background image

ML6420, ML7420 NON-SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS

3

63-2533—03

Table 1. Close-off ratings for ML6420, ML7420 Electric Linear Valve Actuators and Honeywell Valves (psi).

a

Represents maximum pressure difference between the outlet and either of the two inlets.

b

Do not exceed 100 psi with V5011G valves used in steam applications.

Fig. 1. Approximate dimensions of ML6420, ML7420 

Electric Linear Valve Actuator in in. (mm).

INSTALLATION

When Installing this Product...

1.

Read instructions carefully. Failure to follow them could 

damage the product or cause a hazardous condition.

2.

Check ratings and description given in the specifications 

to make sure the product is suitable for your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment circuitry.

Disconnect power supply before installation.

Location

Install the actuator in a location that allows enough clearance 

for mounting accessories and for servicing.

CAUTION

Equipment Damage Hazard.

Can damage actuator due to condensation or a 

valve gland leak.

Install the actuator in a position above horizontal.

Mounting

1.

Place the actuator on the valve with the U-bolt around 

the valve collar. See Fig. 2.

2.

Place the U-bolt against the valve collar and secure the 

actuator to the valve by turning each U-bolt nut clock-

wise.

NOTE: To assure even pressure on the collar, first 

tighten the nuts finger-tight and then alternate 

turning each U-bolt nut until both are snug.

3.

Push aside the stem button retaining clip and hold. See 

Fig. 3.

4.

Lift valve stem until the head of the valve stem button is 

inside the large slot of the stem button retaining clip on 

the actuator.

5.

Release the stem button retaining clip to secure the stem 

button. Check to make certain the stem button is secured 

by the retaining clip.

6.

Remove the cover from the actuator using a Phillips or 

crosspoint screwdriver. See Fig. 4.

Type

Valve

1/2 in.

3/4 in.

1 in.

1-1/4 in. 1-1/2 in.

2 in.

2-1/2 in.

3 in.

Flange

V5011A

28

16

V3350/3351/3450/3451

21

14

V5013B,C; V3360/3361/3460/3461

21

a

14

a

NPT

V5011F,G

150

b

150

b

150

b

134

b

77

49

28

16

V5011H,J

150

150

150

145

V5011N1xxx, V5011N3xxx, V5013N

230

230

163

104

67

37

V5011N2xxx

100

100

100

100

V5013F

150

150

150

126

77

49

5-5/15 
(135)

6-5/16 
(161)

x

2-11/16 (67)

12-11/16 (322)
MINIMUM
CLEARANCE

9-3/16

(233)

9-9/16

(242)

5-9/16

(141)

M17419

1/2 (13) FPT

YOKE 
DIAMETER
1-3/8 (35)

Содержание ML6420

Страница 1: ...rollers that provide an analog output of 0 to 10 Vdc or 2 to 10 Vdc These actuators operate standard Honeywell valves in HVAC applications An internal selector plug can be used to reverse the direction of action FEATURES Quick and easy installation No separate linkage required Conduit connector is standard No adjustments required Low power consumption High close off ratings Force limiting end swit...

Страница 2: ...t 24 Vac ML7420 7 VA maximum at 24 Vac Signal Source Output Resistance 1K ohm maximum Signal Load 1 mA maximum Ambient Ratings Temperature Ambient 14 F to 122 F 10 C to 50 C Storage 40 F to 158 F 40 C to 70 C Maximum Valve Medium 300 F 150 C Humidity 5 to 95 percent relative humidity noncondensing Stem Force 135 lbf 600N Signal Inputs Supply Voltage Between Terminals ML6420 B and 24 Vac Drives val...

Страница 3: ...ge actuator due to condensation or a valve gland leak Install the actuator in a position above horizontal Mounting 1 Place the actuator on the valve with the U bolt around the valve collar See Fig 2 2 Place the U bolt against the valve collar and secure the actuator to the valve by turning each U bolt nut clock wise NOTE To assure even pressure on the collar first tighten the nuts finger tight and...

Страница 4: ...ng the wiring diagram in Fig 6 connect power and control wires Make sure that all wiring is correct 3 For ML7420 only Check the selector plugs for proper settings See Signal Input Failure section for details 4 When wiring is complete replace the actuator cover See Fig 7 5 Apply power and control signals to the actuator Fig 5 Connecting power and control wiring Fig 6 ML6420 wiring M6632 M6633 M1742...

Страница 5: ... O1 O2 1 3 2 INPUT FEEDBACK OUTPUT 3 2 1 L1 HOT L2 M17422 L1 HOT L2 1 1 WIRING STRIP F T2 T1 O1 O2 1 1 2 2 3 3 4 5 6 L1 HOT L2 1 ML7420 T775 WITH 2 10 VDC OUTPUT DUAL TRANSFORMERS POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M17423 SENSOR L1 HOT L2 1 1 WIRING STRIP F T2 T1 O1 O2 1 1 2 2 3 3 4 5 6 ML7420 T775 WITH 2 10 VDC OUTPUT SINGLE TRANSFORMER 40 VA 24 VAC POWER SU...

Страница 6: ...ML6420 ML7420 NON SPRING RETURN ELECTRIC LINEAR VALVE ACTUATORS 63 2533 03 6 Fig 13 Replacing actuator cover M17428 ...

Страница 7: ...and stop the motor After a manual valve close off operation release the spindle one turn by turning the manual operator knob This will ensure automatic disengagement of the manual operator upon power resumption NOTE If the manual operator knob is not pushed in while turned it will rotate only a short distance before disengaging without power resumption Fig 14 Manual operator knob ML7420 Signal Inp...

Страница 8: ... 24 Vac is correctly applied to the actuator 3 Apply the power to the appropriate leadwires to move the valve 4 If the actuator does not move make sure the actuator is properly installed wired 5 If the actuator installation and wiring are both correct and the actuator does not run replace the actuator Controller Checkout 1 Adjust the setpoint of the controller to call for opening the valve Observe...

Отзывы: