MORLEY-IAS
Dimension
Series
Page 12
Document No. 996-148-000-5, Revision: 5
User Manual
4.2.1 Fire Alarm Conditions
•
If the control panel initiates an alarm condition, the FIRE LED Indicators will be illuminated and, if
appropriate, the relevant ZONE FIRE LED Indicators will illuminate. The internal buzzer will sound and
the alphanumeric display will indicate the number of fires.
•
To view more detailed information regarding the fire alarm location use the navigation keys as follows.
•
Press
the
ÍÏÐÎ
keys to select the FIRES option, then press the
9
key and the display shows the
following for example:
TOTAL PANEL FIRES :1
→
:Panel Events
TOTAL ZONES IN FIRE :2
↓
:Zone Details
•
This display indicates that there are two zones in fire and that a fire alarm has been raised at the
panel. To view these, press the
Î
key to view the fire alarm initiated at the panel and press the
Ð
key
to view the zones in fire.
4.2.1.1
Panel Fire Alarms
FIRE 01/01 11:22
EVACUATE
←
:back
R
:more
•
The above example shows there are one of one fire alarm raised at the panel. This was an “Evacuate”
raised at 11:22AM when the “Sound Alarms” key was pressed.
•
If there is more than one fire alarm indicated, use the
Ï
and
Ð
keys to view these (Note: The ‘
R
:
more’ option is not shown if there is only one event, the ‘
↓
’ and ‘
↑
’ keys are shown for the first and last
entries in the list). Press the
Í
key to return to the previous display.
4.2.1.2
Zone Fire Alarms
•
When selected, the display shows the first zone with a fire alarm condition. For example:
IN FIRE ZONE 3 1/ 2
R
:More Zones
<Zone-Location-Text>
→
:Device Details
•
The display shows the Zone number and Zone Location Text (20 character description).
•
To view other zones in fire (or to return to the previous display), press the
Ï
and
Ð
keys.
•
To view the devices (points) in a fire alarm condition, press the
Î
key. The display then shows the
first point in alarm in the selected zone. For example:
FIRE 01/02 Z04 L1 A011 MCP 11:45
<Point-Location-Txt>
←
:back
R
:more
•
The display shows the alarm number and the total number of devices (points) in a fire alarm condition in
this zone (01/02), the Zone number (Z04), the loop number to which this device is connected (L1), the
address of this device on the loop (A011), the type of device (MCP), the time at which the device entered
the alarm condition (11:45) and the Point Location Text (20 character description) for this device.