background image

MV100 ELECTRIC CONTROLLERS T100, T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES

62-3048—2

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

MV100 Electric Controller

Dimensions: 

See Fig. 1.

Materials:

Body: Industrial grade plastics with low thermal conductivity.

Fastening Ring: Plated brass.

Internal Parts: Brass thermostat capsule, other metals.

Thermal element: Wax-filled brass capsule.

Electrical Ratings:

Control Type: Spst switch.

Controller: 

Voltage: 24 Vac, 60 Hz,  or 24 Vdc.

Power Consumption: 0.125A, 3W.

End Switch: Low-voltage (24 Vac, 5A), two-position, spst, 

normally open switch (closes when controller powered).

Configuration (with Controller Mounted):

Normally closed (valve remains closed without power).

NOTE: Normally open model available in Canada.

Opening Time (at 78°F): 

Maximum: 5 minutes from cold to 

fully open.

Ambient Temperature Rating: 

Maximum: 122°F (50°C).

T100,T200 Thermostatic Controllers

Models: 

See Table 1.

Dimensions: 

See Fig. 1.

Power: 

Self-powered, no electrical connections.

Components: 

Sensor, setpoint dial and valve actuator.

Materials:

Body: Industrial grade plastic with low thermal conductivity.

Fastening Ring: Plated brass.

Internal Parts: Brass thermostat capsule, other metals.

Thermal Element:

T100A,M: Wax.

T200,T100B,C,F: Liquid Ethyl Acetate (non-toxic, 

flammable).

Temperature Ratings:

Range: 43°F to 79°F (6°C to 26°C).

Maximum: 125¼F (52¼C).

V2000 Valves

Models: 

See Table 2.

Dimensions: 

See Fig. 2 and 3.

Materials:

Body: Bronze.

V2040A (1/2 in.): Brass.

Union: Brass.

Stem Seal: Double EPDM seal.

Cartridge: Brass and stainless steel with EPDM seat disk.

NOTE: Apply 25 ft.-lb. (30 N•m) torque when installing the 

valve cartridge.

Maximum Temperature Rating: 

266°F (130°C).

Maximum Pressure Ratings:

System:

Water: 145 psi (10 bar).

Steam: 15 psi (103 kPa).

Differential:

With MV100 Controller: 36 psi (248 kPa).

With T100 or T200 Controller: 14.5 psi (1 bar).

For Low Noise: 2.9 psi (20 kPa).

Sizes:

V2024H: 1/8 in.

V200LD: 1/2 in., 3/4 in.

V2040D,E,A: 1/2 in., 3/4 in., and 1 in.

Содержание MV100

Страница 1: ...ns T100A F M models have range limiting features to limit adjustment or lock at a fixed setting can require limit pin accessory EPDM valve seat disk assures tight shutoff on steam and hot water systems Nickel plated bronze cast valve body Cartridge containing all working parts inserts into valve body for ease of service Cartridges are replaceable while valves remain in service and under pressurE W...

Страница 2: ...Hz or 24 Vdc Power Consumption 0 125A 3W End Switch Low voltage 24 Vac 5A two position spst normally open switch closes when controller powered Configuration with Controller Mounted Normally closed valve remains closed without power NOTE Normally open model available in Canada Opening Time at 78 F Maximum 5 minutes from cold to fully open Ambient Temperature Rating Maximum 122 F 50 C T100 T200 The...

Страница 3: ...3 5 16 84 MAX 2 50 2 1 8 54 1 25 M12925A TOP T100A 3 77 2 50 M12929 TOP T100M CAPILLARY TUBE LENGTH 4 1 2 FT 1 4 m M12927 CAPILLARY TUBE LENGTH 4 1 2 FT 1 4 m 2 31 32 75 2 5 32 55 2 1 8 54 1 13 16 46 T100C CAPILLARY TUBE LENGTH 6 1 2 FT 2m OR 16 FT 5m M12926 2 5 32 55 2 1 8 54 2 31 32 75 1 13 16 46 T100B 3 76 MAX 1 9 16 40 13 16 20 M12945 TOP T200A H B r a u k m a n n x x x x x x x x x x x x x 2 7...

