PEHA_M_940_16_AM (Rev06_130213)

GB - 1

126056-05

PEHA Elektro GmbH & Co. KG

Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: [email protected] • Internet: www.peha.de

 

SwITchIng conDITIonS For voLTage SwITch-on

You can select the switching states OFF, Memory and ON of the relay‘s from the PHC 

output modules on voltage switch-on or recovery in the PHC software under the menu 

item “

Components 

g

 Switch-on Conditions

”. The switching conditions are pre-set to 

“OFF” by the system. The “Memory” switching condition is selected if, for example, 

after voltage has been recovered following an interruption of > 50 ms, you want the 

output module to retain its previous switching state from the controller.

currenT conSumPTIon

To calculate the current consumption for the power supply, you should assume a 

consumption of 60 mA (internal consumption 10 mA, per relay 7 mA). When a relay 

is switched on the current increases to 150 mA for about 2 seconds.

TechnIcaL DaTa

PermITTeD LoaDS For The reLay ouTPuTS

warranTy conDITIonS

These operating instructions are an integral part of both the device and our terms of 

warranty. They must be handed over to the user. The technical design of the appliance 

is  subject  to  change  without  prior  notification. 

PEHA

 products are manufactured 

and quality-checked with the latest technology according to applicable national and 

international regulations. Nevertheless, if a product should exhibit a defect, 

PEHA

 

warrants to make remedy as follows (regardless of any claims against the dealer to 

which the end user may be entitled as a result of the sales transaction):

In the event of a justified and properly established claim, 

PEHA

 shall exercise its 

prerogative to either repair or replace the defective device. Further claims or liability 

for consequential damage are explicitly excluded. A justifiable deficiency is deemed to 

exist if the device exhibits a structural, manufacturing, or material defect that makes it 

unusable or substantially impairs its utility at the time it is turned over to the end user. 

The warranty does not apply to natural wear, improper usage, incorrect connection, 

device tampering or the effects of external influences. The warranty period is 24 months 

from the date of purchase by the end user from a dealer and ends not later than 36 

months after the device’s date of manufacture. German law shall be applicable for the 

settlement of warranty claims.

DISPoSaL oF The DevIce

Do not dispose of old devices in the household waste! The device must be 

disposed of in compliance with the laws and standards of the country in which it 

is operated! The device contains electrical components that must be disposed 

of as electronics waste. The enclosure is made from recyclable plastic.

DeScrIPTIon

The 940/16 AM output module serves to switch Ohm-resistive and inductive loads. 

The 6 relay outputs 

(o0-o5)

 of the output module are potential-free and galvanically 

separated from each other. 

The module features 6 phase connections 

(

I

0 u. 

I

5)

. The phase connections supply 

the relay outputs with the applied power supply (230V~/50Hz).

connecTIon DIagram

N

N

L L

N

L L

L L

N

N

L L

N

L L

L L

1 1 O1 O1

I I

2 2 O2 O2

I I

0 0 O0 O0

I I

16 A

16 A

16 A

16 A

16 A

16 A

5 O5 O5

5

4 4 O4 O4

I I

3 3 O3 O3

I I

I I

1

DIP

ON

2 3 4 5

940/16 AM

16A/250V AC 

μ 

(I

N

max 6x16A , I

N          

max 6x4,5A)

M

PHC System

coding switch 

module address

mounTIng

The installation of the PHC modules may be carried out by authorised technicians only. 

During installation the system‘s electricity has to be switched off. The PHC module is 

designed for mounting on a 35mm top hat rail acc. EN 50022 in  in-/on-wall distribution 

housing. The devices can be mounted directly next to each other.

This device is only intended to be used for its stated application. Unauthorised 

conversions, modifications or changes are not permissible! 

This device may not be used in conjunction with other devices whose operation could 

present a hazard to people, animals or property.

The following points must be observed:

-  the valid laws, standards and regulations

-  the technical state of the art during installation

-  the PHC manual and the operating instructions of the PHC modules.

-  the fact that operating instructions can only cover general regulations and that

  these regulations must be considered in the context of the PHC system. 

The following systems may not be switched by Phc modules:

-  safety switches such as EMERGENCY OFF

-  emergency power supplies

-  fire alarm systems

-  emergency lighting systems

DaTa connecTIon

The connection between PHC control unit and other PHC modules is established by the 

PHC bus line and the modular connectors of the modules. The module connectors are 

switched parallel in the modules (except in the PHC power supply unit) and therefore 

freely selectable as in- or output. Thus the PHC module can be positioned anywhere 

in the data line. A PHC bus line of 30 cm length is included with every PHC module. 

It is needed for connecting a neighbouring module or for connecting a module in the 

next distributor row. The modules are supplied with voltage by the bus line. Power 

needs to be switched off before disconnecting the bus line.

coDIng SwITch

The output module‘s address is set by the coding switch built into the PHC control 

module. The setting of the coding switch is presented in the PHC software under the 

menu item „

Components 

g

 Edit Modules

“.

Make sure that no identical module addresses are given for PHC output modules. 

The setting of the coding switch may be carried out by technicians only. For this the 

PHC module needs to be switched off and it must be ensured that there can be no 

electrical discharge.

Power supply 

Phc system (Phc bus)

Nom. 24 V DC

21-28 V  DC (ripple voltage 5 %)

own consumption

10-60 mA

In-/output module bus

2 modular sockets 6-pin (PHC bus)

Phase connections

(Terminal 

I

0 u. 

I

7)

Connection for the power supply (230V~/50Hz) 

for the corresponding relay outputs

relay outputs 

(Terminal o0-o7)

6 outputs (O0-O5) for loads up to 16 A 

(230V~/50Hz) 

with 2 terminal clamps each and max. switch-on 

current of 120 A (20 ms)

Life-time cycle of relays

> 22,500 switchings with max. load

coding

DIP switch, 5-pin (Module address)

ambient temperature

+10° to +50°C

Storage temperature

-20° to +60°C

Screw terminals

max. 2 x 1,5  mm²

Test specifications

EN 60669-2-1

approbationen

CE   KEMA/KEUR   CEBEC

Protection level

IP 20

Dimensions

width  =  108 mm

height  =  55 mm

Type of load connected

max. output load per 16 a output

Incandescent lamp

2500 W

Resistive load

3500 W

Fluorescent lamps uncompensated 18 x 58 W
Motor load

4,5 A

InSTaLLaTIon anD oPeraTIng InSTrucTIonS
Phc output modul 940/16 am 

6 relay outputs (6x 16a)

940/16am

gb