POL-200-TS User Manual
15
According to the protocol used (refer to par. 3.5), the system shows the position and the type of
device connected.
CLIP PROTOCOL
• “
O
” Optical Sensor
• “
H
” or “T” Heat/Thermal sensor
• “
I
” ionization sensor
• “
M
” Multi-Sensor. Optical/ thermal
• “
P
” Pinnacle Laser
• “
L
” VIEW Laser
• “
S
” Smart Multi-criteria
Section of Modules - Symbols of identifica-
tion by type:
• “
I
” or “
E
” Input Modules including
Manual Call Points
• “
O
” or “
S
” Output modules
• “
R
” Output modules without End-of-
Line (EOL) by default Relays
• “
Z
” Zone modules for conventional de-
tectors
ADVANCED PROTOCOL
For advanced protocol loops, POL-200-TS
also identifies the following elements:
• “
S
” SMART 4
• “
B
” Beam detectors
• “
P
” Indoor Manual Call Point
• “
M
” FAAST Aspiration unit
To select between CLIP and ADVANCED Protocol please access the configuration screen and
select one of the two protocols available from the button line.
Lower Case or Capital Letter:
if a lower case letter appears in the reading cycle, please confirm
in the configuration that the correct protocol is selected among these different options “Notifi-
er”, “Morley”, “System Sensor” or “Honeywell HBS”.
In case in one address a device changes the type ID or in case of a change from lower case
to capital letter, please check the wiring in this device as its answer is not correct. This can be
caused by a defective device or noise due to interferences.
Содержание POL-200-TS
Страница 1: ...POL 200 TS User Manual 1 User Manual ANALOGUE LOOP DIAGNOSTIC TOOL POL 200 TS ...
Страница 22: ...POL 200 TS User Manual 22 Notes ...
Страница 23: ...POL 200 TS User Manual 23 Notes ...