Страница 4: ... 26 C Direct with remote sensor One 6 1 2 ft 2 m Sensor is remote from combination setpoint dial and valve actuator T100M Directa None Components are in one tamper resistant unit T200A Directa None White body with chrome plated end Model Body Pattern Connection Application Inlet Outlet V2040D Straight NPT Threaded Union Nut with NPT Threaded or Sweat Use where manual valves were not originally ins...

Страница 5: ...n Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in...

Страница 6: ...to correct value One complete revolution of the black pre setting ring equals a pre setting of 10 Fig 7 Fig 7 One complete revolution equals a pre setting of 10 Table 4 CV Values NOTE Pressure drop psi flow gpm cv 2 Product Selection 1 Select the installation diagram from Fig 4 through 16 that most accurately represents your equipment and pip ing configuration 2 Use Table 4 to select the combinati...

Страница 7: ...g 12 Fig 13 Application Figure No Controller Valve 8 T100A T100M T200 MV100 V2040D 9 T100A T100M T200 MV100 V2040A 10 T100A T100M T200 MV100 V2040E 11 T100A T100M T200 MV100 V2042H 12 T100M MV100 V2040A 13 T100F MV100 V2040E 14 T100F MV100 V200LD 15 T100F MV100 V2040D 16 T100F MV100 V2042H 17 T100B MV100 V2040D 18 T100B MV100 V2040E 19 T100C MV100 V2040D 20 T100C MV100 V200LD M4631 M4632 M12934 0 ...

Страница 8: ...flow obstructions such as curtains or enclosures Two essential considerations for choosing the correct controller valve body combination for a particular installation are Adequate dimensional clearances Proper sensor positioning IMPORTANT Install built in sensor type controllers in a horizontal position to prevent air warmed by the hot valve body from influencing the sensor NOTE The most common mi...

Страница 9: ...e capsule contracts the valve opens and flow resumes through the radiation unit T100 The T100 temperature sensitive capsule expands when the temperature rises above the setpoint MV100 When signalled by the thermostat an electric element in the MV100 heats the capsule causing it to expand NOTE For normally open MV100 models the capsule cools when signalled by the thermostat SETTINGS AND ADJUSTMENTS...

Страница 10: ...r initial cost resulting from the use of less piping and elimination of radiator steam traps CAUTION Boiler Flooding Hazard Loss of system control and boiler damage can result For a one pipe steam system radiator install valve only at the vent location IMPORTANT Ensure vacuum breakers are installed on the steam system risers If vacuum breakers that open to the atmosphere at zero psig are not insta...

Страница 11: ...rn a boiler on and off check the manufacturer recommendations b In installations where turning the boiler off at the end of each cycle is undesirable install a control valve such as a Honeywell V5011 Valve on the boiler dis charge line NOTE Install the valve on the boiler side of the condensation takeoff to ensure that the condensation can return to the boiler 3 Verify that the steam pressure has ...

Страница 12: ...tion Change sensor location or change control type Control not properly installed Check for bosses and grooves reset actuator on valve and tighten knurled ring to valve body Capillary tube broken kinked or bent sharply Replace control Dirt or scale under the seat prevents tight shutoff Remove the control from the valve body allowing valve to open fully and flush away scale and debris Reinstall con...

Страница 13: ... 3 Pull handle out to clear VA8200A ball valve A close ball valve B and open drain cock to remove excess water and steam from chamber C See Fig 22 4 Unscrew end cap A and remove cartridge from chamber B See Fig 23 5 Clean or replace cartridge Fig 24 Loosening valve cartridge Fig 25 Attaching VA8200A001 to valve Fig 26 Disconnecting valve cartridge and draining chamber Fig 27 Removing valve cartrid...

Страница 14: ...62 3048 2 14 ...