The SCS⁄SCE
Preliminary SCS-8⁄SCE-8 Design Considerations
3.3.1 Inventory
The SCS-8*
The SCS-8 Smoke Control Station provides the capability to control and display the
status of eight AHU fans and dampers. The SCS-8 is capable of two modes of operation, FSCS
for the control of smoke and HVAC for the control of heating, ventilating and air conditioning.
The SCE-8.
The SCE-8 Smoke Control Expander expands the SCS-8 providing
the capability to control and display an additional eight AHU fans and dampers.
Includes an expander ribbon cable for connection to the SCS-8.
The SCS-8L*
The SCS-8L Smoke Control Station provides the capability to con-
trol and display the status of eight AHU fans and dampers via connection to a custom graphic annuncia-
tor. Graphic annunciators are custom made by a multitude of companies. For information on custom
graphic annunciators, refer to Section 3.7 “SCS-8L⁄SCE-8L Installation”. The SCS-8L is capable of two
modes of operation: FSCS for the control of smoke and HVAC for the control of heating, ventilating and
air conditioning.
The SCE-8L.
The SCE-8L Smoke Control Expander expands the SCS-8L providing the capability to
control and display an additional eight AHU fans and dampers via connection to a custom graphic
annunciator. Includes an expander ribbon cable for connection to the SCS-8L.
The LDM-R32.
The LDM-R32 Relay Expander Module provides the SCS-8L⁄SCE-8L with 32 dry
Form-A (normally open) contacts. The relay module serves as a slave to the particular SCS-8L it is connected to. Instead of driving lamps or
LEDs, the ON, OFF, or TROUBLE signals from the SCS-8L⁄SCE-8L module are used to activate the relays on the LDM-R32.
The SCS-8L-CBL24 and SCS-8L-CBL48
.
Cable sets for connecting SCS-8/8L and SCE-8/8L outputs to lamps or LEDs are
provided through the optional SCS-8L-CBL24 (24" long) and SCS-8L-CBL48 (48" long) assemblies. Each cable has a plug
on one end for connection to the annunciator module and stripped and tinned ends on the other end of the assembly. Each
cable supports eight output pins. The SCS-8L-CBL24 and SCS-8L-CBL48 are cable sets that provide several cables, suffi-
cient for most applications.
3.4 Preliminary SCS-8⁄SCE-8 Design Considerations
A smoke control system must not only be able to control a fan or damper, but it must also be able to verify what state the fan or damper is in
(ON/OFF or OPEN/CLOSED). Following is an explanation of how the SCS-8 controls and monitors a fan or damper in conjunction with the
FACP/INA/Network Control Annunciator.
3.4.1 Related Documentation
To obtain a complete understanding of the potential features of related products, or to become familiar with functions in general, make use of
the documentation listed in Section 1.3 “Supplemental Documentation” at the front of this book.
SCS
8
.w
mf
Expander
Ribbon Cable
SCE-8 75073
SCE-8 75120
SC
Ee
xpa
nde
rr
ib
n
cb
l.wmf
SC
S
-8
L
.w
m
f
cb
l2
4
48.
wm
f
NOTE:
1.
Software Part Numbers 73631 and 73845 are not compatible with INA combinations after M2.7.
2. Part #SCSV2.84 is not compatible with FACP/INA combinations prior to M2.8.
3. NFS-320s, NFS2-640s, NFS-640s, NFS2-3030s, NFS2-3030s, NCAs and NCA-2s are only compatible with software #SCS2.84 or higher.
(They are not compatible with any 73XXX series software versions.)
4. To use the SCS V4.0, NFS2-3030, and/or NCA-2 must be running software V21 or higher.