SFP-5UD & SFP-10UD Series Manual—
P/N 52879:C2 1/24/2012
15
Specifications
Product Description
Alarm Silence
System Reset/Lamp Test
Drill
•
LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
•
Piezo sounder for alarm, trouble and supervisory
•
24 volt operation
•
Low AC voltage sense
•
Alarm Verification
•
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•
Automatic battery charger with charger supervision
•
Silent or audible walktest capabilities
•
Optional PS-Tools utilityfor local or remote Upload/Download of program and data
•
Optional N-CAC-5X Class A Converter Module for NACs and IDCs
•
Optional 4XTM Transmitter Module
•
Optional ANN-SEC card for a secondary ANN-BUS
1.2 Specifications
AC Power
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
SFP-5UDC (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
SFP-10UD(C) (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.90 amps
SFP-5UDE (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
Wire size: minimum #14 AWG (2.0 mm
2
) with 600V insulation
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 18 Amp Hour battery for SFP-5UD, and 26 Amp Hour battery for
SFP-5UDC and SFP-10UD(C)/E [two 18 Amp Hour batteries can be housed in FACP cabinet.
Larger batteries require a separate battery box such as the NFS-LBB or BB-26 and the CHG-75 or
CHG-120 Battery Charger.]
Minimum Battery Size: 7 Amp Hour (12 Amp Hour for SFP-5UD-7C & SFP-10UD-7C)
NOTE:
For wiring specifications, refer to“Wire Requirements” on page 153.
Содержание NOTIFIER SFP-10UD Series
Страница 110: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 110 Notes ...
Страница 128: ...SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 128 Notes ...
Страница 139: ...139 SFP 5UD SFP 10UD Series Manual P N 52879 C2 1 24 2012 Notes ...
Страница 164: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...