PEHA_M_940_16_AM (Rev06_130213)
GB - 1
126056-05
PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: [email protected] • Internet: www.peha.de
SwITchIng conDITIonS For voLTage SwITch-on
You can select the switching states OFF, Memory and ON of the relay‘s from the PHC
output modules on voltage switch-on or recovery in the PHC software under the menu
item “
Components
g
Switch-on Conditions
”. The switching conditions are pre-set to
“OFF” by the system. The “Memory” switching condition is selected if, for example,
after voltage has been recovered following an interruption of > 50 ms, you want the
output module to retain its previous switching state from the controller.
currenT conSumPTIon
To calculate the current consumption for the power supply, you should assume a
consumption of 60 mA (internal consumption 10 mA, per relay 7 mA). When a relay
is switched on the current increases to 150 mA for about 2 seconds.
TechnIcaL DaTa
PermITTeD LoaDS For The reLay ouTPuTS
warranTy conDITIonS
These operating instructions are an integral part of both the device and our terms of
warranty. They must be handed over to the user. The technical design of the appliance
is subject to change without prior notification.
PEHA
products are manufactured
and quality-checked with the latest technology according to applicable national and
international regulations. Nevertheless, if a product should exhibit a defect,
PEHA
warrants to make remedy as follows (regardless of any claims against the dealer to
which the end user may be entitled as a result of the sales transaction):
In the event of a justified and properly established claim,
PEHA
shall exercise its
prerogative to either repair or replace the defective device. Further claims or liability
for consequential damage are explicitly excluded. A justifiable deficiency is deemed to
exist if the device exhibits a structural, manufacturing, or material defect that makes it
unusable or substantially impairs its utility at the time it is turned over to the end user.
The warranty does not apply to natural wear, improper usage, incorrect connection,
device tampering or the effects of external influences. The warranty period is 24 months
from the date of purchase by the end user from a dealer and ends not later than 36
months after the device’s date of manufacture. German law shall be applicable for the
settlement of warranty claims.
DISPoSaL oF The DevIce
Do not dispose of old devices in the household waste! The device must be
disposed of in compliance with the laws and standards of the country in which it
is operated! The device contains electrical components that must be disposed
of as electronics waste. The enclosure is made from recyclable plastic.
DeScrIPTIon
The 940/16 AM output module serves to switch Ohm-resistive and inductive loads.
The 6 relay outputs
(o0-o5)
of the output module are potential-free and galvanically
separated from each other.
The module features 6 phase connections
(
I
0 u.
I
5)
. The phase connections supply
the relay outputs with the applied power supply (230V~/50Hz).
connecTIon DIagram
N
N
L L
N
L L
L L
N
N
L L
N
L L
L L
1 1 O1 O1
I I
2 2 O2 O2
I I
0 0 O0 O0
I I
16 A
16 A
16 A
16 A
16 A
16 A
5 O5 O5
5
4 4 O4 O4
I I
3 3 O3 O3
I I
I I
1
DIP
ON
2 3 4 5
940/16 AM
16A/250V AC
μ
(I
N
max 6x16A , I
N
max 6x4,5A)
M
PHC System
coding switch
module address
mounTIng
The installation of the PHC modules may be carried out by authorised technicians only.
During installation the system‘s electricity has to be switched off. The PHC module is
designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-wall distribution
housing. The devices can be mounted directly next to each other.
This device is only intended to be used for its stated application. Unauthorised
conversions, modifications or changes are not permissible!
This device may not be used in conjunction with other devices whose operation could
present a hazard to people, animals or property.
The following points must be observed:
- the valid laws, standards and regulations
- the technical state of the art during installation
- the PHC manual and the operating instructions of the PHC modules.
- the fact that operating instructions can only cover general regulations and that
these regulations must be considered in the context of the PHC system.
The following systems may not be switched by Phc modules:
- safety switches such as EMERGENCY OFF
- emergency power supplies
- fire alarm systems
- emergency lighting systems
DaTa connecTIon
The connection between PHC control unit and other PHC modules is established by the
PHC bus line and the modular connectors of the modules. The module connectors are
switched parallel in the modules (except in the PHC power supply unit) and therefore
freely selectable as in- or output. Thus the PHC module can be positioned anywhere
in the data line. A PHC bus line of 30 cm length is included with every PHC module.
It is needed for connecting a neighbouring module or for connecting a module in the
next distributor row. The modules are supplied with voltage by the bus line. Power
needs to be switched off before disconnecting the bus line.
coDIng SwITch
The output module‘s address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „
Components
g
Edit Modules
“.
Make sure that no identical module addresses are given for PHC output modules.
The setting of the coding switch may be carried out by technicians only. For this the
PHC module needs to be switched off and it must be ensured that there can be no
electrical discharge.
Power supply
Phc system (Phc bus)
Nom. 24 V DC
21-28 V DC (ripple voltage 5 %)
own consumption
10-60 mA
In-/output module bus
2 modular sockets 6-pin (PHC bus)
Phase connections
(Terminal
I
0 u.
I
7)
Connection for the power supply (230V~/50Hz)
for the corresponding relay outputs
relay outputs
(Terminal o0-o7)
6 outputs (O0-O5) for loads up to 16 A
(230V~/50Hz)
with 2 terminal clamps each and max. switch-on
current of 120 A (20 ms)
Life-time cycle of relays
> 22,500 switchings with max. load
coding
DIP switch, 5-pin (Module address)
ambient temperature
+10° to +50°C
Storage temperature
-20° to +60°C
Screw terminals
max. 2 x 1,5 mm²
Test specifications
EN 60669-2-1
approbationen
CE KEMA/KEUR CEBEC
Protection level
IP 20
Dimensions
width = 108 mm
height = 55 mm
Type of load connected
max. output load per 16 a output
Incandescent lamp
2500 W
Resistive load
3500 W
Fluorescent lamps uncompensated 18 x 58 W
Motor load
4,5 A
InSTaLLaTIon anD oPeraTIng InSTrucTIonS
Phc output modul 940/16 am
6 relay outputs (6x 16a)
940/16am
gb