background image

M200-102-01

9

I56-6576-001

Turn the sensor head anti-clockwise to remove from base (and 

clockwise to relocate). Do 

NOT

 interchange the devices and do 

NOT

 

alter the rotary address switch settings on the sensors.  If replacing a 

sensor, ensure that the address set on the new sensor is the same as 

on the sensor being replaced. Use 

ONLY

 model number 

F-SEN-MI

 as 

a replacement sensor.

WARNING

Using compressed air to clean the pipe system

High pressure air flushed through the system could damage the 

fan, ensure that the FAAST LT-200 unit is sealed or detached from 

the system before commencing this procedure.

 

USB Connection

PC connectivity is provided by an on board USB 

B

 port located centrally 

between  the  filter  and  the  sensor  cover  (see  Figure  9  displayed 

earlier in the guide). The USB interface allows access to the PipeIQ 

application software running on a PC.

Note:  The  USB  connecting  cable  should  be  removed  during 

normal operation

.

Changing Default Settings / Verifying a Pipe Layout Design

To change any of the default options, or to use the pipe layout design 

function, it will be necessary to connect the detector to a PC/laptop 

with the PipeIQ software installed (version 2.9.1 or higher). For more 

complex designs using increased functionality (experienced users 

only) see the 

FAAST LT-200 Advanced Setup and Control Guide

 for 

further information.

P

ipe

IQ

 SOFTWARE

The PipeIQ software is supplied on a USB pen stick with the device, 

or can be downloaded from www.faast-detection.com. 

For the FAAST 

LT-200, it is necessary to use PipeIQ version 2.9.1 or higher.

Note 1:

 It is strongly recommended that some form of training is 

taken before using any version of PipeIQ (contact your distributor 

for information on this)

. The information provided here is only a brief 

introduction.

Note 2:

 To connect a FAAST LT-200 to a PC using the USB port, the 

PipeIQ software must be running on the PC and the device must be in 

Maintenance

 mode (See 

Password Sequence to Enter Maintenance 

Mode

 section previously).

Connecting a PC to a FAAST LT-200 Device for the First Time

Minimum System Requirements

Microsoft Windows Vista, 7, 8 or 10, XP - SP3 (not recommended). 

1 GB of RAM.

Graphics hardware with 128 MB of memory and support for OpenGL 

2.0 or later.
5 GB of free hard disc space

When the PipeIQ installation is complete:

1)  With PipeIQ open on the PC and the device in 

Maintenance

 mode, 

open the device front door by releasing the two Phillips screws. 

2)  Connect a USB cable from the internal port in the centre of the 

device to a spare USB port on the PC (make sure that the USB 

connector is pushed fully into the FAAST LT-200 port until it clicks). 

The device will now be in 

Remote Maintenance

 mode.

  The USB connection must be made within 5 minutes of entering 

the 

Maintenance

 mode password.

 

The first time a PC running PipeIQ is connected to a FAAST LT-200 

device, the USB port drivers will be installed.

3)  In PipeIQ, open the project file (.mdf file) that is associated with 

the FAAST LT-200 device being used. If no project file has been 

created yet, click on 

New

 and create a new project. Accept the 

PipeIQ disclaimer, select the measurement units, device type and 

number of channels. 

Make sure that the device type selected 

matches the type of FAAST LT-200 device being used

. The 

project will assume the factory default configuration for a device.

4)  In the Left Hand pane of PipeIQ, left click on the FAAST LT-200 

device in the system tree to highlight it. Right click on the FAAST 

LT-200 icon in the left hand pane to reveal the menu. Click on 

Connect Device

  Note that to use the full range of connection options, a user must 

be connected to the FAAST LT-200 device as an 

Administrator

Tick the 

Admin

 box and enter the 

Administrator

 password to 

access these extra commands. The 

Administrator

 password is the 

same as the 

Remote Maintenance

 password (the default is 3111).

5)  Click on 

Connect

The detector is connected when a small green 

tick is indicated on the device icon. 

FAAST LT-200 Connected

 is 

shown at the bottom left corner of the screen.

6) Depending on what operations are required, select the 

Configuration

Design

 or 

Monitoring

 tab at the bottom of the screen 

as necessary.

For greater detail on using PipeIQ with the FAAST LT-200 see the 

FAAST LT-200 Setup and Troubleshooting Guide

. For information on 

using the 

Configuration

Design

 and 

Monitoring

 tabs in PipeIQ, see the 

FAAST LT-200 Advanced Setup and Control Guide.

Setting the Fan Speed

A default air velocity reference value is set into each FAAST LT-200 

unit before leaving the factory. This equates to an optimum air flow of 

approximately 45 l/min. Default high/low flow limit thresholds are set to 

guarantee a flow fault when the air flow is ±20% of the reference flow.

The FAAST LT-200 fan speed in each channel can be set to 

Auto

 or 

Manual 

control. Use Auto mode in normal operation.

EN54-20 : 2006

Class A B & C

Aspirating Smoke Detectors

0832  18

MI-FL2011EI-HS:  DOP-ASP031

MI-FL2012EI-HS:  DOP-ASP032

MI-FL2022EI-HS:  DOP-ASP033

Honeywell Morley-IAS

140 Waterside Road

Hamilton Industrial Estate

Leicester, LE5 1TN, UK

DoP Ref:

Honeywell Morley-IAS

140 Waterside Road

Hamilton Industrial Estate

Leicester.

LE5 1TN

UK

Содержание LT-200 MI-FL20 Series

Страница 1: ...he performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Quantity FAAST ...

Страница 2: ...NDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 Minimum clearance required from hinges to open door 35 mm Figure 1 Dimensions and Knock Outs PHYSICAL INSTALLATION Front Panel Labels The LT 200 MI FL01 is shipped without the front panel labels f...

Страница 3: ...should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS CLASS PIPE LENGTH m MAX No HOLES CH HOLE SIZES C 10...

Страница 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Страница 5: ... 7 NO Alarm Relay CH1 8 NC Alarm Relay CH2 T3 9 C Alarm Relay CH2 10 NO Alarm Relay CH2 11 NC Fault Relay CH1 T4 12 C Fault Relay CH1 13 NO Fault Relay CH1 14 NC Fault Relay AUX CH2 T5 15 C Fault Relay AUX CH2 16 NO Fault Relay AUX CH2 17 Sounder Output 1 47 k ohm EOL Resistor T6 18 Sounder Output 1 19 Sounder Output 2 47 k ohm EOL Resistor T7 20 Sounder Output 2 21 Configurable Input Reset Defaul...

Страница 6: ...this Note The sensors communicate with the fire panel through the loop connection whether the 24VDC power supply is on or not Module The module address is set by means of rotary decade address switches located behind the door of the unit Use a screwdriver to rotate the wheels to the desired address The selected address refers to channel 1 on 2 channel units the device assigns the next 1 module add...

Страница 7: ... ACTION WARNING OR TROUBLE COMMENT ACTION LOW FLOW 1 Blink Yellow Fault delay in progress Default is 60s general fault set at end of delay ON Yellow Low flow fault Check filter check pipe network for blockages INPUT 1 BLINK Yellow External input fault Not used with default settings SENSOR 2 BLINKS Yellow Sensor communication fault Check sensor addresses and installation replace sensor ASPIRATOR ON...

Страница 8: ... smoke The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the duration of the test Smoke pellets or matches can be used close to the sampling point to introduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do...

Страница 9: ...rt in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will be inst...

Страница 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Страница 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Страница 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Страница 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...

Отзывы: