background image

MN6105VAV 5 NM VAV ACTUATOR

3

31-00150EF—03

Installing the New Actuator

1.

Install new actuator by inserting the anti-rotation 
end below the foam block in the bottom of the hous-
ing, then push the output end of the actuator into 
the locking mechanism. It should distinctly snap 
into place.

NOTE:

The actuator must be flat against the bot-
tom of the enclosure. If not, check that the 
slot of the actuator is below the plastic anti-
rotation feature in the bottom of the enclo-
sure.

2.

Replace the wiring connector, with the cables point-
ing down and away from the circuit board.

3.

Replace the cover that was previously set aside by 
latching the tabs on the top of the housing, and 
pushing down on the bottom of the cover until the 
bottom tabs engage.

NOTE:

The actuator declutch button may need to 
be pushed down while rotating the cover 
down to engage the bottom tabs.

4.

Follow the steps in “Mounting Actuator Onto 
Damper Shaft” below to re-install the actuator onto 
the VAV box.

Mounting Actuator Onto Damper Shaft

Tools required:
— Phillips #2 screwdriver - end-limit set screw 

adjustment

— 8 mm wrench - shaft adapter nuts
The unit is shipped with the actuator set to rotate open in 
the clockwise (CW) direction to a full 95 degrees. The extra 
5 degrees ensures a full opening range for a 90 degree 
damper. The installation procedure varies depending on 
the damper opening direction and angle:

1.

If the damper rotates clockwise (CW) to open, and 
the angle of the damper open-to-closed is 90 
degrees:
a. Manually open the damper fully (rotate clock-

wise). 

b. Using the declutch button, rotate the universal 

shaft adapter fully clockwise. 

c.

Mount the actuator to the VAV damper box and 
shaft. 

d. Tighten the two bolts on the centering clamp 

(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] 
torque). When the actuator closes, the damper 
rotates CCW 90 degrees to fully close. 

2.

If the damper rotates clockwise (CW) to open, and 
the angle of the damper open-to-closed is 45 or 60 
degrees:
a. Manually open the damper fully (rotate clock-

wise).

b. The actuator is shipped with the mechanical 

end-limits set at 95 degrees. Adjust the two 
mechanical end-limit set screws to provide the 

desired amount of rotation. Adjust the two set 
screws closer together to reduce the rotation 
travel.

c. Tighten the two mechanical end-limit screws 

(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5 
Nm] torque).

d. Using the declutch button, rotate the universal 

shaft adapter fully clockwise. 

e. Mount the actuator to the VAV damper box and 

shaft. 

f.

Tighten the two bolts on the centering clamp 
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] 
torque).

g. When the actuator closes, the damper rotates 

CCW either 45 or 60 degrees to fully close.

3.

If the damper rotates counterclockwise (CCW) to open, 
and the angle of the damper open-to-closed is 
90 degrees:
a. Manually open the damper fully (rotate counter-

clockwise).

b. Using the declutch button, rotate the universal 

shaft adapter fully counterclockwise. 

c. Mount the actuator to the damper box and shaft. 
d. Tighten the two bolts on the centering clamp (8 

mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). 
When the actuator closes, the damper rotates 
CW 90 degrees to fully close.

4.

If the damper rotates counterclockwise to open, and 
the angle of the damper open-to-closed is 45 or 
60 degrees:
a. Manually open the damper fully (rotate counter-

clockwise).

b. The actuator is shipped with the mechanical 

end-limits set at 95 degrees. Adjust the two 
mechanical end-limit set screws to provide the 
desired amount of rotation. Adjust the two set 
screws closer together to reduce the rotation 
travel.

c. Tighten the two mechanical end-limit screws 

(Phillips #2 screwdriver; 26.5–31 lb-in. [3.0–3.5 
Nm] torque).

d. Using the declutch button, rotate the universal 

shaft adapter fully counter-clockwise. 

e. Mount the actuator to the VAV damper box and 

shaft. 

f.

Tighten the two bolts on the centering clamp 
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] 
torque).

g. When the actuator closes, the damper rotates 

CW either 45 or 60 degrees to fully close.

IMPORTANT

Special precautions must be taken for dampers 
that open in a CCW direction. The actuator is 
shipped with its rotation direction set to CW to 
Open, which applies to the damper direction in 
steps 1 and 2 above. If the damper shaft rotates in 
the CCW direction to open, the controller software 
must be programmed to change the rotation to 
“Reverse to Open,” which applies to the damper 
direction in steps 3 and 4 above. 

Содержание MN6105VAV

Страница 1: ...er nominal voltage conditions Power consumption MN6105 5 VA 2 W Ambient limits Ambient operating limits 5 122 F 20 50 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Lifetime Full strokes 60000 Repositions 1 5 million Mounting Round damper shaft 3 8 1 2 in 9 5 12 7 mm Square damper shaft 1 4 1 2 in 6 4 12 7 mm 45 steps Shaft length min 1 5 8 in 41 3 mm Torque rating...

Страница 2: ...ws set to 95 degrees of rota tion Adjust the two set screws closer together to reduce the rotation travel Each hash mark indicator on the bracket represents approxi mately 6 5 of rotation per side 2 The declutch button when pressed allows you to rotate the universal shaft adapter see Fig 1 IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 Fig 1 Series 60 Flo...

Страница 3: ...chanical end limit set screws to provide the desired amount of rotation Adjust the two set screws closer together to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 26 5 31 lb in 3 0 3 5 Nm torque d Using the declutch button rotate the universal shaft adapter fully clockwise e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts...

Страница 4: ...t any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you Panel Mounting The controller enclosure is constructed of a plastic base plate and a plastic factory snap on cover NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts usi...

Страница 5: ... 60 Hz Toutes les valeurs du présent document s appliquent à une utilisation à tension nominale normale Consommation électrique MN6105 5 VA 2 W Plages d utilisation Plage de températures de fonctionnement 20 à 50 C 5 à 122 F Plage de températures d entreposage 30 à 80 C 22 à 176 F Humidité relative 5 à 95 sans condensation Durée de vie Courses complètes 60000 Repositionnements 1 5 million Montage ...

Страница 6: ...ossède une course rotationnelle totale de 95 voir la figure 1 REMARQUES 1 Le servomoteur est livré avec les vis de réglage de butée mécanique de fin de course réglées à une rotation de 95 Réglez les deux vis plus près l une de l autre pour réduire la course de rotation Chaque indicateur hachuré sur le support correspond à environ 6 5 de rotation de chaque côté 2 Vous pouvez tourner l adaptateur d ...

Страница 7: ...et à la main rotation horaire b Le servomoteur est livré avec les vis de réglage de butée mécanique de fin de course réglées à une rotation de 95 Réglez les deux vis de réglage de butée mécanique de fin de course pour obtenir le degré de rotation voulu Réglez les deux vis plus près l une de l autre pour réduire la course de rotation c Serrez les deux vis de butée mécanique de fin de course tournev...

Страница 8: ...ts qui s ouvrent en sens antihoraire Le servomoteur est livré configuré pour une ouver ture dans le sens horaire ce qui s applique au sens de rotation du volet des étapes 1 et 2 ci dessus Si l arbre de volet tourne en sens antihoraire pour ouvrir le volet vous devez modifier le logiciel du régulateur et régler la rotation à Inverser pour ouvrir ce qui s applique au sens de rotation du volet des ét...

Отзывы: