GB - 1
PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: [email protected] • Internet: www.peha.de
PEHA_M_940_AMA (Rev05_130219)
126005-04
DATA connecTIon
The connection between PHC control unit and other PHC modules is established by the
PHC bus line and the modular connectors of the modules. The module connectors are
switched parallel in the modules (except in the PHC power supply unit) and therefore
freely selectable as in- or output. Thus the PHC module can be positioned anywhere
in the data line. A PHC bus line of 30 cm length is included with every PHC module.
It is needed for connecting a neighbouring module or for connecting a module in the
next distributor row. The modules are supplied with voltage by the bus line. Power
needs to be switched off before disconnecting the bus line.
coDIng swITch
The output module‘s address is set by the coding switch built into the PHC control
module. The setting of the coding switch is presented in the PHC software under the
menu item „
Components
g
Edit Modules
“.
Make sure that no identical module addresses are given for PHC output modules.
The setting of the coding switch may be carried out by technicians only. For this the
PHC module needs to be switched off and it must be ensured that there can be no
electrical discharge.
currenT consumPTIon
To calculate the current consumption for the power supply, you should assume a
consumption of 10 mA.
TechnIcAL DATA
Power supply
230 V~ ±10 % 50 Hz
own consumption (230 v)
approx. 10 mA
own consumption
(Phc-system)
10 mA
In-/output module bus
2 modular sockets 6-pin (PHC bus)
button inputs
(stand-alone mode)
6 inputs (
I
0-
I
5) with 230V~ (1 mA)
Analogue input
(no seLv)
UAE = 0 to 10 VDC
UB = 12 VDC
Analogue output
(no seLv)
Active 1 to 10VDC (10mA) or
current sink 1 to 10VDC (50 mA)
(automatic depending on connected device)
switch output (relay)
Switch current max.10 A (max. 5 ECGs)
breaking capacity of the
switch output (relay)
Due to a combination of relay and triac,
switch-on pulses > 150 A for about 1 ms
are possible (switching on in zero crossing).
coding
DIP switch, 5-pin
Ambient temperature
+20°C to +50 °C
storage temperature
-20°C to +60 °C
connections
2 screw terminals for power supply
(N, L)
2 screw terminals for switch output
(3, 4)
3 screw terminals for analogue output (0, 1, 2)
3 screw terminals for analogue input (5, 6,7)
6 screw terminals for button
(
I
0-
I
5)
screw terminals
max. 2 x 1,5 mm²
Test specifications
EN 60669-2-1
certifications
KEMA KEUR , CE , CEBEC
Protection level
IP 20
Dimensions
Width = 108 mm
Height = 55 mm
DescrIPTIon
The PHC analogue module has an switch output (10 A) with a no-voltage releasing
magnet to switch up to 5 electronic ballasts. The module requires its own power supply
of 230V~/50Hz. The analogue output 1-10 V can be used either as a voltage output
or as a current sink for electronic ballasts (ECGs). The analogue input 0-10 V can be
used for the light sensor 940 LS.
A stand-alone mode without PHC system is possible. In this case the operation is by
buttons that are connected to the 230 V inputs
(
I
0-
I
5)
.
These inputs cannot be programmed in the PHC software.
connecTIon DIAgrAm
1-10V
0V
0V
UB
L
N
L
N
L
1
DIP
ON
2 3 4 5
Art. Nr.: 940AMA
1 Relaisausgang I max. 10A
1 Analogausgang 1-10V
1 Analogeingang 1-10V
6 Eingänge 1mA/230V~
N
Analogmodul
0
3
4
L
N
1
2
10 A
1-10V
230 V
0V
6 x Input 1 mA / 230 V
0V 0-10V +12V
5
7
0
1
2
3
4
5
6
I
I
I
I
I
I
CEBEC
29
940 AMA
6 Inputs 1mA/230V AC
1 Analogue Input/Output 1-10V
1 Output 10A/230V AC (I
N
max 10A)
PHC System
coding switch
230 v inputs for the
stand-alone mode
Analogue output 1-10v
for ECGs
switch output 10A
for ECGs
Power supply
230v~/50hz (L,n)
Art. no. 940 AK Ls
4 3 2 1
Light sensor
940 Ls
Analogue input 1-10v
for light sensor 940 Ls
0v
1-10
v
ub
= 12
v
– +
0V 1-10V
L N
L N
L
mounTIng
The installation of the PHC modules may be carried out by authorised technicians only.
During installation the system‘s electricity has to be switched off. The PHC module is
designed for mounting on a 35mm top hat rail acc. EN 50022 in in-/on-wall distribution
housing. The devices can be mounted directly next to each other. The PHC modules
may not be employed in connection with devices that may endanger people, animals
or property when operated.
The following points must be observed:
- the valid laws, standards and regulations
- the technical state of the art during installation
- the PHC manual and the operating instructions of the PHC modules.
- Operating instructions can only cite general stipulations.
These are to be viewed in the context of a specific system.
The following systems may not be switched by Phc output modules:
- safety switches such as EMERGENCY OFF
- emergency power supplies
- fire alarm systems
- emergency lighting systems
InsTALLATIon AnD oPerATIng InsTrucTIons
Phc Analogue module 940 AmA
Analogue module for switching and controlling dimmable ecgs
940 AmA
gb