Configuring via the Web Server
Configuring Other I/O & Groups Tab
NetAXS™ Access Control Unit User’s Guide
,
Document 800-00233, Revision A
2
-
45
Steps
: Use the descriptions in the following table to configure the Power Fail, Panel
Tamper, and downstream inputs:
Table 2-10: Configuration > Other I/O & Groups > Inputs Tab Field Descriptions
Setting
Description
Name
Enter a unique name to identify the device.
Mode
Normally Closed
– Specifies that the door’s normal state is
closed.
Normally Open
– Specifies that the door’s normal state is open.
Unsupervised
– Specifies that the door’s electrical circuit is
wired in one path without alternative paths supervised by
resistors.
Supervised
– Specifies that the door’s electrical circuit is wired
with alternative paths supervised by resistors.
Shunt Time
Specifies the amount of time for which the inputs will be
shunted, or de-activated. For example, it specifies how long a
door strike will remain released. Enter the desired number of
hours (1024 maximum), minutes (60 maximum), and seconds
(60 maximum). The sum of all three units comprises the shunt
time. Note that you can express seconds in tenths of a second.
Debounce Time
Specifies the period of time the input must remain in a new state
before generating an alarm. For example, if a Normal state is
changed to Alarm, the state must remain in Alarm for five
seconds before an alarm is generated.
Time Zones
Shunt
– Specifies the time period during which the input will be
energized.
Disable Interlock
– Specifies the time period during which the
programmed action on this input from another point will be
disabled.
Disable Alarm Msgs
– Specifies the time period during which
the input will generate no alarms.
Auto-Relock
Causes the door to re-lock immediately when the door status
switch closes after entry. The output relay that controls the door
strike de-energizes when the associated input returns to normal
state instead of remaining energized for the duration of the pulse
time. To enable Auto-Relock, de-select the
Disable
checkbox,
and select the associated output from the drop down list.
Содержание NetAXS
Страница 8: ...viii www honeywell com ...
Страница 18: ...1 10 www honeywell com Connecting to the Web Server Reading the Select Panel ...
Страница 74: ...2 56 www honeywell com Configuring via the Web Server Configuring Users ...
Страница 84: ...3 10 www honeywell com Configuring via WIN PAK Adding a New NetAXS Panel ...
Страница 86: ...3 12 www honeywell com Configuring via WIN PAK Adding a New NetAXS Panel ...
Страница 100: ...4 14 www honeywell com Monitoring NetAXS Status Monitoring System Status ...