ModBus
Register
Number
Information R/W
Data
Type
Data
Size
(Byte)
Description
Note
40002
Monitoring
Status
R
u16
2
bit 0 : Warmup bit 1 : Inhibit Mode bit 2
: Alarm/Fault simulation bit 3 : 4-20mA
calibration mode bit 4 : 4-20mA test
mode bit 5 : Flow calibration mode bit
6 : LIT calibration mode (Reserved) bit
7 : LIT Enabled (Reserved) bit 8 : Gas
calibration mode bit 9 : Gas bump test
mode bit 10 : Alarm bit 11 : Fault bit 12
~ 15 : for future expansion
40003
Alarm State
R
u16
2
bit 0 : Ch1 Alarm 1 active bit 1 : Ch1
Alarm 2 active bit 2 : Ch2 Alarm 1
active bit 3 : Ch2 Alarm 2 active bit 4 :
Ch3 Alarm 1 active bit 5 : Ch3 Alarm 2
active bit 6 : Ch4 Alarm 1 active bit 7 :
Ch4 Alarm 2 active bit 8~15 : for future
expansion
40004
Fault State
R
u16
2
bit 0 : Ch1 fault active bit 1 : Ch2 fault
active bit 2 : Ch3 fault active bit 3 : Ch4
fault active bit 4 : Device fault active bit
5~15 : for future expansion
40005
Top Fault
R
u16
2
Number of
most important
active fault
Midas-M
87
User Manual
Содержание Midas-M
Страница 2: ......
Страница 6: ......
Страница 9: ...User Interface Detector s User Interface overview Midas M 9 User Manual ...
Страница 16: ...Midas M 16 User Manual ...
Страница 25: ...Generic example Midas M Isolated 4 20mA output w PoE power Midas M 25 User Manual ...
Страница 37: ...Option Operations you can Test from the selected option l Inhibit time Midas M 37 User Manual ...
Страница 55: ...3 Wait until the gas reading is stable and then click Accept Midas M 55 User Manual ...
Страница 63: ...Midas M 63 User Manual ...
Страница 64: ......
Страница 68: ......
Страница 81: ......
Страница 100: ...Midas M 100 User Manual ...
Страница 104: ...The certificate should be reinstalled when the IP address is changed Midas M 104 User Manual ...
Страница 109: ... 2019 ...