Test Failure Checks

If the detector fails either the sensitivity or functional test, several steps
should be taken to determine if the detector is faulty or simply needs to
be re-adjusted, before returning the unit.  These steps include:

1.

Verify all wiring connections and appropriate power is applied to the
detector.

2.

Verify that the optical line of sight is free from obstructions or any
other light sources including reflective objects such as gloss painted
surfaces.

It is imperative that at least 90% of the received light is from the
reflector alone, otherwise sensitivity cannot be assured.

3.

Apply the maintenance procedure in this manual.  Repeat the test
procedure.  If the detector still fails the test procedure proceed with
step 4.

4.

Repeat the alignment procedure in this manual.  If the alignment
procedure is successful repeat the test procedure.  If the detector
still fails the test it should be returned for repair.

MI-LPB2-S2I BEAM DETECTOR:  SET-UP PROCEDURE SUMMARY

Beam Alignment

 

– 

ensure power is on

Course Alignment

Carry out using target eyepiece
Adjust using horizontal and vertical thumb screws

Fine Adjustment

Initiate using 

Alignment Switch

Continue adjustment using horizontal and vertical thumb screws
When the adjustment is complete press the 

Alignment Switch

Sensitivity Setting

Select using 

Sensitivity Switch

Final Gain Adjustment

 – ensure front cover is fitted

Initiate using the 

Reset Switch

Completed when the green LED blinks

Final Verification

Use obscuration filters or reflector test card to initiate 

Fire and Fault signals

MAINTENANCE

Note:

Before cleaning the detector, notify the proper authorities that the

smoke detector system is undergoing maintenance, and therefore the
system will be temporarily out of service.  Disable the zone or system
undergoing maintenance to prevent unwanted alarms.

1.

Carefully clean the outer housing lens face. A damp soft cloth with a
mild soap may be used.  Avoid products with solvents or ammonia.

2.

Carefully clean the reflector.  A damp soft cloth with a mild soap may
be used.  Avoid products with solvents or ammonia.

Functional Testing

For periodic maintenance functional testing, the detector can be tested
using the Calibrated Test Filter method.

Note:

This test should satisfy most local periodic maintenance and

testing requirements.

If the detector fails this test refer to the Test Failure Checks described
above

PAINTING

The outer aesthetic ring may be painted using enamel or acrylic paints
either by brush or spray.

Note:

Never paint the flat lens surface of the outer housing.

In addition to the four standard sensitivity selections the detector has two
Acclimate settings.  When either of these settings is chosen the detector
will automatically adjust its sensitivity using advanced software
algorithms to select the optimum sensitivity for the environment.  The
sensitivity will be continuously adjusted within the ranges specified in the
Chart 1.

Percentage obscuration can be converted to percent per metre
assuming uniform smoke density for the entire length of the beam.  Chart
1 converts obscuration to percent per metre for all acceptable sensitivity
settings.

SENSITIVITY  TESTING

NOTES:

1.

Before testing, notify the proper authorities that the smoke detector
system is undergoing maintenance, and therefore the system will be
temporarily out of service.  Disable the zone or system undergoing
maintenance to prevent unwanted alarms.

Detectors must be tested after installation and following periodic
maintenance. The sensitivity of the MI-LPB2-S2I may be tested as follows:

Calibrated Test Filter Method

The sensitivity of the detector can be tested using an opaque material
(such as this manual ) to cover the reflector by an amount indicated by
the graduated scale on the reflector, see Figure 10.

1.

Verify the sensitivity setting of the detector in % obscuration.  See the
Sensitivity Selection section of this manual for sensitivity
determination if sensitivity is unknown.

2.

Place the blocking material over the reflector, lining it up with the
graduated marks that are 10 less than the detector setting in %
obscuration.  The detector should not alarm or fault.  Keep the
material in place for a minimum of 1 minute.

3.

Place the blocking material over the reflector lining it up with the
graduated marks that are 10 more than the detector setting in %
obscuration.  The detector should enter alarm within 1 minute.

4.

The detector can be reset with the reset switch on the detector unit or
remote reset.

CHART 1:  SENSITIVITY (%/m vs DISTANCE)

(Assuming uniform smoke distribution)

0

1

2

3

4

5

6

7

0

10

20

30

40

50

60

70

80

90

100

Distance (Metres)

O

b

scu

ra

ti

o

n

 (

%

/M

et

re

)

Level 1

Level 2

Level 3

Level 4

Figure 10. Reflector Test Card Procedure

MOVE BLOCKING MATERIAL TO
DESIRED AMOUNT OF OBSCURATION

LINE UP EDGE OF BLOCKING MATERIAL
WITH APPROPRIATE OBSCURATION
LEVEL

Содержание MORLEY-IAS MI-LPB2-S2I

Страница 1: ...ote that only a single 20cm x 20cm reflector can be mounted using the MMK The 6500 LRK BEAMLRK is not compatible with the MMK 6500 SMK BEAMSMK Surface Mounting Kit for the transmitter receiver also used in combination with the 6500 MMK BEAMMMK to give an additional 43mm depth to assist surface mounting and to permit side entry cabling RTS151KEY Remote annunciator accessory providing a reset functi...

Страница 2: ... INPUT LOOP LOOP LOOP LOOP Figure 4 RTS151KEY Wiring SEE RTS151KEY INSTALLATION INSTRUCTIONS FOR ELECTRICAL RATINGS OF RTS151KEY WIRING Note All wiring must be installed in accordance with local requirements Warning Before working on the system notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service Wiring connections are made to pluggable ter...

Страница 3: ... installed distance Ensure that the line of sight between the detector and reflector is clear and that reflective objects are a minimum of 380mm from the line of sight Ensure that both the detector and reflector are mounted within their operational parameters for off axis angles CODE SWITCH TENS ONES Figure 6 Switch Locations ISOLATOR SHUNTS SHOWN DISABLED ALIGNMENT SENSITIVITY TEST RESET Disable ...

Страница 4: ...necessary to complete this step with the outer housing installed since the housing will change the amount of light received from the reflector 1 Install the outer housing of the detector The housing is installed by tightening the four captive screws one in each corner of the housing Note The housing contains a gasket seal that protects the detector circuitry from corrosion and moisture To ensure t...

Страница 5: ...nd testing requirements If the detector fails this test refer to the Test Failure Checks described above PAINTING The outer aesthetic ring may be painted using enamel or acrylic paints either by brush or spray Note Never paint the flat lens surface of the outer housing In addition to the four standard sensitivity selections the detector has two Acclimate settings When either of these settings is c...

Страница 6: ...s too low Alignment switch Alarm On Off Off On Off Smoke test filter RTS151KEY test stations Fault Drift Comp limit reached Off 3 Quick Blinks Blink Blink Off Long term drift reference out of range Clean detector and reflector Fault Signal over range Off 2 Quick Blinks Blink Blink Off Increase of reflected signal Inspect line of sight between detector and reflector for reflective objects in beam p...