background image

S-326.1-ALI50EN-ENG   A. 1   05-2015  

    

 

 

 

 

 

  

                                 Page 6 of 7 

Output relay failure indication is active for: 

 

Low battery (voltage lower than 20,8 Vdc) 

 

Overcharged battery (voltage over 28 Vdc) 

 

Disconnected battery 

 

Battery internal resistance > 1 ohm 

 

Faulty fuse 

 

START UP OF THE SYSTEM 

E

ven if not imperative, the following sequence of connection is suggested: 

1.  Connect mains and ground to the concerned terminal AC1. Turn ON the AC power. The load LEDs flash and after about 20 

seconds the missed battery LED flashes 

2.  Connect the battery. After 20 seconds the LED switches off 
3.  Connect the loads: the LEDs, indicating the current supplied, light up 

 

SYSTEM RUNNING 

Battery voltage

If the voltage drops below V(B)min = 19,8V, the battery is isolated to avoid the deep discharge. After the battery gets 
unplugged, the battery will be connected to the system if the voltage is higher than 16V. 

 is monitored continuously, if the voltage drops below V(B)low = 20,8V, the relay “GUASTO” turns on and the Front panel 

“Battery Low” lights on. 

 

Battery internal resistance is tested every 2,5 hours, at least. If the resistance is higher than 1 Ohm a warning in raised. The Front Panel 

LED “Failure” is lighted on, the LED “Overcharged battery” slow flashes and the internal DL1 quick flashes. 

Battery Fuse monitoring, in case of fault of the fuse, the LED “Low battery” starts to flash slowly. When the fuse is replaced the signal 

disappear. 

Fuses monitoring, if a fuse became open the LED lights on, when the cause of fault disappears the LED lights off. 
Mains monitoring

 

, when the mains is missed, The Front Panel LED “Mains” is lighted off, and the relay “RETE” is activated. When the 

mains return LED “Mains” is lighted on, and the relay “RETE” is restored. 

SERVICING 

Periodical  programmed servicing must be carried out by qualified personnel in order to prevent the possibility of a malfunctioning of the 
power supply. It is recommended to carry out servicing every 6 months and to evaluate control panel of the system in order to check 
possible alarms during tests. 

Check the connections of the 230 Vac supplying lines 

Check the connections of the alarm indication lines and related shields 

Check the battery connections, they have to be well tightened and there must be no oxidation 

Check the output Voltage on the charge (see electrical specifications) 

 
Although the power supply is equipped with a self-diagnosis system carrying out a periodical control of the battery and indicating possible 
failures, it is suggested to manually check the battery every six months. 
 

Disconnect the battery and check if the voltage of the power supply is within the values shown. 

After re-connecting the battery, disconnect the primary supplying and check if the battery can maintain the Voltage on the higher 

23 Vdc charge. On the contrary, replace battery immediately. 

Check presence of related alarms during tests. 

 

CONTROL BOARD LEDs 

 

The DL1 LED shows the failures: 

In case of contemporary presence of more alarms, the LED indication follows the priority shown in the table 6 

 

Priority 

DL1 

ALARM 

Slow flashing (1 Hz) 

Battery disconnected  

Quick flashing (4 Hz) 

Battery resistance > 1 ohm 

On fix 

Fuse F1 (battery) interrupted 

Off 

None of previous failures 

           

 

LEDs DL2, DL3, DL4 and DL5 show the current used by the outputs

 

Condition 

LED Status 

DL2 

DL3 

DL4 

DL5 

I < 0,3 A 

OFF 

OFF 

OFF 

OFF 

I < 0,625 A 

SLOW FLASH  

OFF 

OFF 

OFF 

0,625 A < I < 1,25A 

ON 

OFF 

OFF 

OFF 

1,25 A < I < 1,875A 

ON 

SLOW FLASH  

OFF 

OFF 

1,875 A < I < 2,5A 

ON 

ON 

OFF 

OFF 

2,5A < I < 3,125 A 

ON 

ON 

SLOW FLASH 

OFF 

3,125 A < I < 3,75A 

ON 

ON 

ON 

OFF 

3,75A < I < 4,375 A 

ON 

ON 

ON 

SLOW FLASH 

4,375 A < I < 5A 

ON 

ON 

ON 

ON 

OVERLOAD I > 5A 

SLOW FLASH  

SLOW FLASH  

SLOW FLASH  

SLOW FLASH  

Note: SLOW FLASH = 1 Hz ;  

 

Tab 6 

 

Tab 7 

 

Содержание NOTIFIER ALI50EN

Страница 1: ...e test will be carried out every 10 minutes whilst in case it is not connected it will continue carry out the test every 20 seconds showing indication FAILURE During normal operation the battery efficiency is checked by controlling the batteries voltage If batteries do not manage to maintain an acceptable voltage during test there will be the indication FAILURE A test of the battery internal resis...

Страница 2: ...cerning power supplies CEI 64 8 INSTALLATION Mechanical mounting This device has to be mounted on vertical stable walls suitable to support the power supply by means of 4 screws with 6mm diameter for spacers and screws on the 4 holes on the bottom of the box The battery must be fixed using the strap given within ELECTRICAL SPECIFICATIONS Supplying Voltage 230 Vac 10 15 Ac mains frequency 50 Hz sin...

Страница 3: ...age 3 of 7 1 Rotate the screw in tie mounts in vertical position and insert the tie Do the same thing on the right side 2 Rotate the screw in tie mounts in horizontal position Do the same thing on the right side SCREW IN TIE MOUNTS TIE ...

Страница 4: ...6 1 ALI50EN ENG A 1 05 2015 Page 4 of 7 3 Insert the belt in the central screw in tie mounts Do the same thing on the right side 4 Place the battery and then fix the belt Do the same thing on the right side ...

Страница 5: ...nection N connection to neutral Checks and Adjustments Control is shown below VRES1 is adjusted at factory and Tampering of this control automatically means the lost of the warranty must not be altered by the operator VRES1 Potentiometer for adjustment of the output Voltage INDICATION ON THE FRONT PANEL located on the door of the power supply Standard visualization Alternate visualization Pushing ...

Страница 6: ...servicing must be carried out by qualified personnel in order to prevent the possibility of a malfunctioning of the power supply It is recommended to carry out servicing every 6 months and to evaluate control panel of the system in order to check possible alarms during tests Check the connections of the 230 Vac supplying lines Check the connections of the alarm indication lines and related shields...

Страница 7: ...ier s r l Via A Grandi 22 20097 S Donato Milanese MI 15 Dop N 1293 CPR 0483 EN 54 4 1997 A2 2006 AC 1999 Power supply equipment for fire detection and fire alarm systems for buildings ALI50EN Wasting This product must be wasted in appropriate wheelie bin for electric and electronic materials Do not put in wheelie bin for other kind of waste Fig 3 FUSE1 Fuse of the 230 Vac mains not replaceable F1 ...

Отзывы: