Installation Instructions / OmniAssure Touch Square
3
3.6
Test the reader / Commissioning
Apply power (the green LED indicates power) and present a valid creden-
tial. The light ring should flash and the sounder should produce a short
tone indicating a successful read. If the Host system is connected the light
ring and sounder should follow the functionality of the Host system.
3.7
Cable specification
– The reader is supplied with 2 m (6 ft.) of shielded, 8-conductor
0,14 mm² (AWG 26) cable which may be extended with the length
and size of cable listed below.
min. conductor size
for panel power suppy
max. cable
length
9,5 V
1)
12 V
18 V
Interface
meters
feet
mm² AWG mm² AWG mm² AWG
61
200
0,55 20 0,33 22 0,22 24
91
300
0,82 18
0,5
20 0,33 22
Wiegand /
RS-485
(cable
power)
152
500
1,35 16 0,81 18 0,54 20
RS-485
(local power) 1220
4000
0,16 mm² / AWG 25
1)
to ensure that the reader power supply is at least 7 V DC
3.8
Wire assignments
The connection must be carried out in de-energized state! Risk of
damage!
To ensure reliable functioning, ensure that a possible extension of the 4 m
connecting cable does not exceed 152 m (condition: no external voltage
supply unit is required). For extension purposes up to 152 m an additional
JY(ST)Y (6x2x0.6 mm) cable can be used.
The reader can be used remotely for extension purposes at a distance of
max. 1220 m. We recommend using a Cat 5 connecting cable (condition:
an external voltage supply unit for the reader is required).
In general, by use of RS-485 interface:
When the reader is the last user
on the RS-485 bus, a 120 Ω end-of-line resistor (from TRX+ to TRX-)
must be installed in front of the reader. For further information, refer to the
description of the corresponding controller.
Interface
Wire color
Wiegand
RS-485
red
POWER (+U_b)
POWER (+U_b)
black
GND (0 V)
GND (0 V)
white
D1
TRX+
green
D0
TRX-
blue
Hold line
do not connect
yellow
Buzzer
do not connect
orange
LED green
do not connect
purple
Tamper
do not connect
Caution
Floating communication lines may cause spurious emissions, invalidating
certification. Ensure all communication lines are properly biased and ter-
minated.
Input Hold line
This input makes it pos-
sible to switch 2 read-
ers in parallel (e.g. at
NetAXS).
Reader 1
Reader 2
Hold line 2
Hold line 1
NetAXS
GND
Tamper line
Physical tamper switches:
– tear-off
– enclosure
The electronic switch opens when
the operating vU_b fails.
mechanical tamper switch
electronic tamper switch
Tamper line
4
Operation
When a credential is read successfully, the light ring lights briefly, the
sounder sounds a short tone and the credential associated code is sent
to the Host system.
The light ring and sounder are also controllable by the Host system.
Reader output formats are determined by the personalization of the cre-
dential and/or configuration of the reader; on SmartTech and MultiTech
readers the behaviour of the light ring and sounder can be modified
through configuration.
4.1
Short briefing of buttons and LEDs
OmniAssure Touch Square 16 key
A
B
I
E
C
F
D
G
H
K
J
A
Numeric keypad for PIN entry
(PIN= Personal identification number)
B
LED light ring
C, E, G, I
Not used
D
LED green
F
LED yellow
H
Duo LED red/green
J
Acknowledge: execute the PIN code / Activate
the BLE credential
K
Clear PIN code entry