APS2-6R/E Instruction Manual —
P/N 53232:B 2/26/2014
21
AFP-300/AFP-400
UL 864 8th Edition Configurations
7. Attach battery interconnect cable.
B.2 AFP-300/AFP-400
The APS2-6R must be mounted to the CHS-4/L chassis in the CAB-3/4 Series backbox. See “In a CAB-3/4 Series
Backbox” on page 11.
B.2.1 Connecting to the MPS-400 Power Supply
1. Connect trouble output from
J3
on the AP2S-6R to
J4
on the MPS-400.
2. Place shunt across both pins of
JP4
on the APS2-6R.
3. Connect primary power from
TB1
on the APS2-6R to terminal block
TB1
(
NEUT
and
HOT
)
on the MPS-400.
4. Connect AC power to
TB1
on the MPS-400. Make sure to properly ground the unit to the backbox.
5. Connect batteries to
TB1
on the MPS-400
6. Connect secondary power from
TB3
on the APS2-6R to terminal block
TB1
(+ and -) on the MPS-400.
JP2
JP7
JP5
SW3
SW2
JP3
JP9
JP1
JP6
+
-
Figure B.1 Wiring to AFP-200
ap
s26
raf
p2
00.
wm
f
Power-limited circuit
Non-power-limited circuits
grounding
stud
BB-17 Backbox
with batteries
AC
The shaded area and dotted lines represent
the APS2-6R and wiring behind the panel.
Note: Maintain 0.25” spacing between
Power-limited and Non-power-limited
wiring. Install tie wraps and adhesive
squares to secure the wiring.
!
WARNING:
Be sure to finish installation before applying power. Test AC power before continuing.