DATA connecTIon

The connection between PHC control unit and other PHC modules is established by the 

PHC bus line and the modular connectors of the modules. The module connectors are 

switched parallel in the modules (except in the PHC power supply unit) and therefore 

freely selectable as in- or output. Thus the PHC module can be positioned anywhere 

in the data line. A PHC bus line of 30 cm length is included with every PHC module. 

It is needed for connecting a neighbouring module or for connecting a module in the 

next distributor row. The modules are supplied with voltage by the bus line. Power 

needs to be switched off before disconnecting the bus line.

coDIng swITch

The output module‘s address is set by the coding switch built into the PHC control 

module. The setting of the coding switch is presented in the PHC software under the 

menu item „

Components 

g

 Edit Modules

“.

Make sure that no identical module addresses are given for PHC output modules. 

The setting of the coding switch may be carried out by technicians only. For this the 

PHC module needs to be switched off and it must be ensured that there can be no 

electrical discharge.

currenT consumPTIon

To calculate the current consumption for the power supply, you should assume a 

consumption of 10 mA.

TechnIcAL DATA

Power supply

230 V~ ±10 % 50 Hz

own consumption (230 v)

approx. 10 mA 

own consumption 

(Phc-system)

10 mA

In-/output module bus

2 modular sockets 6-pin (PHC bus)

button inputs 

(stand-alone mode)

6  inputs (

I

0-

I

5)  with 230V~ (1 mA)

Analogue input

(no seLv)

UAE = 0 to 10 VDC

UB   = 12 VDC

Analogue output 

(no seLv)

Active 1 to 10VDC (10mA) or 

current sink 1 to 10VDC (50 mA)

(automatic depending on connected device)

switch output (relay)

Switch current max.10 A (max. 5 ECGs) 

breaking capacity of the

switch output (relay)

Due to a combination of relay and triac,

switch-on pulses  > 150 A  for about 1 ms

are possible (switching on in zero crossing).

coding

DIP switch, 5-pin

Ambient temperature

+20°C to +50 °C

storage temperature

-20°C to +60 °C

connections

2  screw terminals for power supply 

(N, L)

2  screw terminals for switch output 

(3, 4)

3  screw terminals for analogue output  (0, 1, 2)

3  screw terminals for analogue input  (5, 6,7)

6  screw terminals for  button 

(

I

0-

I

5)

screw terminals

max. 2 x 1,5  mm²

Test specifications

EN 60669-2-1

certifications

KEMA KEUR , CE , CEBEC

Protection level

IP 20

Dimensions

Width  =  108 mm

Height  =  55 mm

DescrIPTIon

The PHC analogue module has an switch output (10 A) with a no-voltage releasing 

magnet to switch up to 5 electronic ballasts. The module requires its own power supply 

of 230V~/50Hz. The analogue output 1-10 V can be used either as a voltage output 

or as a current sink for electronic ballasts (ECGs). The analogue input 0-10 V can be 

used for the light sensor 940 LS.

A stand-alone mode without PHC system is possible. In this case the operation is by 

buttons that are connected to the 230 V inputs 

(

I

0-

I

5)

These inputs cannot be programmed in the PHC software.

connecTIon DIAgrAm

1-10V

0V

0V

UB

L

N

L

N

L

1

DIP

ON

2 3 4 5

Art. Nr.: 940AMA

1 Relaisausgang I max. 10A

1 Analogausgang 1-10V
1 Analogeingang 1-10V
6 Eingänge 1mA/230V~

N

Analogmodul

0

3

4

L

N

1

2

10 A

1-10V

230 V

0V

6 x Input 1 mA / 230 V

0V 0-10V +12V

5

7

0

1

2

3

4

5

6

I

I

I

I

I

I

CEBEC

29

940 AMA

6 Inputs 1mA/230V AC

1 Analogue Input/Output 1-10V

1 Output 10A/230V AC (I

N

max 10A)

PHC System

coding switch 

230 v inputs for the 

stand-alone mode

Analogue output 1-10v

for ECGs

switch output 10A

for ECGs

Power supply

230v~/50hz (L,n)

Art. no. 940 AK Ls

4 3 2 1

Light sensor 

940 Ls

Analogue input 1-10v

for light sensor 940 Ls

0v

1-10

v

ub

 = 12

v

–  +

0V 1-10V

L N

L N

L

mounTIng

The installation of the PHC modules may be carried out by authorised technicians only. 

During installation the system‘s electricity has to be switched off. The PHC module is 

designed for mounting on a 35mm top hat rail acc. EN 50022 in  in-/on-wall distribution 

housing. The devices can be mounted directly next to each other. The PHC modules 

may not be employed in connection with devices that may endanger people, animals 

or property when operated.

The following points must be observed:

-  the valid laws, standards and regulations

-  the technical state of the art during installation

-  the PHC manual and the operating instructions of the PHC modules.

-  Operating instructions can only cite general stipulations. 

  These are to be viewed in the context of a specific system.

The following systems may not be switched by Phc output modules:

-  safety switches such as EMERGENCY OFF

-  emergency power supplies

-  fire alarm systems

-  emergency lighting systems

InsTALLATIon AnD oPerATIng InsTrucTIons
Phc Analogue module 940 AmA

Analogue module for switching and controlling dimmable ecgs

940 AmA

gb

Содержание PEHA 940 AMA

Страница 1: ...alogausgang 0 1 2 3 Schraubklemmen für Analogeingang 5 6 7 6 Schraubklemmen für Taster I0 I5 Schraubklemmen max 2 x 1 5 mm Prüfvorschriften EN 60669 2 1 Approbationen KEMA KEUR CE CEBEC Schutzart IP 20 Abmessungen Breite 108 mm 6TE Höhe 55 mm Beschreibung Das PHC Analogmodul hat einen Schaltausgang 10A mit Nullspannungsschalter zum Ein Ausschalten von maximal 5 EVGs Es benötigt eine eigene Stromve...

Страница 2: ...des Gerätes und der Garantiebedingungen Sie ist dem Benutzer zu überreichen Die technische Bauart der Geräte kann sich ohne vorherige Ankündigung ändern PEHA Produkte sind mit modernsten Technologien nach geltenden nationalen und internationalen Vorschriften hergestellt und qualitätsgeprüft Sollte sich dennoch ein Mangel zeigen übernimmt PEHA unbeschadet der Ansprüche des Endverbrauchers aus dem K...

Страница 3: ...ue input 5 6 7 6 screw terminals for button I0 I5 Screw terminals max 2 x 1 5 mm Test specifications EN 60669 2 1 Certifications KEMA KEUR CE CEBEC Protection level IP 20 Dimensions Width 108 mm Height 55 mm Description The PHC analogue module has an switch output 10 A with a no voltage releasing magnet to switch up to 5 electronic ballasts The module requires its own power supply of 230V 50Hz The...

Страница 4: ...l part of both the device and our terms of warranty They must be handed over to the user The technical design of the appliance is subject to change without prior notification PEHA products are manufactured and quality checked with the latest technology according to applicable national and international regulations Nevertheless if a product should exhibit a defect PEHA warrants to make remedy as fo...

Отзывы: