Q7130A, Q7230A, Q7330A MODUTROL IV INTERFACE MODULES

5

63-2235—07

12.

Recheck the fully open position and readjust the span 

potentiometer, if necessary. (Turn the span potentiome-

ter clockwise to close the motor, counterclockwise to 

open the motor.) Verify the mid point of your stroke.

Fig. 5. Q7230A terminals and adjustments.

Fig. 6. Sequential operation of three motors with Q7230A 

Interface Module.

13.

For sequential operation at two or more motors (as 

shown in Fig. 6), repeat the above steps for each motor, 

individually adjusting each for the desired response to 

the input signal.

Fig. 7. Typical wiring diagram for Q7230A Interface 

Module and M91XXX Modutrol IV Motor with 4-20 mA 

controller.

Fig. 8. Typical wiring diagram for Q7230A Interface 

Module and M91XXX Modutrol IV Motor with 2-10 Vdc 

controller.

M27213

T1 T2 F

Com

V+

CCW

CW

ZERO

SPAN

1+

20

(10)

16

(8)

12

(6)

8

(4)

4

(2)

0

CONTROL

 OUTPUT

mA

 CURRENT

 (OR VOL

TS DC)

CLOSED

OPEN

CLOSED

OPEN

CLOSED

OPEN

MOTOR 1

MOTOR 2

MOTOR 3

1

3

3

3

1

MOTOR 1 PROPORTIONS BETWEEN 4 AND 12 mA; FULLY
CLOSED AT 4 mA, FULLY OPENED AT 12 mA.

MOTOR 2 PROPORTIONS BETWEEN 8 AND 16 mA; FULLY
CLOSED AT 8 mA, FULLY OPENED AT 16 mA.

MOTOR 3 PROPORTIONS BETWEEN 12 AND 20 mA SIGNAL; 
FULLY CLOSED AT 12 mA, FULLY OPENED AT 20 mA.

UP TO 6 MOTORS CAN BE DRIVEN SEQUENTIALY OR IN 
UNISON FROM ONE CONTROLLER.

ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS 
TO ACHIEVE DESIRED SEQUENCE.

2

2

3

SEQUENTIAL OPERATION

FOR ADJUSTABLE ZERO AND SPAN MODELS

M2893A

4

4-20 mA
CONTROLLER

L1
(HOT)

L2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.

CONNECTING TO EITHER (+) OR (-) WILL DRIVE THE 
MOTOR TO FULLY OPEN.

DRIVE UP TO SIX MOTORS IN UNISON.

EACH MOTOR MUST HAVE SEPARATE TRANSFORMER.
IF COMMON LINE VOLTAGE SUPPLY MUST BE USED,
ADD ISOLATION TRANSFORMER TO EACH M91XX MOTOR.

INTERNAL MODUTROL IV CONNECTION.

1

M506H

1

3

 MOTOR

 MOTOR

+

 MOTOR

2

F

I+

COM

T1

T2

5

5

2

F

I+

COM

T1

T2

5

2

F

I+

COM

T1

T2

5

2

3

4

2-10 Vdc
CONTROLLER

L1
(HOT)

L2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQURED.

CONNECTING TO EITHER (+) OR (-) WILL DRIVE THE 
MOTOR TO FULLY OPEN.

INTERNAL MODUTROL IV CONNECTION.

1

M29166

1

+

 MOTOR

2

F

V+

COM

T1

T2

3

2

3

Содержание Modutrol IV Interface Modules Q7130A

Страница 1: ...ure provides easy handling and protection for circuitry Q7130A provides selectable voltage range 4 7 6 9 or 10 5 13 5 Vdc Adapts M91XX Modtrol IV Motor to function as M71XX model for M734H J M744D M745G P replacements Includes reversing switch to allow replacement of electrically normally open or electrically normally closed motors Q7230A provides current or voltage control 4 20 mA and 2 10 Vdc wi...

Страница 2: ...r applications Module controls only one motor See Table 1 Electrical Ratings Input Voltage 24 Vac 50 60 Hz Power Consumption 2 VA Input Impedance Q7130A 100k ohms Q7230A voltage input 100k ohms current input 67 ohms Temperature Rating 40 F to 150 F 40 C to 66 C Dimensions See Fig 1 Fig 1 Q7130 Q7230 Q7330 Modutrol IV Interface Module dimensions in in mm a Refer to customer honeywell com for cross ...

Страница 3: ...om the motor 4 If motor has an internal transformer make sure trans former is not powered and disconnect secondary wires from T1 and T2 terminals Clip quick connect termina tions from transformer secondary brown wires Trim 1 8 to 1 4 in 3 to 6 mm of insulation from the ends of the wire Tin wire ends with solder 5 Plug terminal block onto quick connect terminals inside wiring box 6 Connect field wi...

Страница 4: ... motor starts to open 8 Turn the zero potentiometer slowly clockwise until the motor is fully closed This is defined as the zero setting 9 Set the controller to output the signal required to drive the motor to the fully open position Wait for the motor to stop driving open 10 Turn the span potentiometer slowly clockwise until the motor starts to drive closed The difference between the fully open p...

Страница 5: ...MOTOR 1 PROPORTIONS BETWEEN 4 AND 12 mA FULLY CLOSED AT 4 mA FULLY OPENED AT 12 mA MOTOR 2 PROPORTIONS BETWEEN 8 AND 16 mA FULLY CLOSED AT 8 mA FULLY OPENED AT 16 mA MOTOR 3 PROPORTIONS BETWEEN 12 AND 20 mA SIGNAL FULLY CLOSED AT 12 mA FULLY OPENED AT 20 mA UP TO 6 MOTORS CAN BE DRIVEN SEQUENTIALY OR IN UNISON FROM ONE CONTROLLER ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED...

Страница 6: ...unterclockwise Position 1 Open terminals F Motor closes fully ccw Motor opens fully cw 2 Jumper F to Motor opens fully cw Motor closes fully ccw 3 Remove either T terminal Spring return motors return to normal spring position fully ccw for mechanically normally closed motors fully cw for mechanically normally open motors M27214 T1 T2 4 3 1 2 4 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OV...

Страница 7: ... Fully ccw as viewed from power end Motor opens Fully cw as viewed from the power end 2 With motor powered jumper terminals 1 and 2 Motor drives open clockwise as viewed from powered end Motor drives closed counterclockwise as viewed from the power end 3 Remove either T terminal or disconnect power supply Spring return motors return to normal spring position fully ccw for mechanically normally clo...

Страница 8: ...ions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 63 2235 07 T D Rev 01 11 Printed in U S A ...

Отзывы: