THX9321/9421 Prestige
®
IAQ and RF EIM
19
69-2490—03
Heat pump with outdoor temperature lockouts
Heat pump and backup heat operation
Outdoor temperature lockouts are optional. See Installer Setup
options (ISU 3120).
Heat pump only
Heat pump with backup heat as needed *
Backup heat only
Heat pump only
Heat pump or backup heat operates *
Backup heat only
Outdoor temperature
Outdoor temperature
Backup heat lockout
Backup heat lockout
Compressor lockout
Compressor lockout
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup Heat
Upstage Timer expires.
Heat pump stays ON when backup heat turns on.
* No backup heat unless indoor temperature drops to selected Backup Heat Differential setting, or Backup
Heat Upstage Timer expires.
Heat pump turns OFF when backup heat turns on.
Backup heat allowed to run with heat pump
(see table below)
Backup heat NOT allowed to run with heat pump
(see table below)
Electric forced air
Allowed to run with heat pump
Thermostat controls fan
Gas or oil forced air
NOT allowed to run with heat pump
Equipment controls fan
Hot water radiant heat
Allowed to run with heat pump
[n/a]
Hot water fan coil
Selectable in installer setup
Thermostat controls fan
Other
Selectable in installer setup
Selectable in installer setup
Backup Heat Type
Backup Heat Operation
Backup Heat Fan Operation
69-2490_B.indd 19
7/13/2011 1:42:00 PM