When Installing This Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check the ratings and description given in this specifi-

cation to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

5. Excessive force can damage potentiometer con-

trols.

Use a small screwdriver when adjusting all potentiome-

ters located on the unit. 

CAUTION

Disconnect power before installation to prevent 

electrical shock or equipment damage.

IMPORTANT:

For ease of adjustment, make all stroke and auxiliary 

switch adjustments before installing the interface 

module. After installation, access to the stroke adjust 

cams and auxiliary switches inside the motor is 

restricted. For complete details on performing these 

adjustments, refer to the specification sheet packed 

with the Modutrol Motor.

Installing Terminal Block

CAUTION

When installing the terminal block on the motor 

quick connects, push the board straight down.

Rocking or tilting of the board can damage the 

electrical connectors and result in an inoperative 

wiring module.

1.

Disconnect power from the M91XX Modutrol IV Motor to 

prevent electrical shock or equipment damage.

2.

Remove wiring box cover from the motor by removing 

four screws.

3.

Disconnect all field wiring from the motor.

4.

If motor has an internal transformer, make sure trans-

former is not powered and disconnect secondary wires 

from T1 and T2 terminals. Clip quick-connect termina-

tions from transformer secondary (brown) wires. Trim

1/8 to 1/4 in. (3 to 6 mm) of insulation from the ends of 

the wire. Tin wire ends with solder.

5.

Plug terminal block onto quick-connect terminals inside 

wiring box.

6.

Connect field wiring to screw terminals on terminal 

block. See Fig. 3, 5, and 9 for terminal designations. 

Trim wire ends neatly and tin with solder.

7.

Position circuit module and secure.

SETTINGS AND ADJUSTMENTS

Module Adjustments

Q7130A Adjustments (Fig. 3)

The Q7130A provides selectable range, two-wire voltage 

control (4-7, 6-9 or 10.5-13.5 Vdc). It includes a clockwise/

counterclockwise (cw/ccw) switch for replacing electrically 

normally open or electrically normally closed motors. Please 

remove film from CW/CCW switch before use.

1.

Set Mod IV motor pots—both CW or both CCW for your 

application. Use the checkout procedure in Table 2 to 

ensure proper motor function.

2.

Select desired voltage range using the three-position 

switch reference chart for dip switch settings (see Fig. 

2).

3.

Select desired rotation. Select cw for electrically nor-

mally closed (motor drives clockwise

, as viewed 

from power end, to open with an increase in control sig-

nal). Select ccw for electrically normally open (motor 

drives counterclockwise

, as viewed from power 

end, to close with an increase in control signal) (default 

switch position is clockwise).

4.

See Fig. 4 for typical system wiring.

5.

Set controller to drive motor to fully open position and 

then to fully closed position to check for proper opera-

tion.

Fig. 2. DIP switch reference.

M29165

4-7

Q7130 

6-9

10.5-13.5

Содержание Modutrol IV Interface Modules Q7130A

Страница 1: ...ure provides easy handling and protection for circuitry Q7130A provides selectable voltage range 4 7 6 9 or 10 5 13 5 Vdc Adapts M91XX Modtrol IV Motor to function as M71XX model for M734H J M744D M745G P replacements Includes reversing switch to allow replacement of electrically normally open or electrically normally closed motors Q7230A provides current or voltage control 4 20 mA and 2 10 Vdc wi...

Страница 2: ...r applications Module controls only one motor See Table 1 Electrical Ratings Input Voltage 24 Vac 50 60 Hz Power Consumption 2 VA Input Impedance Q7130A 100k ohms Q7230A voltage input 100k ohms current input 67 ohms Temperature Rating 40 F to 150 F 40 C to 66 C Dimensions See Fig 1 Fig 1 Q7130 Q7230 Q7330 Modutrol IV Interface Module dimensions in in mm a Refer to customer honeywell com for cross ...

Страница 3: ...om the motor 4 If motor has an internal transformer make sure trans former is not powered and disconnect secondary wires from T1 and T2 terminals Clip quick connect termina tions from transformer secondary brown wires Trim 1 8 to 1 4 in 3 to 6 mm of insulation from the ends of the wire Tin wire ends with solder 5 Plug terminal block onto quick connect terminals inside wiring box 6 Connect field wi...

Страница 4: ... motor starts to open 8 Turn the zero potentiometer slowly clockwise until the motor is fully closed This is defined as the zero setting 9 Set the controller to output the signal required to drive the motor to the fully open position Wait for the motor to stop driving open 10 Turn the span potentiometer slowly clockwise until the motor starts to drive closed The difference between the fully open p...

Страница 5: ...MOTOR 1 PROPORTIONS BETWEEN 4 AND 12 mA FULLY CLOSED AT 4 mA FULLY OPENED AT 12 mA MOTOR 2 PROPORTIONS BETWEEN 8 AND 16 mA FULLY CLOSED AT 8 mA FULLY OPENED AT 16 mA MOTOR 3 PROPORTIONS BETWEEN 12 AND 20 mA SIGNAL FULLY CLOSED AT 12 mA FULLY OPENED AT 20 mA UP TO 6 MOTORS CAN BE DRIVEN SEQUENTIALY OR IN UNISON FROM ONE CONTROLLER ADJUST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED...

Страница 6: ...unterclockwise Position 1 Open terminals F Motor closes fully ccw Motor opens fully cw 2 Jumper F to Motor opens fully cw Motor closes fully ccw 3 Remove either T terminal Spring return motors return to normal spring position fully ccw for mechanically normally closed motors fully cw for mechanically normally open motors M27214 T1 T2 4 3 1 2 4 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OV...

Страница 7: ... Fully ccw as viewed from power end Motor opens Fully cw as viewed from the power end 2 With motor powered jumper terminals 1 and 2 Motor drives open clockwise as viewed from powered end Motor drives closed counterclockwise as viewed from the power end 3 Remove either T terminal or disconnect power supply Spring return motors return to normal spring position fully ccw for mechanically normally clo...

Страница 8: ...ions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 63 2235 07 T D Rev 01 11 Printed in U S A ...