Multinode Module Service
2-4
9/95
2.2.1
CAUTION
Power must be removed from the module whenever you are removing or installing any board,
including an I/O paddleboard. Be sure that an I/O paddleboard is installed in the correct slot;
some boards have only one slot that they can be installed in without causing damage. I/O
paddleboards plugged into the wrong slot can cause traces on the backplane to burn open.
Note that a given node may occupy slots 1-2-3, 4-5-6, 7-8, or 9-10 to match slots a-b-c, or
only a-b.
Table 2-1 — Node Configurations for Multinode Modules (Continued)
Computer Gateway (CG)
PLC Gateway (PLCG)
Slot
Front
Rear
Slot
Front
Rear
c
c
b
CLI
CLI I/O
b
PLCI
PLCI I/O
a
K2LCN-2
a
K2LCN-2
Redundant NIM
Network Gateway (NG)
Slot
Front
Rear
Slot
Front
Rear
b
EPNI
NIM MODEM
b
NGI
NGIO
a
K2LCN-3
(1, 2)
a
K2LCN-2
Notes:
(1) A TP485 I/O card is located in Slot 1 and 9 of the modules in the Micro TDC 3000.
(2) The TP485 in Slot 9 provides the interface to the twisted pair, short distance
(
≤
10 meters) TPLCN.
Содержание MT13-520
Страница 1: ...L 8 Node Multinode Module Service MT13 520 ...
Страница 2: ......
Страница 8: ...Multinode Module Service ii 9 95 ...
Страница 28: ...Multinode Module Service 3 8 9 95 ...
Страница 30: ...Multinode Module Service 4 2 9 95 4 1 6 5 3 1 4 2 Figure 4 1 Multinode Module Exploded View 2888 ...
Страница 32: ...Multinode Module Service 4 4 9 95 ...
Страница 36: ...Multinode Module Service 5 4 9 95 ...
Страница 38: ...Multinode Module Service 6 2 9 95 ...
Страница 48: ...Multinode Module Service Index 2 9 95 ...
Страница 51: ......