DSE3‐23 HQ
The device is classified as O. It is designed to cover a maximum volume with side A = 7 m, side B = 10 m, side C = 11 m (See
Pict. 6).
It can be installed on a wall at an altitude of 7 m or on a ceiling at h = 10 m maximum.
For wall installation, the device must be installed with the long side perpendicular to the floor and the strobe flashing unit
looking downwards. Maximum installation height is 7 m, the illumination coverage will be 5,5 m on the right, 5,5 m on the
left and 10 m on front.
For ceiling installation, the device must be installed with the long side perpendicular to the wall and the strobe flashing unit
looking towards the space to be illuminated. Consider that the wall on the side without flash will be not illuminated.
Maximum installation height is 10 m; the illumination coverage will be 7 m at the front, 5,5 m on the right and 5,5 m on the
left.
Pict. 6bis: mount the long side of the device
perpendicular with respect the wall of the room