MORLEY-IAS
Dimension
Series
Page 38
Document No. 996-148-000-5, Revision: 5
User Manual
6.2 Stage
2
•
The stage 2 timer commences counting down as soon as ACCEPT key is pressed.
•
If the panel is not reset, using the
SYSTEM RESET
key, within the time allowed then a full fire alarm
condition will be raised and the sounder outputs will activate.
FIRE STG 2 01/01 Z01 Stage 2 TIME : 57s
<Zone-Location-Text><Point-Location-Text>
•
The lower line of the display cycles through the following messages every second.
<Zone-Location-Text><Point-Location-Text>
Press X to view Faults/Disablement/Test
•
Investigate the cause of the fire alarm signal.
•
If the fire alarm is found to be a false alarm, press
SYSTEM RESET
within the time allowed thereby
resetting the panel.
•
If the fire alarm is found to be genuine, activate a call point to override the remaining delays if possible
(in any case, the panel will automatically sound the alarms at the end of the stage 2 period).
•
Press
MUTE BUZZER
to silence the internal buzzer.
•
If required, press
‘X’
to return the display to the normal display indicating the number if fires, faults,
disablements and test conditions. The details of other conditions can now be viewed.
Manual Call Points (alarm boxes) will always generate an immediate fire alarm condition
regardless of any delayed day mode settings.