S7810M MODBUS™ MODULE
19
65-0249—07
7800 SERIES Burner Control Fault History Records
Table 18 describes the registers that are part of a fault history
record. To determine the actual register address for a
parameter within the record, add the register offset to the start
address of the record.
Expanded Annunciator
The codes shown in Table 19 are available in the Expanded
Annunciator First Out Code Register. These codes are
normally translated to the appropriate fault code by the Burner
Control. The fault code will then be translated to the
appropriate first and second line messages as shown in Table
17 for use by the UMC800 Operator Interface.
Response Message Format for Function Code 17.
This format is device specific and is only available for the 7800
SERIES burner control. See Table 20.
Table 20. Response Message Format for function code 17 (11h), (26 bytes).
a
Slave ID: Always 0x78 when using RM78xx or EC78xx Relay Modules(1 byte) (byte 3).
b
Run Indicator Status: Always FF=ON (one byte)(byte 4).
c
Device Description: ASCII OS number for the Burner Control (11 bytes) (bytes 5-15).
Burner Control Type Codes
The burner control type code indicates the exact model
number of the burner control. See Table 21.
246
FAULT 21h: HIGH OIL
PRESSURE
EA
43
247
FAULT 21g: BOTH FUELS
SELECT
EA
21
248
FAULT 21f: FUEL SELECT OFF
EA
38
249
FAULT 21e: AUX LIMIT #3
EA
19
250
FAULT 21d: HIGH LIMIT
EA
42
251
FAULT 21c: LWCO
EA
63
252
FAULT 21b: AUX LIMIT #2
EA
18
253
FAULT 21a: AUX LIMIT #1
EA
17
254
FAULT 10z: OTHER PREIGN ILK
EA
75
255
FAULT 10y: VALVE CLOSURE
EA
109
Table 18. Fault History Record Format.
Offset Parameter Name Access Format
Notes
0
Fault code
R
U16
See Table
17.
1
Fault String
R
U16
See Table
16.
2
Sequence State
R
U16
See Table
15.
3
First line message
R
U16
See Table16.
4
Second line
message
R
U16
See Table
16.
5
Sequence time
R
U16
Seconds.
6-7
Total cycles
R
U32
8-9
Total hours
R
U32
Table 17. 7800 SERIES Fault Codes. (Continued)
Fault
Code
(Reg
40001)
Fault Message
(NOTE: FAULT n: is not in
the Fault and Strings Code)
Fault
String
Code
(Table 16)
Table 19. Expanded Annunciator
First Out Code.
EA Status
Value (binary)
Status Message
Line 2 String
Code (Table 16)
0xx 00000
No Expanded
Annunciator
N/A
0xx 00001
Burner Sw.
23
0xx 00010
Control On
27
0xx 00011
Aux. Limit #1
17
0xx 00100
Aux. Limit #2
18
0xx 00101
LWCO
63
0xx 00110
High Limit
42
0xx 00111
Aux. Limit #3
19
0xx 01000
FuelSelect Off
38
0xx 01001
BothFuelSelect
21
0xx 01010
High Oil Pres.
43
0xx 01011
Low Oil Pres.
61
0xx 01100
High Oil Temp
44
0xx 01101
Low Oil Temp.
62
0xx 01110
Atomizing Sw.
14
0xx 01111
High Gas Pres.
41
0xx 10000
Low Gas Pres.
59
0xx 10001
Airflow Sw.
13
0xx 10010
Aux. ILK #4
15
0xx 10011
Aux. ILK #5
16
0xx 10100
All Switches On (or)
Other PII (if hold or
lockout condition exists)
110
74
0x1 XXXXX
Valve Closure
109
00XX XXXX
Gas Select
N/A
01XX XXXX
Oil Select
N/A
If the BC is in Standby and the 5LSB value is 1-16, then the
cause of the Standby Hold is the 5LSB value; otherwise the
hold is “Circuit Fault”.
Slave
Address
Function
Code
Byte Count Slave ID
a
Run Indicator
Status
b
Device
Description
c
N/A
CRC
CRC
Byte
0
1
2
3
4
5-15
16-23
24
25