PP904A and B Differential

 

Pressure Regulators

 

INSTALLATION INSTRUCTIONS 

BEFORE INSTALLATION 

CAUTION 

Equipment Damage Hazard. 

Putting stress on the lever assembly can destroy the 
accuracy. Do not move or lift the PP904 by the lever 

assembly. 

Do not remove the shipping protection until after the device is 

permanently mounted. See Fig. 1. 

Special Equipment 

Magnehelic Gage of appropriate range, if not part of the 
system. 

Fig. 1. PP904A and B shipping protection 

(PP904B shown). 

LEVER ASSEMBLY 

SHIPPING 
PROTECTION 
FOAM 

SHIPPING 
TIES 

M18381 

® U.S. Registered Trademark 
Copyright © 2002 Honeywell •  All Rights Reserved 

INSTALLATION 

Mounting 

1.

  

Mount the device in any position using four no. 10

 

screws obtained locally. See Fig. 2.

 

2.

  

Remove the cover. 

3.

  

Remove the shipping protection foam between the flap-

per and the nozzle. See Fig. 1. 

4.

  

Cut and remove the two shipping ties. 

FOUR 
NO. 10 
SCREWS 

8-1/4 (210) 

2-1/4 

(57) 

9 (229) 

PIGTAILS (PP904A ONLY) 

2-1/2 (63) MIN. 

CLEARANCE 

FOR COVER 

REMOVAL 

4-1/8 
(105) 

8-1/8 (206) 

PIGTAILS (PP904A ONLY) 

C3952 

Fig. 2. PP904A and B approximate 

dimensions in in. (mm). 

95-5519EF 

Содержание PP904A

Страница 1: ...B shipping protection PP904B shown LEVER ASSEMBLY SHIPPING PROTECTION FOAM SHIPPING TIES M18381 U S Registered Trademark Copyright 2002 Honeywell All Rights Reserved INSTALLATION Mounting 1 Mount the device in any position using four no 10 screws obtained locally See Fig 2 2 Remove the cover 3 Remove the shipping protection foam between the flap per and the nozzle See Fig 1 4 Cut and remove the tw...

Страница 2: ... A DIRECT ACTING SHOWN M18384 Fig 4 Velocity pressure sensing with flow measuring station To Static Pressure Sensing Heads 1 Push the branch and main tubing onto the PP904A pig tail connectors or the PP904B restrictor See Fig 3 NOTE The PP904A connectors are 1 4 in 6mm pigtail for main line and 5 32 in 4mm pigtail for branch line The PP904B restrictor has 1 4 in 6mm connectors 2 Install the 140042...

Страница 3: ...esired setting See Fig 3 2 Tighten the knob 3 Turn the coarse setpoint adjustment knob to position the pointer to the desired setting on the setpoint scale 4 Connect a Magnehelic Gage between the A and C con nections if not part of the system If desired a 0 to 30 psi gage can be teed into the PP904A branch line to read the branch line pressure 5 With the system running and the PP904 in control tur...

Страница 4: ... Printed in U S A on recycled paper containing at least 10 customer honeywell com post consumer paper fibers 95 5519EF J H Rev 1 02 ...

Страница 5: ... POUR L EXPÉDITION MF18381 U S Registered Trademark Copyright 2002 Honeywell All Rights Reserved INSTALLATION Montage 1 Monter l appareil dans n importe quelle position au moyen de quatre vis n 10 non comprises Voir la Fig 2 A C 210 8 1 4 57 2 1 4 229 9 RACCORDS EN TIRE BOUCHON PP904A SEULEMENT QUATRE VIS Nº 10 Fig 2 Encombrement approximatif en mm po des PP904A et B DÉGAGEMENT DE 63 2 1 2 MIN POU...

Страница 6: ...EVIER DE RÉGLAGE DU C POINT DE CONSIGNE A NIVEAU DE NIVEAU DU COMMANDE À ACTION DIRECTE ILLUSTRÉE RÉGLAGE MF18384 POINT DE DE LA BANDE CONSIGNE PROPORTIONNELLE Fig 4 Détection de la pression dynamique avec poste de mesure des débits BUSE Vers les têtes du capteur de pression statique 1 Relier les canalisations principale et secondaire aux raccords en tire bouchon du PP904A ou au limiteur de débit ...

Страница 7: ...tionnelle TR et placer l index au réglage voulu Voir la Fig 3 2 Serrer le bouton 3 Tourner le bouton de réglage rapide du point de con signe de manière à placer l index au réglage voulu sur l échelle de point de consigne 4 Connecter un débitmètre à hélice entre les raccords A et C si le système ne comprend pas de tel débitmètre Insérer s il y a lieu un manomètre de 0 à 30 psi dans la canalisation ...

Страница 8: ...neywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you ...

Отзывы: