NOTE: Power must not be applied to the unit when changing functionality of 
the shunts.
NOTE: Whether in Class B or Class A wiring, power supply monitoring and 
short circuit protection must be enabled on the NAC circuits that are sharing 
a power supply.
NOTE: Short circuit protection can only be disabled if a power supply is not 
being shared by multiple NACs.

WIRING NOTES

•  Power-limited circuits must employ type FPL, FPLR, or FPLP cable as 

required by Article 760 of the NEC.

•   For easier wiring, assign all power-limited wiring to one side of the en-

closure rather than alternating with non power-limited.

PROGRAMMING

The XP6-C module operates with the following Fire Alarm Control Panels:

•  AM2020/AFP1010

•  AFP-200

•  AFP-300/AFP-400

•  System 5000 with AIM-200

•  AFC-600

•  NFS-640 

•  NFS-3030

The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.  

FIGURE 8:

ENABLE POWER SUPPLY MONITOR

DISABLE SHORT CIRCUIT PROTECTION

SYNC GENERATOR

A/B SELECT

DISABLE 1

DISABLE 2

DISABLE 3

J1 SHUNT

TOP VIEW:

SIDE VIEW:

NOTIFICATION APPLIANCE/ 

POWER SUPPLY TERMINAL

SLC WIRING 

TERMINAL

C0174-00

NOTE: SLC wiring is the top terminal block, notification appliance/power
supply is the bottom.

NAC WIRING AND SUPERVISION

For Class B, Style Y applications (figures 9, 10, and 13 are typical): connect the 
positive terminal of the notification appliance(s) to the NAC+ terminal and 
the negative device terminal to the adjacent NAC- terminal. Connect one (for 
each NAC) of the supplied EOL resistors across the NAC+ and NAC- wires, at 
the ends farthest away from the NAC terminal of the XP6-C. 

For Class A, Style Z applications (figures 11, 12, and 14 are typical) wire the 
NACs per table 2. 

The A/B select shunt must be removed prior to connect-

ing the XP6-C to the SLC

. The EOL resistors should not be used. The XP6-C 

is capable of supporting 3 Class A, Style Z NACs. The XP6-C will only respond 
at the base address, base a2, and base a4 (assuming no ad-
dresses have been disabled). 

TABLE 2

NAC# 

(+) CONNECTIONS 

(–) CONNECTIONS

+0 

+0 NAC+, +1 NAC+, 

+0 NAC–, +1 NAC–

 

NOTIFICATION AP 

NOTIFICATION APPLIANCE–

+2 

+2 NAC+, +3 NAC+, 

+2 NAC–, +3 NAC–,

 

NOTIFICATION AP 

NOTIFICATION APPLIANCE–

+4 

+4 NAC+, +5 NAC+, 

+4 NAC–, +5 NAC–

 

NOTIFICATION AP 

NOTIFICATION APPLIANCE–

N500-79-00  4 I56-1805-019

POWER SUPPLY WIRING AND SUPERVISION

Table 3 gives an overview of how the power connectors, T0–T5 and T10–T15, 
are interconnected by the circuit board (PCB). The external supply connection 
points, at T0–T5, are marked by PS– and PS+ on the PCB legend. Pin 1 is 
indicated by a dot next to T10–T16. The odd pins, on T10–T16, always con-
nect to PS– pins (e.g. PS–, of the +0 NAC, is connected to T10–1 and T11–1). 
The even pins always connect to PS+ pins (e.g. PS+, of the +5 NAC, is con-
nected to T15-4 and T16-2). 

TABLE 3

 PS OR NAC NUMBER (TERMINAL / PINS) 

TERMINAL / PINS

 

+0 (T0 – BOTTOM / PS- & PS+)* 

T10 / 1 & 2,   T11 / 1 & 2

 

+1 (T1 / PS- & PS+) 

T11 / 3 & 4,   T12 / 1 & 2

 

+2 (T2 / PS- & PS+) 

T12 / 3 & 4,   T13 / 1 & 2

 

+3 (T3 / PS- & PS+) 

T13 / 3 & 4,   T14 / 1 & 2

 

+4 (T4 / PS- & PS+) 

T14 / 3 & 4,   T15 / 1 & 2

 

+5 (T5 / PS- & PS+) 

T15 / 3 & 4,   T16 / 1 & 2  

*Note: T0–TOP is reserved for SLC connections only (see Figure 8). 
All power supplies, external to the cabinet (in which the XP6-C is housed), 
should be connected to T0–T5 which are suitable connectors for field wiring. 
The 1 x 4 terminal blocks, shown on page 1, should be used to make these 
connections.

All NACs can be wired to be powered by separate external supplies (figures 
9 and 11 are typical), or a single supply (figures 10 and 12 are typical) can be 
shared among multiple NACs. If a supply is to be shared, between NACs wired 
to a common PCB, use the short power supply jumpers shown on page 1. The 
jumpers can be used on T11–T15. Refer to Table 4 for jumper functions. When 
multiple (2 or more) NAC circuits share a power supply, the wiring for the 
power supply must be in conduit and 20 feet or less from the XP6-C board.

TABLE 4

 

JUMPER LOCATION 

NAC PAIR SHARING SUPPLY

 

T11* 

+0 and +1

 

T12 

+1 and +2

 

T13* 

+2 and +3

 

T14 

+3 and +4

 

T15* 

+4 and +5  

*NOTE:

 Jumpers must be placed on T11, T13 and T15 for all Class A, Style Z 

applications.
A supply can be wired to be shared among multiple PCBs in the same cabinet 
(figure 15 is typical). To share among multiple PCBs: use the long power sup-
ply jumpers (shown on page 1) to connect either T10 or T16, of one PCB, to 
either T10 or T16 of  the other PCB..

An EOL relay must be used for every external power supply (figures 9–12 are 
typical). The EOL relay coil should always be connected at the external power 
supply input of  the module which is connected to the ends of the wires which 
are farthest from the power supply. The EOL relay contacts should always be 
connected in series with the NAC wiring of the same module. The EOL relay 
coil should be connected across the PS+ (red wire) and PS- (black wire) if 
it is connected at T0 – T5. The EOL relay coil should be connected across 
adjacent pins (red – even pin#, black – odd pin#), of the same connector, if 
T10 – T16 are used. If the supply is an audio amplifier then the points, where 
the EOL relay coil would normally be connected, should be connected to the 
amplifier supervision EOL device (figures 13 and 14 are typical).

All wiring must be in accordance with the NEC, NFPA 72 and all other ap-
plicable codes and standards. All external power supplies must be voltage 
regulated with battery back-up. All external power supplies, audio amplifiers, 
EOL relays, and notification appliances must be UL listed for fire protection 
signaling applications. 

NOTE: All references to power limited represent “Power Limited (Class 2)”.

Содержание Notifier XP6-C

Страница 1: ...ED PARTIES This product incorporates field programmable software In order for the product to comply with requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below PROGRAM FEATURE OR OPTION PERMITTED IN UL 864 Y N POSSIBLE SETTINGS SETTINGS PERMITTED IN...

Страница 2: ...n the rear position of a chassis Method one is for installation of a rear module only when no module will be installed in front of it Refer to Figure 5 for instructions Method two is for installation of a rear module when another module will be installed in the chassis position in front of it Refer to Figures 6a and 6b for method two All necessary screws and standoffs are supplied with the modules...

Страница 3: ...l be addressed to 29 30 31 32 and 33 To select Class A operation remove the J1 Shunt A maximum of three Class A circuits are available For example if the base address switch is set to 28 30 and 32 will be automatically assigned to the modules while 29 31 and 33 are available to be used for other modules on the SLC For Class A and B opera tion DO NOT set the lowest address above 154 as the other mo...

Страница 4: ... g PS of the 0 NAC is connected to T10 1 and T11 1 The even pins always connect to PS pins e g PS of the 5 NAC is con nected to T15 4 and T16 2 TABLE 3 PS OR NAC NUMBER TERMINAL PINS TERMINAL PINS 0 T0 BOTTOM PS PS T10 1 2 T11 1 2 1 T1 PS PS T11 3 4 T12 1 2 2 T2 PS PS T12 3 4 T13 1 2 3 T3 PS PS T13 3 4 T14 1 2 4 T4 PS PS T14 3 4 T15 1 2 5 T5 PS PS T15 3 4 T16 1 2 Note T0 TOP is reserved for SLC co...

Страница 5: ... EOLR 1 RED VIO VIO RED BLK BLK 47K NOTE EOL RELAY COIL CONNECTIONS MUST BE MADE USING EOL RELAY CONNECTOR ASSEMBLIES ON T10 T16 IN EVENT THAT ALL NACS ON THE PCB HAVE DEDICATED SUPPLIES C0816 04 FIGURE 10 EXAMPLE OF CLASS B STYLE Y NAC CONFIGURATION WITH A SINGLE SUPPLY SHARED BY 2 NACS BASE ADDRESS STATUS INDICATORS NAC PS NAC PS NAC PS NAC PS NAC TOP BOT NAC PS SLC PS 1 2 3 4 5 T11 T10 T0 0 T12...

Страница 6: ...UCTION MANUAL FOR WIRE REQUIREMENTS POWER LIMITED AND SUPERVISED TOP OF T0 EOLR 1 TYP RED VIO VIO RED BLK BLK C0818 02 FIGURE 12 EXAMPLE OF CLASS A STYLE Z NAC CONFIGURATION WITH A SINGLE SUPPLY SHARED BY 2 NACS BASE ADDRESS STATUS INDICATORS NAC PS NAC PS NAC PS NAC PS NAC TOP BOT NAC PS SLC PS 1 2 3 4 5 T11 T10 T0 0 T12 T1 T2 T3 T4 T5 T13 T14 T15 T16 ENABLE POWER SUPPLY MONITOR DISABLE SHORT CIR...

Страница 7: ...MITED AND SUPERVISED TOP OF T0 SLC SLC SLC SLC 47K C0179 06 FIGURE 14 EXAMPLE OF CLASS A STYLE Z AUDIO NAC CONFIGURATION BASE ADDRESS STATUS INDICATORS NAC PS NAC PS NAC PS NAC PS NAC TOP BOT NAC PS SLC PS 1 2 3 4 5 T11 T10 T0 0 T12 T1 T2 T3 T4 T5 T13 T14 T15 T16 ENABLE POWER SUPPLY MONITOR DISABLE SHORT CIRCUIT PROTECTION A B SELECT DISABLE 1 DISABLE 2 DISABLE 3 0 1 2 3 4 5 6 7 8 9 0 7 8 6 5 4 3 ...

Страница 8: ...e following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Отзывы: