
3
NOTE:
If an EIM is mounted inside a metal cabinet, it is recommended to use
a THM4000R1000 Wireless Adapter for extended wireless range. Mount the
Wireless Adapter outside the metal cabinet and connect to the ABCD terminals at
the EIM.
NOTE:
When installing multiple
thermostats and EIMs, mount the
EIMs at least 2 feet apart for best
RedLINK performance.
1.1 Mount EIM.
Mount the EIM near the HVAC
equipment or on the equipment
itself.
Use screws and anchors as
appropriate for the mounting
surface.
1.2 Wire EIM as shown.
Refer to the table and wiring diagrams on pages 3-5.
NOTE:
If you are installing discharge and return air sensors, refer to the mounting
instructions in the Alerts and Delta T Diagnostics Installation Instructions packed
in the kit.
1
Installing the equipment interface module (EIM)
Terminal Designations
Conventional System
Heat Pump
Terminal
Description
Terminal
Description
C
Common wire from 24 VAC
transformer.
C
Common wire from 24 VAC
transformer.
R*
Power wire from 24 VAC
transformer.
R
Power wire from 24 VAC
transformer.
RH*
Heating power.
RH
Heating power.
RC*
Cooling power.
RC
Cooling power.
W
Heat Stage 1
O/B
Changeover valve for heat pumps.
W2
Heat Stage 2
AUX 1
Backup Heat Stage 1/Emergency
Heat Stage 1
W3
Heat Stage 3
AUX 2
Backup Heat Stage 2/Emergency
Heat Stage 2
Y
Compressor Stage 1
Y
Compressor Stage 1
Y2
Compressor Stage 2
Y2
Compressor Stage 2
G
Fan Relay
G
Fan Relay
A
Connect to Economizer Module or
Lighting Panel (TOD).
L/A
Connect to Compressor Monitor,
Zone Panel, Economizer Module or
Lighting Panel (TOD).
*
Remove jumpers when separate transformers are used.
R
C
Y
Y2
G
W
O/
B
W2
AUX1
W3
AUX2
A L/A