56
SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
Installation
ANN-BUS Audio Panel
N-ANN-RLY Board Layout and Connection to FACP
Figure 2.29 illustrates the N-ANN-RLY board wiring connections to the FACP.
2.9 ANN-BUS Audio Panel
The FACP must be enabled to communicate with the NFV-25/50ZS/T Audio Panel over the ANN-
BUS (refer to “ANN-BUS Enabled” on page 82). This is accomplished by programming the Audio
Panel ANN-BUS address into the FACP (refer to“BUS Modules” on page 82). For details on set-
ting the ANN-BUS address and programming the audio panel, refer to the
NFV-25/50ZS/T Series
Audio Panel manual
(document #52290).
The NFV-25/50ZS/T Series audio panel connects to the FACP via the ANN-BUS communication
circuit. The five input zones on the SFP-5UD correspond to the first five NFV-25/50ZS/T Series
audio zones and the ten input zones on the SFP-10UD correspond to the first ten NFV-25/50ZS/T
Series audio zones. The programmer can select which of the five audio messages at the audio panel
will play when an FACP input zone goes into alarm (refer to“ACC Message” on page 66). The
Figure 2.29 N-ANN-RLY Board Layout and Connection to FACP
FACP
N-ANN-RLY
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS (ID#)
Address DIP switch
TB3
an
n-rl
yt
o5x.
wm
f
!
WARNING: RISK OF ELECTRICAL SHOCK
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY WIRING.
Содержание NOTIFIER SFP-10UD Series
Страница 110: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 110 Notes ...
Страница 128: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 128 Notes ...
Страница 139: ...139 SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 Notes ...
Страница 164: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...