48
ACS Manual —
P/N 15842:
N3
5/4/2022
System 5000 Systems: ACM-16AT and ACM-32A Only (UL 8th)
Configuring the ACS for System 5000
G.5 Configuring the ACS for System 5000
DIP Switch settings
G.6 ACS Program Mapping
Annunciator points “track” or follow those system points they are programmed to annunciate; they do not latch. Table G.1 outlines the
annunciation of various system circuits and functions.
NOTE:
Address and DIP switches must be set before the annunciator will operate properly. The annunciator can be set for addresses 1, 2, 3
or 4. (Annunciator Address “3” and “4” are used with AIM-200. Refer to “AIM-200 Point Annunciation” on page 49.) The actual mapping
arrangement for a respective annunciator module and its expanders depends on System annunciator programming. Refer to the
System 5000
Programming Manual
for a more detailed explanation.
Switch #
ACM-16AT and ACM-32A Function
1
Not used: This switch must be set “OFF”
2, 3
Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.13.3 for more info.
4
Eight-Point Shift: Set switch “ON” to shift the control panel functions from the first eight annunciator positions to expander positions 57-64.
This shift can only be set on an annunciator set for address “1”.
5
Receive Only: Set this switch “ON” for each annunciator that will provide the same information as another annunciator in a different location.
(When two or more annunciators hold the same address, all but one must be configured as “Receive Only” annunciators.)
6
Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is “ON”.)
7
Switch Inhibit: Set this switch “ON” to disable the point control switches on the annunciator and prevent them from executing system control
functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will
function only in a local capacity unrecognized by the system.
NOTE:
Only the first four switches control the System 5000. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill.
8
Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the
piezo from sounding.
Circuit Type
ACM-16AT & AEM-16AT
ACM-32A & AEM-32A
Red LED
Yellow LED
Control Switch
1
IZM-8, IZM-8CS, IZM-8CS4
circuit
Indicates alarm status of circuit
2
Indicates trouble status of circuit
Not used
ICM-4/ICE-4 circuit
Indicates Activation
3
Indicates trouble status of circuit
Controls Notification Circuit
4
CRM-4/CRE-4 circuit
Indicates Activation
Indicates trouble status of relay
Controls Relays
TCM-2, TCM-4, VCM-4,
DCM-4 circuit
Indicates Activation
Indicates trouble status of relay
Remote Switch Functions
AIM-200 zone
5
Indicates alarm status of circuit
Indicates trouble status of circuit
Not used
Annunciator Point #1
6
Indicates System Alarm
Indicates System Trouble
ACKNOWLEDGE
Annunciator Point #2
Not used
Indicates signals have been silenced
SIGNAL SILENCE
Annunciator Point #3
Not used
Not used
SYSTEM RESET
Annunciator Point #4
Not used
Indicates Supervisory condition
Not used
Annunciator Point #5
Indicates that Notification Circuit 1 has been
activated
Indicates trouble status of circuit
Controls Notification Circuit #1
Annunciator Point #6
Indicates that Notification Circuit 2 has been
activated
Indicates trouble status of circuit
Controls Notification Circuit 2
Annunciator Point #7
Indicates that the Remote Signaling to
Municipal Tie has been activated
Indicates trouble status of circuit
7
Controls Remote Signaling
Municipal Tie
Annunciator Point #8
Indicates that the Alarm Relay has been
activated
Indicates AC Fail
Controls Alarm Relay
Table G.1 Annunciator Program Mapping with System 5000
1
These control switches are active only if all of the following conditions are set: – Receive Only (DIP Switch #5) is set to “OFF”.
– Switch Inhibit (DIP Switch #7) is set to “OFF”.
2
With Software P/N#S5000R7.0 or higher installed in the System 5000, the manner in which IZM-8 circuits programmed as supervisory are
annunciated depends upon whether Mode 1 or Mode 2 is selected.
3
These status LEDs are active only when the system is programmed for “Output Status”.
4
These control switches require that the system be programmed for “Output Control”.
5
The ACS annunciates the eight AIM-200 software zones only, except as described below.
6
If the Eight-Point Shift (DIP switch #4) is set “ON”, the eight control panel functions will be shifted from annunciator points 1 through 8 to points 57
through 64 (provided those points exist in the system).
7
Annunciator Point #7 yellow LED indicates Municipal Tie Trouble if no UDACT is installed. It will annunciate Low Battery/Ground Fault if a UDACT is
installed in the system.
NOTE:
Control Switches marked “not used” will still function as local LAMP TEST or local ACKNOWLEDGE switches for their respective
points.