S7810M MODBUS™ MODULE
65-0249—07
20
.
7800 SERIES Burner Control State Bits
The burner control sequence state is translated into State Bit
Register as shown in Table 22.
Table 21. Burner Control Type Codes
CODE
DEVICE DESCRIPTION
0
(undefined)
100
RM7800E
101
RM7800G
102
RM7800L
103
RM7800M
104
RM7838A
105
RM7838B
106
RM7840E
107
RM7840G
108
RM7840L
109
RM7840M
110
RM7885A
111
RM7888A
112
RM7890A
113
RM7895A
114
RM7895B
115
RM7823A
116
RM7824A
117
RM7830A
118
RM8738C
119
RM7845A
120
RM7850A
121
RM7865A
122
RM7865B
123
RM7865C
124
RM7890B
125
RM7890C
126
RM7890D
127
RM7895C
128
RM7895D
129
RM7895E
130
RM7895F
131
RM7896A
132
RM7896B
133
RM7896C
134
RM7896D
135
RM7897A
136
RM7897C
137
RM7898A
138
R7140G
139
R7140L
140
R7140M
199
RM78xx
200
EC7810A
201
EC7820A
202
EC7830A
203
EC7850A
204
EC7885A
205
EC7890A
206
EC7895A
207
EC7895C
208
EC7823A
209
EC7840L
210
EC7865
299
EC78xx
Table 22. Burner Control State Bits.
BIT
Description
BC State Bits Register
0
Initiate
0000 0000 0000 0001
1
Standby
0000 0000 0000 0010
2
Purge
0000 0000 0000 0100
3
Pilot Ignition
0000 0000 0000 1000
4
Main Ignition
0000 0000 0001 0000
5
Run
0000 0000 0010 0000
6
Postpurge
0000 0000 0100 0000
7
Pre-Ignition
0000 0000 1000 0000
8
Valve Proving
0000 0001 0000 0000
13
Alarm
1010 0000 xxxx xxxx
NOTE: Lockout bit is also set.
14
Hold
0100 0000 xxxx xxxx
One other bit may be on.
15
Lockout
1010 0000 0000 0000
NOTE: Alarm bit is also set.
Table 21. Burner Control Type Codes (Continued)
CODE