... resistors 1k ohm 1 tolerance 2 unsupervised dedicated inputs Communication Wire requirements Mechanical Environment RS 485 Range 9 600 to 38 400 bps Power 1 twisted pair 18AWG Honeywell 3114 or equivalent RS 485 24 AWG 4 000 feet 1 200 m max twisted pair with shield 120 23pF Honeywell 3328 or equivalent Inputs 1 twisted pair per input 30 ohms max Outputs As required for the load Readers 6 conduct...

Страница 13: ...vides 12 VDC J3 Position 5 Reader 2 Power terminal provides 5 VDC Position 12 Reader 2 Power terminal provides 12 VDC S8 S7 S6 S5 S4 S3 S2 S1 Selection OFF OFF OFF OFF ON ADDRESS 1 OFF OFF OFF ON OFF ADDRESS 2 OFF OFF OFF ON ON ADDRESS 3 OFF OFF ON OFF OFF ADDRESS 4 OFF OFF ON OFF ON ADDRESS 5 OFF OFF ON ON OFF ADDRESS 6 OFF OFF ON ON ON ADDRESS 7 OFF ON OFF OFF OFF ADDRESS 8 OFF ON OFF OFF ON ADD...

Страница 14: ...20 ON OFF ON OFF ON ADDRESS 21 ON OFF ON ON OFF ADDRESS 22 ON OFF ON ON ON ADDRESS 23 ON ON OFF OFF OFF ADDRESS 24 ON ON OFF OFF ON ADDRESS 25 ON ON OFF ON OFF ADDRESS 26 ON ON OFF ON ON ADDRESS 27 ON ON ON OFF OFF ADDRESS 28 ON ON ON OFF ON ADDRESS 29 ON ON ON ON OFF ADDRESS 30 ON ON ON ON ON ADDRESS 31 OFF OFF Reserved OFF ON 9 600 BPS ON OFF 19 200 BPS ON ON 38 400 BPS OFF Not Used S8 S7 S6 S5 ...

Страница 15: ...the relay is energized The assignment for each relay status LED is shown in the following table The following table lists the LEDs D1 through D4 Table 2 LED Settings Mode LED D1 LED D2 Description Power up sequence ON OFF Start power up hardware setup OFF ON Testing RAM ON ON Testing ROM and completing initialization FLASH ON LED D1 flashes 4 times after power up is completed Normal Operation FLAS...

Страница 16: ...rs and is available at both reader connectors Note POLARITY for 12VDC power is important Make sure the 12 VDC is connected to the terminal labeled 12V and the return is connected to the terminal labeled GND Communications The Two Reader Module communicates to the host controller via an RS 485 interface The interface allows for multi drop communication of up to 4 000 feet D6 Input1 D7 Input 2 D8 In...

Страница 17: ... for DIP switch settings For wiring to an RS 485 port 1 TR is the plus side of the transmit and receive differential signal 2 TR is the negative side of the transmit and receive differential signal 3 GND is the signal ground The wiring for this signal is required and NOT optional This signal must NOT be connected to chassis GND 4 Use 24 AWG low capacitance twisted pair shielded cable Honeywell 332...

Страница 18: ...assis GND Inside Panel Chassis GND Inside Panel Voltage is selected by Jumper J2 On Board Voltage is selected by Jumper J2 On Board RED BROWN YELLOW WHITE GREEN BLACK DRAIN RED BROWN YELLOW WHITE GREEN BLACK DRAIN BLACK RED D1 D2 D3 D4 D15 D16 D17 D20 D18 D19 D5 D6 D7 D8 D9 D10 D11 D12 D13 D14 RS 485 TR RS 4845 TR RS 485 GND 12V GND READER1 V READER1 LED READER1 BZR READER1 D1 READER1 D0 READER1 G...

Страница 19: ...he default Each reader port supports a reader with TTL D1 D0 Clock Data F 2F or 2 wire RS 485 signaling Power to the reader is selectable Input on supervised F 2F readers may be unsupervised or supervised supervised shown Reader Wiring The following Honeywell reader module numbers have been approved by UL for use with the PRO4200 OM40BHONA OM55BHONA OP10HONE OP30HONE Reader Input Output 0 1 Reader...

Страница 20: ...shown below If Beeper Control is not used its terminal can be programmed to be the second wire for the two wire bi colored reader LED To fully utilize each reader port a 6 conductor cable 18AWG is required Reader port configuration is set via host software Input Wiring Inputs 0 to 7 may be configured to use normally open or normally closed contacts and non supervised or supervised with standard 1 ...

Страница 21: ...to indicate safe condition Input configuration including debounce and hold time is set via host software Control Output Wiring Six form C relay contacts are provided for controlling door strike or other devices Each may be assigned to door related functions or general purpose output They are configurable as standard energize to activate or fail safe de energize to activate via host software The en...

Страница 22: ...al purpose inputs two general purpose outputs and two dedicated inputs are not accessible and should not be used The most common reason for mounting a board flat is that it is being installed remotely to be located near the door s being monitored In this case it will be mounted in its own enclosure creating the need to monitor cabinet tamper and power fault detection inputs The two additional gene...

Страница 23: ... 25698V1 23 6 Connect relay output wiring as appropriate 7 Connect communications wiring to the Intelligent Controller 8 Recheck wiring for correct connections and continuity 9 When all boards have been installed connect the power supply cord for proper 10 connections and power 11 Set up the panel controls using the host software ...

Страница 24: ...24 www honeywell com Installing the PRO4200 Two Reader Module Wiring Diagram for Connectors TB1 TB7 9 This page is left blank intentionally for double sided printing ...

Страница 25: ...Powerfail Shunted Termination Jumper J1 Not Active RS485 Port Power Connector Connected Cable Cable Destination Conductor Color RS485 TX Pin 1 RS485 RX Pin 2 Common Pin 3 Power Power Connector Connected Cable Cable Destination Conductor Color Power Pin 1 Power Pin 2 Inputs 4 and 5 Connected Cable Cable Destination Conductor Color Input 4 Pin 1 Input 4 Com Pin 2 Input 5 Pin 3 Input 5 Com Pin 4 Door...

Страница 26: ... Reader 1 in WIN PAK Door 2 Input Output Connected Cable Cable Destination Conductor Color Input 2 Pin 1 Input 2 Com Pin 2 Input 3 Pin 3 Input 3 Com Pin 4 Relay 2 No Pin 5 Relay 2 Com Pin 6 Relay 2 NC Pin 7 Relay 3 No Pin 8 Relay 3 Com Pin 9 Relay 3 NC Pin 10 Reader 2 WIN PAK Reader 2 the reader address used in the WIN PAK hardware setup VDC Select J2 5 Volt Connected Cable Cable Destination Condu...

Страница 27: ...25 Inputs 6 and 7 Connected Cable Cable Destination Conductor Color Input 6 Pin 1 Input 6 Com Pin 2 Input 7 Pin 3 Input 7 Com Pin 4 Inputs 4 and 5 Connected Cable Cable Destination Conductor Color Relay 4 NC Pin 1 Relay 4 Com Pin 2 Relay 4 NO Pin 3 Relay 5 NC Pin 4 Relay 5 Com Pin 5 Relay 5 NO Pin 6 ...

Страница 28: ...26 www honeywell com 2 Reader Input Module Programming Guide This page is left blank intentionally for double sided printing ...

Страница 29: ... login discover default asp YouTube Honeywell Help and Support https www youtube com channel UCBEL6ouNV_LN5lEpYRujMTg featured Honeywell Access Systems 135 W Forest Hill Avenue Oak Creek WI 53154 United States 800 323 4576 414 766 1798 Fax www honeywellaccess com Specifications subject to change without notice Document 800 25698V1 2020 Honeywell All rights reserved ...

Отзывы: