51268E-01
Note:
In case of battery replacement, this must be replaced with parts of the same type and characteristics.
The replacement must be performed by the manufacturer or a competent person.
Note:
The light source is non-replaceable.
Note:
If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person
in order to avoid hazard.
Battery replacement:
Disconnect mains, carefully pull the luminaire and main unit down, make
sure that the springs do not snap. Unscrew the battery cover (step 3,
screw
A
). Disconnect the battery and install a new one of the same type
and characteristics. Refit the cover and fasten the screw.
The
Ova/OmniLED R Spot
is a self-contained non-maintained luminaire with selftest function.
Selftest functions
Every 15 days the luminaire will perform an emergency operation test, this will light the white LED for
approx. 3 seconds. The red LED will flash during this test sequence.
Every 6. month the luminaire will perform a battery condition test. The test will last for 60 minutes. The
white LED will be lit and the yellow LED will flash during this test sequence.
Note:
When using DALI or Wireless communication, the frequencies and schedules for tests will
instead be determined by the connected PC software.
Manual test functions
Manual tests can only be performed if both mains and battery are connected.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed.
The white LED will be lit for approx. 3 seconds, the red LED will flash during this test sequence.
By pressing the test button for between 5 and 10 seconds a battery condition test is performed.
This test will last for 60 minutes and can only be performed when the battery is fully charged (steady
green LED). The white LED will be lit and the yellow LED will flash during this test sequence.
Resetting errors
Push the test button for >10 seconds to delete all indicated errors. Then the luminaire enters regular
operation mode.
In case that the luminaire no longer meets its rated duration of operation, the battery must be replaced
(see chapter “Battery replacement” on top of this page).
Part number:
290071.10
Lumen output:
350 lm
Operation voltage:
220-240VAC 50/60Hz
Emergency mode duration:
Minimum 1 hour
Battery:
6,4V / 1,2Ah LiFePO4
Battery protection:
Overcharge and full discharge
Charging time:
18 hours
Maximum power consumption:
3,8W / 4,3VA
Ambient temperature range:
5 to 40°C
Relative humidity:
Up to 95%
Weight:
440 g
Classification:
EN 60598-2-22
Technical lifetime (light source):
> 100000 hours
IP20
Expected battery lifetime 10 years
Technical description
GB
Indicator LEDs
G
R
EE
N
YE
LL
O
W
R
ED
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
Description
LED status explanation
Off
On
Flashing
Important notice when installing
luminaires within the same area!!!
To avoid that luminaires perform their
battery test at the same day, connect
the battery packs with more than 1,5
minutes inbetween.
At the end of their useful life the
packaging, product and batteries
should be disposed of via a
suitable recycling centre. Do not
dispose of with your normal
household waste. Do not burn.