
N200-501-00
I56-4405-001
0905
21
DOP-IOD074
EN54-17: 2005
EN54-18: 2005
-20°C
60°C
22 mm
Notifier by Honeywell
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The M700 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices. The M701E is
an output module that allows the control of auxiliary devices such as fire shutters or
sounders.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module is
polled. When the control panel switches the relay to the energised state the LED can
be set to continuous green.
SPECIFICATIONS
Operating Voltage Range:
15 to 32VDC (Min 16.5VDC for LED operation)
Maximum Standby Current
160 µA - No Communication
LED Current (Red):
1.5 mA
LED Current (Yellow):
5.5 mA
Isolator features:
see S00-7100
Humidity:
5% to 95% relative humidity (non-condensing)
Maximum Wire Gauge
2.5 mm²
INSTALLATION
Note:
These modules must only be connected to control panels using compatible
proprietary analogue addressable communication protocols for monitoring and control.
M700 series modules can be mounted in several ways (See
Figure 1
):
1:1
An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2
The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in
Figure 1:2
.
Wiring to all series M700 modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
CAUTION
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 4
). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module. (Note: The number of addresses
available will be dependent on panel capability, check the panel documentation for
information on this.)
Short Circuit Isolators
All M700 series modules are provided with short circuit monitoring and isolators on the
intelligent loop. If required the isolators may be wired out of the loop to facilitate the
use of the modules on high current loaded loops, for example if sounders are used.
To achieve this, the loop out positive should be wired to terminal 5 rather than terminal
2. See the relevant wiring diagram for details.
M701E WIRING
The M701E can be wired for either
Supervised
(Figure 2)
or
Non-Supervised
(Figure 3)
operation respectively.
M701E
INSTALLATION INSTRUCTIONS
FOR THE M701E OUTPUT MODULE
EN
M701E Single Output Module with Supervised Output
When the module is used in supervised mode and power is supplied to the module,
a switched negative input on terminal 12 can be used to signal an external fault
condition, such as a power supply fault. Loss of power is also supervised in this mode
such that if the supply voltage falls below 7V a fault indication is achievable. Note that
the use of this fault mode is dependant on panel software. Please contact the panel
manufacturer for further details.
PSU monitoring is not available when the module switches the output to
Alarm
.
Wire as follows (see
Figure 2
):
a: T1
Loop Output -.
b: T2
Loop .
c: T3
Loop Input -.
d: T4
Loop Input +
e: T5
Loop . If short circuit isolation is not required, loop should be
wired to terminal 5 and not 2. Terminal 5 is internally connected to terminal 4.
f:
To enable output circuit supervision, the link supplied must be fitted across
terminals 6 and 7, and the load must be polarised.
Notifier by Honeywell, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK
CAUTION
Electrostatic Sensitive Device
Observe precautions when handling and making connections
M701E
M701E
Fig./Abb. 4
+
(i)
(ii)
(iii)
Fig./Abb. 2
Fig./Abb. 3
Fig./Abb. 5
Lift
Sollevare
Levantar
Anheben
Push down
Premere
Precionar
hacia abajo
Runterdrücken
Rotate / Ruotare
Girar /
Drehen
Rotate
Ruotare
Girar
Drehen
Clip / Agganciare
Acoplar /
Einrasten
Plug
Inserire
Conectar
Einhaken
2
3
1
1
3
2
1:2 DIN
1:1 M200E-SMB
Fig./Abb. 1